Ballot Results
Comment: View Comment Results
Ballot Name:
2022-02 Modifications to TPL-001 and MOD-032 | Draft 1 MOD-032-2 AB 2 ST
Voting Start Date:
11/10/2023 12:01:00 AM
Voting End Date:
11/20/2023 8:00:00 PM
Ballot Type:
ST
Ballot Activity:
AB
Ballot Series:
2
Total # Votes:
249
Total Ballot Pool:
292
Quorum:
85.27
Quorum Established Date:
11/20/2023 3:10:51 PM
Weighted Segment Value:
39.52
Segment | Ballot Pool | Segment Weight | Affirmative Votes | Affirmative Fraction | Negative Votes w/ Comment | Negative Fraction w/ Comment | Negative Votes w/o Comment | Abstain | No Vote |
---|---|---|---|---|---|---|---|---|---|
Segment: 1 | 79 | 1 | 19 | 0.339 | 37 | 0.661 | 1 | 8 | 14 |
Segment: 2 | 7 | 0.7 | 5 | 0.5 | 2 | 0.2 | 0 | 0 | 0 |
Segment: 3 | 65 | 1 | 17 | 0.34 | 33 | 0.66 | 0 | 6 | 9 |
Segment: 4 | 15 | 0.9 | 3 | 0.3 | 6 | 0.6 | 0 | 2 | 4 |
Segment: 5 | 74 | 1 | 18 | 0.327 | 37 | 0.673 | 0 | 9 | 10 |
Segment: 6 | 44 | 1 | 9 | 0.265 | 25 | 0.735 | 0 | 5 | 5 |
Segment: 7 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Segment: 8 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 0 |
Segment: 9 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Segment: 10 | 7 | 0.4 | 3 | 0.3 | 1 | 0.1 | 0 | 2 | 1 |
Totals: | 292 | 6 | 74 | 2.371 | 141 | 3.629 | 1 | 33 | 43 |
Ballot Pool Members
Segment | Organization | Voter | Designated Proxy | Ballot | NERC Memo |
---|---|---|---|---|---|
5 | National Grid USA | Robin Berry | Negative | Third-Party Comments | |
5 | AEP | Thomas Foltz | Negative | Comments Submitted | |
1 | AEP - AEP Service Corporation | Dennis Sauriol | Negative | Comments Submitted | |
1 | Southern Company - Southern Company Services, Inc. | Matt Carden | Affirmative | N/A | |
6 | Southern Company - Southern Company Generation | Ron Carlsen | Affirmative | N/A | |
5 | Pattern Operators LP | George E Brown | Negative | Third-Party Comments | |
1 | International Transmission Company Holdings Corporation | Michael Moltane | Allie Gavin | Abstain | N/A |
6 | PPL - Louisville Gas and Electric Co. | Linn Oelker | Negative | Third-Party Comments | |
3 | Southern Company - Alabama Power Company | Joel Dembowski | Affirmative | N/A | |
5 | Southern Company - Southern Company Generation | Leslie Burke | Affirmative | N/A | |
1 | NextEra Energy - Florida Power and Light Co. | Silvia Mitchell | Abstain | N/A | |
1 | Allete - Minnesota Power, Inc. | Hillary Creurer | Negative | Comments Submitted | |
5 | NRG - NRG Energy, Inc. | Patricia Lynch | Affirmative | N/A | |
5 | AES - AES Corporation | Ruchi Shah | Negative | Comments Submitted | |
3 | Arkansas Electric Cooperative Corporation | Ayslynn Mcavoy | Abstain | N/A | |
1 | Tallahassee Electric (City of Tallahassee, FL) | Scott Langston | None | N/A | |
1 | Manitoba Hydro | Nazra Gladu | Negative | Comments Submitted | |
6 | Arkansas Electric Cooperative Corporation | Bruce Walkup | Abstain | N/A | |
1 | Western Area Power Administration | Ben Hammer | Negative | Comments Submitted | |
1 | Imperial Irrigation District | Jesus Sammy Alcaraz | Denise Sanchez | Abstain | N/A |
5 | Xcel Energy, Inc. | Gerry Huitt | Negative | Third-Party Comments | |
4 | FirstEnergy - FirstEnergy Corporation | Mark Garza | Negative | Comments Submitted | |
6 | NextEra Energy - Florida Power and Light Co. | Justin Welty | Abstain | N/A | |
6 | Public Utility District No. 1 of Chelan County | Anne Kronshage | Affirmative | N/A | |
1 | Xcel Energy, Inc. | Eric Barry | Negative | Third-Party Comments | |
1 | FirstEnergy - FirstEnergy Corporation | Theresa Ciancio | Negative | Comments Submitted | |
5 | Public Utility District No. 1 of Chelan County | Rebecca Zahler | Affirmative | N/A | |
1 | IDACORP - Idaho Power Company | Sean Steffensen | None | N/A | |
4 | Sacramento Municipal Utility District | Foung Mua | Tim Kelley | Negative | Comments Submitted |
3 | NextEra Energy - Florida Power and Light Co. | Karen Demos | None | N/A | |
5 | Austin Energy | Michael Dillard | Affirmative | N/A | |
5 | Greybeard Compliance Services, LLC | Mike Gabriel | Negative | Third-Party Comments | |
3 | OGE Energy - Oklahoma Gas and Electric Co. | Donald Hargrove | Negative | Third-Party Comments | |
4 | Austin Energy | Tony Hua | Affirmative | N/A | |
1 | Austin Energy | Thomas Standifur | Affirmative | N/A | |
5 | Choctaw Generation Limited Partnership, LLLP | Rob Watson | None | N/A | |
5 | Edison International - Southern California Edison Company | Selene Willis | Negative | Comments Submitted | |
3 | Sempra - San Diego Gas and Electric | Bryan Bennett | Affirmative | N/A | |
4 | North Carolina Electric Membership Corporation | Richard McCall | Scott Brame | Negative | Comments Submitted |
3 | North Carolina Electric Membership Corporation | Chris Dimisa | Scott Brame | Negative | Comments Submitted |
6 | Public Utility District No. 2 of Grant County, Washington | Mike Stussy | None | N/A | |
1 | Sempra - San Diego Gas and Electric | Mohamed Derbas | Affirmative | N/A | |
5 | Sempra - San Diego Gas and Electric | Jennifer Wright | Jennifer Lapaix | Affirmative | N/A |
1 | NB Power Corporation | Jeffrey Streifling | Affirmative | N/A | |
5 | Omaha Public Power District | Kayleigh Wilkerson | Negative | Third-Party Comments | |
1 | Omaha Public Power District | Doug Peterchuck | Negative | Third-Party Comments | |
5 | FirstEnergy - FirstEnergy Corporation | Matthew Augustin | Negative | Comments Submitted | |
3 | PNM Resources - Public Service Company of New Mexico | Amy Wesselkamper | Affirmative | N/A | |
5 | Duke Energy | Dale Goodwine | Negative | Third-Party Comments | |
1 | Santee Cooper | Chris Wagner | None | N/A | |
6 | OGE Energy - Oklahoma Gas and Electric Co. | Ashley F Stringer | Negative | Third-Party Comments | |
3 | Santee Cooper | Vicky Budreau | None | N/A | |
6 | Santee Cooper | Marty Watson | None | N/A | |
5 | Santee Cooper | Carey Salisbury | None | N/A | |
1 | Pacific Gas and Electric Company | Marco Rios | Michael Johnson | Abstain | N/A |
6 | Portland General Electric Co. | Stefanie Burke | None | N/A | |
1 | Portland General Electric Co. | Brooke Jockin | None | N/A | |
6 | Tennessee Valley Authority | Armando Rodriguez | Negative | Third-Party Comments | |
3 | Tennessee Valley Authority | Ian Grant | Negative | Third-Party Comments | |
5 | Tennessee Valley Authority | Nehtisha Rollis | Negative | Third-Party Comments | |
1 | Tennessee Valley Authority | David Plumb | Negative | Third-Party Comments | |
6 | FirstEnergy - FirstEnergy Corporation | Stacey Sheehan | Negative | Comments Submitted | |
5 | New York Power Authority | Zahid Qayyum | Negative | Comments Submitted | |
3 | Manitoba Hydro | Mike Smith | Negative | Comments Submitted | |
6 | Salt River Project | Timothy Singh | Israel Perez | Negative | Comments Submitted |
3 | New York Power Authority | David Rivera | Negative | Comments Submitted | |
10 | Texas Reliability Entity, Inc. | Rachel Coyne | Affirmative | N/A | |
5 | Dairyland Power Cooperative | Tommy Drea | Negative | Third-Party Comments | |
6 | Dominion - Dominion Resources, Inc. | Sean Bodkin | Negative | Comments Submitted | |
6 | Con Ed - Consolidated Edison Co. of New York | Michael Foley | Negative | Third-Party Comments | |
5 | Imperial Irrigation District | Tino Zaragoza | Denise Sanchez | Abstain | N/A |
10 | Northeast Power Coordinating Council | Gerry Dunbar | Abstain | N/A | |
3 | Dominion - Dominion Virginia Power | Bill Garvey | Negative | Comments Submitted | |
1 | Dairyland Power Cooperative | Karrie Schuldt | Negative | Third-Party Comments | |
3 | Con Ed - Consolidated Edison Co. of New York | Peter Yost | Negative | Third-Party Comments | |
1 | Lakeland Electric | Larry Watt | None | N/A | |
1 | Dominion - Dominion Virginia Power | Elizabeth Weber | Negative | Comments Submitted | |
1 | Sunflower Electric Power Corporation | Paul Mehlhaff | None | N/A | |
3 | Salt River Project | Mathew Weber | Israel Perez | Negative | Comments Submitted |
5 | Lincoln Electric System | Brittany Millard | Negative | Third-Party Comments | |
1 | Lincoln Electric System | Josh Johnson | None | N/A | |
3 | Lincoln Electric System | Sam Christensen | Negative | Comments Submitted | |
5 | Avista - Avista Corporation | Glen Farmer | Affirmative | N/A | |
1 | CenterPoint Energy Houston Electric, LLC | Daniela Hammons | Negative | Comments Submitted | |
1 | Avista - Avista Corporation | Mike Magruder | Affirmative | N/A | |
2 | California ISO | Darcy O'Connell | Val Neiberger | Affirmative | N/A |
3 | Exelon | Kinte Whitehead | Negative | Comments Submitted | |
1 | Exelon | Daniel Gacek | Negative | Comments Submitted | |
1 | Long Island Power Authority | Isidoro Behar | Abstain | N/A | |
6 | Lincoln Electric System | Eric Ruskamp | Negative | Comments Submitted | |
3 | FirstEnergy - FirstEnergy Corporation | Aaron Ghodooshim | Negative | Comments Submitted | |
10 | Western Electricity Coordinating Council | Steven Rueckert | Negative | Comments Submitted | |
5 | Oglethorpe Power Corporation | Donna Johnson | Negative | Third-Party Comments | |
5 | Tri-State G and T Association, Inc. | Sergio Banuelos | Negative | Comments Submitted | |
1 | Oncor Electric Delivery | Byron Booker | Kacie Fischer | Negative | Comments Submitted |
5 | Cowlitz County PUD | Deanna Carlson | Affirmative | N/A | |
6 | Seminole Electric Cooperative, Inc. | Bret Galbraith | None | N/A | |
2 | Electric Reliability Council of Texas, Inc. | Kennedy Meier | Affirmative | N/A | |
1 | Berkshire Hathaway Energy - MidAmerican Energy Co. | Terry Harbour | Negative | Comments Submitted | |
6 | Black Hills Corporation | Claudine Bates | Negative | Comments Submitted | |
1 | Black Hills Corporation | Micah Runner | Carly Miller | Negative | Comments Submitted |
3 | Ameren - Ameren Services | David Jendras Sr | Negative | Comments Submitted | |
5 | Black Hills Corporation | Sheila Suurmeier | Negative | Comments Submitted | |
6 | Ameren - Ameren Services | Robert Quinlivan | Negative | Comments Submitted | |
1 | Ameren - Ameren Services | Tamara Evey | Negative | Comments Submitted | |
5 | Ameren - Ameren Missouri | Sam Dwyer | None | N/A | |
5 | Evergy | Jeremy Harris | Alan Kloster | Negative | Comments Submitted |
6 | Entergy | Julie Hall | Negative | Comments Submitted | |
3 | Public Utility District No. 1 of Chelan County | Joyce Gundry | Affirmative | N/A | |
2 | ISO New England, Inc. | John Pearson | Affirmative | N/A | |
2 | PJM Interconnection, L.L.C. | Thomas Foster | Elizabeth Davis | Negative | Third-Party Comments |
5 | Dominion - Dominion Resources, Inc. | Anna Salmon | None | N/A | |
3 | Southern Indiana Gas and Electric Co. | Ryan Snyder | Abstain | N/A | |
5 | Talen Generation, LLC | Donald Lock | Negative | Comments Submitted | |
6 | Southern Indiana Gas and Electric Co. | Kati Barr | Abstain | N/A | |
5 | Southern Indiana Gas and Electric Co. | Larry Rogers | Abstain | N/A | |
1 | PNM Resources - Public Service Company of New Mexico | Lynn Goldstein | Affirmative | N/A | |
6 | Evergy | Tiffany Lake | Alan Kloster | Negative | Comments Submitted |
5 | Bonneville Power Administration | Christopher Siewert | Affirmative | N/A | |
1 | Evergy | Kevin Frick | Alan Kloster | Negative | Comments Submitted |
6 | Austin Energy | Imane Mrini | Affirmative | N/A | |
6 | NiSource - Northern Indiana Public Service Co. | Joseph OBrien | Negative | Comments Submitted | |
3 | Austin Energy | Lovita Griffin | Affirmative | N/A | |
1 | Duke Energy | Katherine Street | None | N/A | |
5 | Vistra Energy | Daniel Roethemeyer | David Vickers | Affirmative | N/A |
1 | Georgia Transmission Corporation | Greg Davis | Negative | Comments Submitted | |
4 | Georgia System Operations Corporation | Katrina Lyons | None | N/A | |
1 | National Grid USA | Michael Jones | Negative | Third-Party Comments | |
4 | Public Utility District No. 1 of Snohomish County | John D. Martinsen | Affirmative | N/A | |
1 | Minnkota Power Cooperative Inc. | Theresa Allard | Andy Fuhrman | Negative | Comments Submitted |
3 | Great River Energy | Michael Brytowski | Negative | Third-Party Comments | |
6 | Duke Energy | John Sturgeon | None | N/A | |
5 | Sacramento Municipal Utility District | Ryder Couch | Tim Kelley | Negative | Comments Submitted |
3 | Avista - Avista Corporation | Robert Follini | Affirmative | N/A | |
1 | Tacoma Public Utilities (Tacoma, WA) | John Merrell | Jennie Wike | Affirmative | N/A |
1 | Public Utility District No. 1 of Chelan County | Diane E Landry | Affirmative | N/A | |
1 | Associated Electric Cooperative, Inc. | Mark Riley | None | N/A | |
5 | CMS Energy - Consumers Energy Company | David Greyerbiehl | None | N/A | |
1 | Arizona Electric Power Cooperative, Inc. | Jennifer Bray | Negative | Comments Submitted | |
3 | CMS Energy - Consumers Energy Company | Karl Blaszkowski | None | N/A | |
6 | Northern California Power Agency | Dennis Sismaet | Negative | Comments Submitted | |
5 | Orlando Utilities Commission | Dania Colon | None | N/A | |
6 | Sacramento Municipal Utility District | Charles Norton | Tim Kelley | Negative | Comments Submitted |
5 | Berkshire Hathaway - NV Energy | Dwanique Spiller | Negative | Comments Submitted | |
5 | NB Power Corporation - New Brunswick Power Transmission Corporation | Fon Hiew | Affirmative | N/A | |
1 | Eversource Energy | Joshua London | Negative | Comments Submitted | |
1 | Salt River Project | Sarah Blankenship | Israel Perez | Negative | Comments Submitted |
6 | Constellation | Kimberly Turco | Negative | Comments Submitted | |
1 | OGE Energy - Oklahoma Gas and Electric Co. | Terri Pyle | Negative | Third-Party Comments | |
5 | Constellation | Alison MacKellar | Negative | Comments Submitted | |
1 | Bonneville Power Administration | Kamala Rogers-Holliday | Affirmative | N/A | |
4 | CMS Energy - Consumers Energy Company | Aric Root | Negative | Third-Party Comments | |
5 | OGE Energy - Oklahoma Gas and Electric Co. | Patrick Wells | Negative | Third-Party Comments | |
5 | Los Angeles Department of Water and Power | Glenn Barry | Abstain | N/A | |
2 | Midcontinent ISO, Inc. | Bobbi Welch | Affirmative | N/A | |
3 | Los Angeles Department of Water and Power | Tony Skourtas | Abstain | N/A | |
1 | Tri-State G and T Association, Inc. | Donna Wood | Negative | Comments Submitted | |
6 | AEP | Mathew Miller | Negative | Comments Submitted | |
3 | AEP | Kent Feliks | Negative | Comments Submitted | |
1 | Pedernales Electric Cooperative, Inc. | Bradley Collard | Abstain | N/A | |
3 | Duke Energy - Florida Power Corporation | Marcelo Pesantez | None | N/A | |
2 | Southwest Power Pool, Inc. (RTO) | Joshua Phillips | Shannon Mickens | Negative | Comments Submitted |
5 | DTE Energy - Detroit Edison Company | Adrian Raducea | Negative | Comments Submitted | |
10 | ReliabilityFirst | Lindsey Mannion | Stephen Whaite | Abstain | N/A |
5 | Lower Colorado River Authority | Teresa Krabe | Affirmative | N/A | |
5 | Tacoma Public Utilities (Tacoma, WA) | Ozan Ferrin | Jennie Wike | Affirmative | N/A |
6 | Bonneville Power Administration | Tanner Brier | Affirmative | N/A | |
6 | Omaha Public Power District | Shonda McCain | Negative | Third-Party Comments | |
1 | Balancing Authority of Northern California | Kevin Smith | Tim Kelley | Negative | Comments Submitted |
6 | Lakeland Electric | Paul Shipps | Abstain | N/A | |
8 | Florida Reliability Coordinating Council – Member Services Division | Vince Ordax | Abstain | N/A | |
3 | Tacoma Public Utilities (Tacoma, WA) | John Nierenberg | Jennie Wike | Affirmative | N/A |
3 | Eversource Energy | Vicki O'Leary | Negative | Comments Submitted | |
6 | Manitoba Hydro | Kelly Bertholet | Negative | Comments Submitted | |
3 | Sacramento Municipal Utility District | Nicole Looney | Tim Kelley | Negative | Comments Submitted |
4 | Arkansas Electric Cooperative Corporation | Jenni Sudduth | Abstain | N/A | |
3 | NiSource - Northern Indiana Public Service Co. | Steven Taddeucci | Negative | Comments Submitted | |
1 | Glencoe Light and Power Commission | Terry Volkmann | Negative | Third-Party Comments | |
4 | Tacoma Public Utilities (Tacoma, WA) | Hien Ho | Jennie Wike | Affirmative | N/A |
3 | Xcel Energy, Inc. | Nicholas Friebel | Negative | Third-Party Comments | |
3 | Berkshire Hathaway Energy - MidAmerican Energy Co. | Joseph Amato | Negative | Comments Submitted | |
1 | Hydro One Networks, Inc. | Emma Halilovic | None | N/A | |
1 | Arkansas Electric Cooperative Corporation | Emily Corley | Abstain | N/A | |
1 | SaskPower | Wayne Guttormson | Affirmative | N/A | |
5 | PSEG Nuclear LLC | Tim Kucey | Negative | Third-Party Comments | |
5 | APS - Arizona Public Service Co. | Andrew Smith | Affirmative | N/A | |
1 | APS - Arizona Public Service Co. | Daniela Atanasovski | Affirmative | N/A | |
10 | Midwest Reliability Organization | Mark Flanary | Affirmative | N/A | |
6 | APS - Arizona Public Service Co. | Marcus Bortman | Affirmative | N/A | |
1 | JEA | Joseph McClung | Affirmative | N/A | |
3 | APS - Arizona Public Service Co. | Jessica Lopez | Affirmative | N/A | |
2 | Independent Electricity System Operator | Helen Lainis | Affirmative | N/A | |
3 | Seminole Electric Cooperative, Inc. | Marc Sedor | None | N/A | |
1 | New York Power Authority | Daniel Valle | Negative | Comments Submitted | |
6 | Muscatine Power and Water | Nicholas Burns | Negative | Third-Party Comments | |
3 | Muscatine Power and Water | Seth Shoemaker | Negative | Third-Party Comments | |
1 | Central Iowa Power Cooperative | Kevin Lyons | Negative | Third-Party Comments | |
1 | Hydro-Quebec (HQ) | Nicolas Turcotte | Affirmative | N/A | |
1 | Muscatine Power and Water | Andrew Kurriger | Negative | Third-Party Comments | |
3 | Nebraska Public Power District | Tony Eddleman | Negative | Third-Party Comments | |
1 | NiSource - Northern Indiana Public Service Co. | Alison Nickells | None | N/A | |
3 | DTE Energy - Detroit Edison Company | Marvin Johnson | None | N/A | |
6 | New York Power Authority | Shelly Dineen | Negative | Comments Submitted | |
3 | Owensboro Municipal Utilities | William Berry | Abstain | N/A | |
1 | Great River Energy | Gordon Pietsch | Negative | Third-Party Comments | |
1 | BC Hydro and Power Authority | Adrian Andreoiu | Negative | Comments Submitted | |
5 | Nebraska Public Power District | Ronald Bender | Kevin Schawang | Negative | Third-Party Comments |
5 | Seminole Electric Cooperative, Inc. | Melanie Wong | None | N/A | |
5 | Manitoba Hydro | Kristy-Lee Young | Negative | Comments Submitted | |
10 | New York State Reliability Council | Wesley Yeomans | None | N/A | |
5 | BC Hydro and Power Authority | Helen Hamilton Harding | Negative | Comments Submitted | |
5 | Ontario Power Generation Inc. | Constantin Chitescu | Affirmative | N/A | |
5 | Lakeland Electric | Carmen Rodriguez | Abstain | N/A | |
5 | NiSource - Northern Indiana Public Service Co. | Kathryn Tackett | Negative | Comments Submitted | |
5 | North Carolina Electric Membership Corporation | Reid Cashion | Scott Brame | Negative | Comments Submitted |
3 | Evergy | Marcus Moor | Alan Kloster | Negative | Comments Submitted |
3 | Lakeland Electric | Steven Marshall | Abstain | N/A | |
1 | Entergy | Brian Lindsey | Kristen Long | Negative | Comments Submitted |
4 | Electricities of North Carolina | Marcus Freeman | None | N/A | |
5 | Public Utility District No. 2 of Grant County, Washington | Nikkee Hebdon | Abstain | N/A | |
3 | Entergy | James Keele | Negative | Comments Submitted | |
5 | Salt River Project | Thomas Johnson | Israel Perez | Negative | Comments Submitted |
1 | Basin Electric Power Cooperative | David Rudolph | None | N/A | |
1 | Los Angeles Department of Water and Power | faranak sarbaz | None | N/A | |
5 | Pacific Gas and Electric Company | Frank Lee | Michael Johnson | Abstain | N/A |
3 | Omaha Public Power District | David Heins | Negative | Third-Party Comments | |
6 | NRG - NRG Energy, Inc. | Martin Sidor | Affirmative | N/A | |
3 | MGE Energy - Madison Gas and Electric Co. | Ronald Bauer | Negative | Third-Party Comments | |
3 | WEC Energy Group, Inc. | Christine Kane | Negative | Comments Submitted | |
3 | Colorado Springs Utilities | Hillary Dobson | None | N/A | |
5 | Colorado Springs Utilities | Jeffrey Icke | None | N/A | |
6 | WEC Energy Group, Inc. | David Boeshaar | Negative | Comments Submitted | |
3 | Anaheim Public Utilities Dept. | Agustin Torres | None | N/A | |
5 | WEC Energy Group, Inc. | Clarice Zellmer | Negative | Comments Submitted | |
4 | DTE Energy | Patricia Ireland | None | N/A | |
1 | U.S. Bureau of Reclamation | Richard Jackson | Abstain | N/A | |
5 | Florida Municipal Power Agency | Chris Gowder | LaKenya Vannorman | None | N/A |
1 | Colorado Springs Utilities | Corey Walker | None | N/A | |
3 | National Grid USA | Brian Shanahan | Negative | Third-Party Comments | |
6 | Powerex Corporation | Raj Hundal | Negative | Third-Party Comments | |
3 | Pacific Gas and Electric Company | Sandra Ellis | Michael Johnson | Abstain | N/A |
3 | PPL - Louisville Gas and Electric Co. | James Frank | Negative | Third-Party Comments | |
4 | Public Utility District No. 2 of Grant County, Washington | Karla Weaver | Abstain | N/A | |
6 | Imperial Irrigation District | Diana Torres | Denise Sanchez | Abstain | N/A |
4 | WEC Energy Group, Inc. | Matthew Beilfuss | Negative | Comments Submitted | |
3 | Florida Municipal Power Agency | Navid Nowakhtar | LaKenya Vannorman | None | N/A |
5 | Associated Electric Cooperative, Inc. | Chuck Booth | Affirmative | N/A | |
5 | JEA | John Babik | Affirmative | N/A | |
1 | Lower Colorado River Authority | Matt Lewis | Affirmative | N/A | |
1 | Public Utility District No. 1 of Snohomish County | Alyssia Rhoads | Affirmative | N/A | |
3 | Snohomish County PUD No. 1 | Holly Chaney | Affirmative | N/A | |
5 | Great River Energy | Jacalynn Bentz | Negative | Third-Party Comments | |
6 | Snohomish County PUD No. 1 | John Liang | Affirmative | N/A | |
4 | Illinois Municipal Electric Agency | Mary Ann Todd | None | N/A | |
3 | Black Hills Corporation | Josh Combs | Negative | Comments Submitted | |
1 | OTP - Otter Tail Power Company | Charles Wicklund | Negative | Third-Party Comments | |
5 | OTP - Otter Tail Power Company | Stacy Wahlund | Negative | Third-Party Comments | |
3 | OTP - Otter Tail Power Company | Wendi Olson | Negative | Third-Party Comments | |
3 | NW Electric Power Cooperative, Inc. | Heath Henry | Affirmative | N/A | |
3 | Associated Electric Cooperative, Inc. | Todd Bennett | Affirmative | N/A | |
1 | KAMO Electric Cooperative | Micah Breedlove | Affirmative | N/A | |
3 | KAMO Electric Cooperative | Tony Gott | Affirmative | N/A | |
3 | Sho-Me Power Electric Cooperative | Jarrod Murdaugh | Affirmative | N/A | |
1 | Northeast Missouri Electric Power Cooperative | Brett Douglas | Affirmative | N/A | |
3 | M and A Electric Power Cooperative | Stephen Pogue | Affirmative | N/A | |
1 | M and A Electric Power Cooperative | William Price | Affirmative | N/A | |
1 | N.W. Electric Power Cooperative, Inc. | Mark Ramsey | Affirmative | N/A | |
5 | Hydro-Quebec (HQ) | Junji Yamaguchi | Affirmative | N/A | |
5 | U.S. Bureau of Reclamation | Wendy Kalidass | Abstain | N/A | |
1 | Platte River Power Authority | Marissa Archie | Negative | No Comment Submitted | |
5 | Public Utility District No. 1 of Snohomish County | Becky Burden | Affirmative | N/A | |
3 | Tri-State G and T Association, Inc. | Ryan Walter | Negative | Comments Submitted | |
3 | BC Hydro and Power Authority | Alan Xu | Negative | Comments Submitted | |
5 | Entergy - Entergy Services, Inc. | Gail Golden | Negative | Comments Submitted | |
3 | Central Electric Power Cooperative (Missouri) | Adam Weber | Affirmative | N/A | |
3 | Buckeye Power, Inc. | Carl Spaetzel | Ryan Strom | Negative | Comments Submitted |
6 | Associated Electric Cooperative, Inc. | Brian Ackermann | Affirmative | N/A | |
5 | Enel Green Power | Natalie Johnson | None | N/A | |
5 | Buckeye Power, Inc. | Kevin Zemanek | Ryan Strom | Negative | Comments Submitted |
5 | Tallahassee Electric (City of Tallahassee, FL) | Karen Weaver | Abstain | N/A | |
4 | Buckeye Power, Inc. | Jason Procuniar | Ryan Strom | Negative | Comments Submitted |
1 | Sacramento Municipal Utility District | Wei Shao | Tim Kelley | Negative | Comments Submitted |
1 | Nebraska Public Power District | Jamison Cawley | Negative | Third-Party Comments | |
5 | Basin Electric Power Cooperative | Amanda Wangler | Negative | Third-Party Comments | |
1 | PPL Electric Utilities Corporation | Michelle McCartney Longo | Negative | Third-Party Comments | |
6 | Tacoma Public Utilities (Tacoma, WA) | Terry Gifford | Jennie Wike | Affirmative | N/A |
3 | Northeast Missouri Electric Power Cooperative | Skyler Wiegmann | Affirmative | N/A | |
10 | SERC Reliability Corporation | Dave Krueger | Affirmative | N/A | |
3 | JEA | Marilyn Williams | Affirmative | N/A | |
6 | Western Area Power Administration | Chrystal Dean | Negative | Comments Submitted | |
6 | Xcel Energy, Inc. | Steve Szablya | Negative | Third-Party Comments | |
5 | LS Power Development, LLC | C. A. Campbell | Abstain | N/A |