Ballot Name: 2021-06 Modifications to IRO-010 and TOP-003 IRO-010-5 FN 3 ST
Voting Start Date: 7/21/2023 10:15:00 AM
Voting End Date: 7/31/2023 8:00:00 PM
Ballot Type: ST
Ballot Activity: FN
Ballot Series: 3
Total # Votes: 247
Total Ballot Pool: 289
Quorum: 85.47
Quorum Established Date: 7/21/2023 11:12:25 AM
Weighted Segment Value: 76.36

Segment Ballot Pool Segment Weight Affirmative Votes Affirmative Fraction Negative Votes w/ Comment Negative Fraction w/ Comment Negative Votes w/o Comment Abstain No Vote
Segment: 1 80 1 43 0.662 22 0.338 0 6 9
Segment: 2 7 0.6 6 0.6 0 0 0 0 1
Segment: 3 64 1 34 0.68 16 0.32 0 4 10
Segment: 4 15 0.8 7 0.7 1 0.1 0 1 6
Segment: 5 70 1 41 0.707 17 0.293 0 3 9
Segment: 6 46 1 28 0.757 9 0.243 0 2 7
Segment: 7 0 0 0 0 0 0 0 0 0
Segment: 8 1 0 0 0 0 0 0 1 0
Segment: 9 0 0 0 0 0 0 0 0 0
Segment: 10 6 0.5 4 0.4 1 0.1 0 1 0
Totals: 289 5.9 163 4.505 66 1.395 0 18 42
Segment Organization Voter Designated Proxy Ballot NERC Memo
1 Allete - Minnesota Power, Inc. Hillary Creurer Negative N/A
5 AEP Thomas Foltz Affirmative N/A
6 AEP Mathew Miller Affirmative N/A
6 NRG - NRG Energy, Inc. Martin Sidor Affirmative N/A
5 Sacramento Municipal Utility District Pedro Juarez Tim Kelley Affirmative N/A
3 Arkansas Electric Cooperative Corporation Ayslynn Mcavoy Abstain N/A
1 AEP - AEP Service Corporation Dennis Sauriol Affirmative N/A
5 Oglethorpe Power Corporation Donna Johnson Affirmative N/A
6 Arkansas Electric Cooperative Corporation Bruce Walkup Abstain N/A
6 OGE Energy - Oklahoma Gas and Electric Co. Ashley F Stringer Negative N/A
5 Nebraska Public Power District Ronald Bender Negative N/A
1 Nebraska Public Power District Jamison Cawley Negative N/A
1 Manitoba Hydro Nazra Gladu Affirmative N/A
3 Pacific Gas and Electric Company Sandra Ellis Michael Johnson Abstain N/A
1 CenterPoint Energy Houston Electric, LLC Daniela Hammons Affirmative N/A
3 Georgia System Operations Corporation Scott McGough Affirmative N/A
1 Georgia Transmission Corporation Greg Davis Affirmative N/A
3 OGE Energy - Oklahoma Gas and Electric Co. Donald Hargrove Negative N/A
6 Dominion - Dominion Resources, Inc. Sean Bodkin None N/A
5 North Carolina Electric Membership Corporation Reid Cashion Scott Brame Affirmative N/A
5 Manitoba Hydro Kristy-Lee Young Affirmative N/A
1 Seminole Electric Cooperative, Inc. Kristine Ward Abstain N/A
1 National Grid USA Michael Jones Negative N/A
6 Manitoba Hydro Brandin Stoesz Affirmative N/A
3 Tennessee Valley Authority Ian Grant Affirmative N/A
3 North Carolina Electric Membership Corporation Chris Dimisa Scott Brame Affirmative N/A
4 North Carolina Electric Membership Corporation Richard McCall Scott Brame Affirmative N/A
6 Southern Indiana Gas and Electric Co. Kati Barr Affirmative N/A
6 Constellation Kimberly Turco Affirmative N/A
5 Great River Energy Jacalynn Bentz Affirmative N/A
4 FirstEnergy - FirstEnergy Corporation Mark Garza Affirmative N/A
5 Xcel Energy, Inc. Gerry Huitt Joseph Gatten Affirmative N/A
1 NextEra Energy - Florida Power and Light Co. Silvia Mitchell Affirmative N/A
6 PSEG - PSEG Energy Resources and Trade LLC Laura Wu Negative N/A
1 FirstEnergy - FirstEnergy Corporation Theresa Ciancio Affirmative N/A
2 Independent Electricity System Operator Helen Lainis Affirmative N/A
5 Con Ed - Consolidated Edison Co. of New York Michelle Pagano Negative N/A
1 NB Power Corporation Jeffrey Streifling Affirmative N/A
6 Public Utility District No. 2 of Grant County, Washington Mike Stussy None N/A
1 Con Ed - Consolidated Edison Co. of New York Dermot Smyth Negative N/A
1 Long Island Power Authority Isidoro Behar Abstain N/A
6 Xcel Energy, Inc. Steve Szablya None N/A
5 Edison International - Southern California Edison Company Selene Willis None N/A
5 APS - Arizona Public Service Co. Andrew Smith Affirmative N/A
5 Lower Colorado River Authority Teresa Krabe Affirmative N/A
5 AES - AES Corporation Ruchi Shah Negative N/A
1 Pacific Gas and Electric Company Marco Rios Michael Johnson Abstain N/A
1 OGE Energy - Oklahoma Gas and Electric Co. Terri Pyle Negative N/A
5 OGE Energy - Oklahoma Gas and Electric Co. Patrick Wells Negative N/A
3 Edison International - Southern California Edison Company Romel Aquino None N/A
1 Xcel Energy, Inc. Eric Barry Affirmative N/A
5 NRG - NRG Energy, Inc. Patricia Lynch Affirmative N/A
5 Constellation Alison MacKellar Affirmative N/A
1 Dominion - Dominion Virginia Power Steven Belle None N/A
5 Southern Indiana Gas and Electric Co. Larry Rogers Affirmative N/A
5 Cowlitz County PUD Deanna Carlson None N/A
4 Oklahoma Municipal Power Authority Michael Watt None N/A
3 APS - Arizona Public Service Co. Jessica Lopez Affirmative N/A
3 Dominion - Dominion Virginia Power Victoria Crider None N/A
6 Platte River Power Authority Sabrina Martz Affirmative N/A
5 Omaha Public Power District Kayleigh Wilkerson Negative N/A
6 APS - Arizona Public Service Co. Marcus Bortman Affirmative N/A
3 Con Ed - Consolidated Edison Co. of New York Peter Yost Negative N/A
1 Muscatine Power and Water Andrew Kurriger Negative N/A
3 Platte River Power Authority Richard Kiess Affirmative N/A
3 FirstEnergy - FirstEnergy Corporation Aaron Ghodooshim Affirmative N/A
1 APS - Arizona Public Service Co. Daniela Atanasovski Affirmative N/A
1 Lakeland Electric Larry Watt None N/A
3 Seminole Electric Cooperative, Inc. Marc Sedor Abstain N/A
6 Seminole Electric Cooperative, Inc. Bret Galbraith Abstain N/A
5 Seminole Electric Cooperative, Inc. Melanie Wong None N/A
1 Salt River Project Laura Somak Affirmative N/A
6 Edison International - Southern California Edison Company Stephanie Kenny None N/A
3 Nebraska Public Power District Tony Eddleman Negative N/A
6 FirstEnergy - FirstEnergy Corporation Stacey Sheehan Affirmative N/A
4 Sacramento Municipal Utility District Foung Mua Tim Kelley Affirmative N/A
6 NextEra Energy - Florida Power and Light Co. Justin Welty Affirmative N/A
1 Omaha Public Power District Doug Peterchuck Negative N/A
5 U.S. Bureau of Reclamation Wendy Kalidass Affirmative N/A
3 Bonneville Power Administration Ron Sporseen None N/A
3 PSEG - Public Service Electric and Gas Co. Christopher Murphy Negative N/A
5 Bonneville Power Administration Juergen Bermejo Negative N/A
3 Xcel Energy, Inc. Nicholas Friebel Affirmative N/A
1 Tennessee Valley Authority David Plumb Affirmative N/A
3 Great River Energy Michael Brytowski Affirmative N/A
3 Snohomish County PUD No. 1 Holly Chaney Affirmative N/A
3 Tri-State G and T Association, Inc. Ryan Walter None N/A
6 Omaha Public Power District Shonda McCain Negative N/A
1 Western Area Power Administration Ben Hammer Kimberly Bentley Negative N/A
1 Lincoln Electric System Josh Johnson None N/A
2 Electric Reliability Council of Texas, Inc. Kennedy Meier Affirmative N/A
6 Lincoln Electric System Eric Ruskamp Negative N/A
1 Great River Energy Gordon Pietsch Affirmative N/A
6 Con Ed - Consolidated Edison Co. of New York Jason Chandler Negative N/A
6 Cleco Corporation Robert Hirchak None N/A
6 Duke Energy John Sturgeon Affirmative N/A
3 Sempra - San Diego Gas and Electric Bryan Bennett Affirmative N/A
1 Duke Energy Katherine Street Affirmative N/A
1 Imperial Irrigation District Jesus Sammy Alcaraz Denise Sanchez Affirmative N/A
1 Sempra - San Diego Gas and Electric Mohamed Derbas Affirmative N/A
5 Sempra - San Diego Gas and Electric Jennifer Wright Affirmative N/A
5 Pacific Gas and Electric Company Tyler Brun Michael Johnson Abstain N/A
1 Central Iowa Power Cooperative Kevin Lyons Negative N/A
6 Imperial Irrigation District Diana Torres Denise Sanchez Affirmative N/A
3 Lincoln Electric System Sam Christensen Negative N/A
5 Lincoln Electric System Brittany Millard Negative N/A
1 Minnkota Power Cooperative Inc. Theresa Allard Andy Fuhrman Negative N/A
1 Arizona Electric Power Cooperative, Inc. Jennifer Bray Affirmative N/A
10 Texas Reliability Entity, Inc. Rachel Coyne Affirmative N/A
1 Associated Electric Cooperative, Inc. Mark Riley Affirmative N/A
1 Public Utility District No. 1 of Snohomish County Alyssia Rhoads Affirmative N/A
3 Duke Energy - Florida Power Corporation Marcelo Pesantez Affirmative N/A
2 PJM Interconnection, L.L.C. Thomas Foster Elizabeth Davis Affirmative N/A
5 Tri-State G and T Association, Inc. Sergio Banuelos Affirmative N/A
1 BC Hydro and Power Authority Adrian Andreoiu Affirmative N/A
1 Tri-State G and T Association, Inc. Donna Wood Affirmative N/A
6 Western Area Power Administration Chrystal Dean Affirmative N/A
3 Imperial Irrigation District George Kirschner Denise Sanchez Affirmative N/A
1 New York Power Authority Daniel Valle Affirmative N/A
5 Greybeard Compliance Services, LLC Mike Gabriel Negative N/A
5 Dominion - Dominion Resources, Inc. Anna Salmon None N/A
3 Owensboro Municipal Utilities William Berry Affirmative N/A
3 Salt River Project Mathew Weber Affirmative N/A
1 Exelon Daniel Gacek Negative N/A
6 Salt River Project Timothy Singh Affirmative N/A
5 Salt River Project Thomas Johnson Affirmative N/A
5 FirstEnergy - FirstEnergy Corporation Robert Loy Affirmative N/A
6 Entergy Julie Hall Affirmative N/A
1 Berkshire Hathaway Energy - MidAmerican Energy Co. Terry Harbour Negative N/A
10 SERC Reliability Corporation Dave Krueger Affirmative N/A
1 Public Utility District No. 1 of Chelan County Diane E Landry Affirmative N/A
5 Duke Energy Dale Goodwine Affirmative N/A
5 Public Utility District No. 1 of Chelan County Rebecca Wickel Affirmative N/A
3 Public Utility District No. 1 of Chelan County Joyce Gundry Affirmative N/A
1 PNM Resources - Public Service Company of New Mexico Lynn Goldstein Negative N/A
3 PNM Resources - Public Service Company of New Mexico Amy Wesselkamper Negative N/A
6 Evergy Jennifer Flandermeyer Alan Kloster Affirmative N/A
1 Hydro One Networks, Inc. Emma Halilovic Negative N/A
1 Southern Company - Southern Company Services, Inc. Matt Carden Negative N/A
3 Southern Company - Alabama Power Company Joel Dembowski Negative N/A
6 Southern Company - Southern Company Generation Ron Carlsen Negative N/A
3 Avista - Avista Corporation Robert Follini Affirmative N/A
6 Public Utility District No. 1 of Chelan County Robert Witham Affirmative N/A
3 Exelon Kinte Whitehead Negative N/A
3 Entergy James Keele Affirmative N/A
5 Entergy - Entergy Services, Inc. Gail Golden Affirmative N/A
3 Muscatine Power and Water Seth Shoemaker Negative N/A
1 Entergy Brian Lindsey Affirmative N/A
5 Imperial Irrigation District Tino Zaragoza Denise Sanchez Affirmative N/A
2 California ISO Darcy O'Connell Affirmative N/A
6 Muscatine Power and Water Nicholas Burns Negative N/A
3 Associated Electric Cooperative, Inc. Todd Bennett Affirmative N/A
1 N.W. Electric Power Cooperative, Inc. Mark Ramsey Affirmative N/A
3 Sho-Me Power Electric Cooperative Jarrod Murdaugh Affirmative N/A
3 Central Electric Power Cooperative (Missouri) Adam Weber None N/A
3 NW Electric Power Cooperative, Inc. Heath Henry Affirmative N/A
3 Northeast Missouri Electric Power Cooperative Skyler Wiegmann None N/A
1 Glencoe Light and Power Commission Terry Volkmann Negative N/A
3 Berkshire Hathaway Energy - MidAmerican Energy Co. Joseph Amato Negative N/A
1 Platte River Power Authority Marissa Archie Affirmative N/A
3 M and A Electric Power Cooperative Gary Dollins Affirmative N/A
3 CMS Energy - Consumers Energy Company Karl Blaszkowski None N/A
5 Southern Company - Southern Company Generation Leslie Burke Negative N/A
1 IDACORP - Idaho Power Company Sean Steffensen Affirmative N/A
3 New York Power Authority Richard Machado Affirmative N/A
6 Powerex Corporation Raj Hundal Affirmative N/A
5 Choctaw Generation Limited Partnership, LLLP Rob Watson Negative N/A
6 Black Hills Corporation Rachel Schuldt Affirmative N/A
5 National Grid USA Robin Berry Negative N/A
1 JEA Joseph McClung Affirmative N/A
4 Electricities of North Carolina Marcus Freeman None N/A
6 Associated Electric Cooperative, Inc. Brian Ackermann Affirmative N/A
3 NiSource - Northern Indiana Public Service Co. Steven Taddeucci Affirmative N/A
5 NiSource - Northern Indiana Public Service Co. Kathryn Tackett Affirmative N/A
6 Northern California Power Agency Dennis Sismaet Affirmative N/A
5 Avista - Avista Corporation Glen Farmer Affirmative N/A
1 Los Angeles Department of Water and Power faranak sarbaz Abstain N/A
3 PPL - Louisville Gas and Electric Co. James Frank Affirmative N/A
4 Northern California Power Agency Marty Hostler Affirmative N/A
1 PPL Electric Utilities Corporation Michelle McCartney Longo Affirmative N/A
6 PPL - Louisville Gas and Electric Co. Linn Oelker Affirmative N/A
1 KAMO Electric Cooperative Micah Breedlove Affirmative N/A
1 NiSource - Northern Indiana Public Service Co. Alison Nickells Affirmative N/A
1 Portland General Electric Co. Brooke Jockin Negative N/A
1 Eversource Energy Joshua London Negative N/A
1 Northeast Missouri Electric Power Cooperative Brett Douglas Affirmative N/A
1 M and A Electric Power Cooperative William Price Affirmative N/A
6 Los Angeles Department of Water and Power Anton Vu None N/A
1 International Transmission Company Holdings Corporation Michael Moltane Allie Gavin Abstain N/A
5 Los Angeles Department of Water and Power Robert Kerrigan Abstain N/A
3 Ameren - Ameren Services David Jendras Sr Affirmative N/A
1 Tallahassee Electric (City of Tallahassee, FL) Scott Langston Affirmative N/A
1 SaskPower Wayne Guttormson Abstain N/A
6 Ameren - Ameren Services Robert Quinlivan Affirmative N/A
1 Ameren - Ameren Services Tamara Evey Affirmative N/A
3 Lakeland Electric Steven Marshall Affirmative N/A
5 Black Hills Corporation Sheila Suurmeier Affirmative N/A
3 Omaha Public Power District David Heins Negative N/A
3 Los Angeles Department of Water and Power Fausto Serratos Abstain N/A
5 Ameren - Ameren Missouri Sam Dwyer Affirmative N/A
5 Northern California Power Agency Jeremy Lawson Affirmative N/A
1 Avista - Avista Corporation Mike Magruder Affirmative N/A
6 Berkshire Hathaway - PacifiCorp Lindsay Wickizer Affirmative N/A
5 JEA John Babik Affirmative N/A
3 AEP Leshel Hutchings Affirmative N/A
1 Austin Energy Thomas Standifur Affirmative N/A
4 Alliant Energy Corporation Services, Inc. Larry Heckert None N/A
3 WEC Energy Group, Inc. Christine Kane Negative N/A
6 WEC Energy Group, Inc. David Boeshaar Negative N/A
4 WEC Energy Group, Inc. Matthew Beilfuss Negative N/A
3 Santee Cooper Vicky Budreau None N/A
1 Santee Cooper Chris Wagner None N/A
5 Evergy Jeremy Harris Alan Kloster Affirmative N/A
3 Northern California Power Agency Michael Whitney Affirmative N/A
3 Black Hills Corporation Josh Combs Affirmative N/A
5 WEC Energy Group, Inc. Michelle Hribar Negative N/A
5 Platte River Power Authority Jon Osell Affirmative N/A
5 Austin Energy Michael Dillard Affirmative N/A
6 Santee Cooper Marty Watson None N/A
1 Black Hills Corporation Micah Runner Affirmative N/A
1 Sacramento Municipal Utility District Wei Shao Tim Kelley Affirmative N/A
10 ReliabilityFirst Lindsey Mannion Negative N/A
5 Ontario Power Generation Inc. Constantin Chitescu Affirmative N/A
10 Northeast Power Coordinating Council Gerry Dunbar Abstain N/A
5 Cleco Corporation Stephanie Huffman None N/A
3 National Grid USA Brian Shanahan Negative N/A
1 Evergy Kevin Frick Alan Kloster Affirmative N/A
3 Evergy Marcus Moor Alan Kloster Affirmative N/A
6 Sacramento Municipal Utility District Charles Norton Tim Kelley Affirmative N/A
1 OTP - Otter Tail Power Company Charles Wicklund Negative N/A
3 OTP - Otter Tail Power Company Wendi Olson Negative N/A
5 Public Utility District No. 2 of Grant County, Washington Nikkee Hebdon Affirmative N/A
5 New York Power Authority Zahid Qayyum Affirmative N/A
3 DTE Energy - Detroit Edison Company Marvin Johnson Affirmative N/A
1 Central Electric Power Cooperative (Missouri) Michael Bax None N/A
2 Midcontinent ISO, Inc. Bobbi Welch Affirmative N/A
1 Sunflower Electric Power Corporation Paul Mehlhaff Affirmative N/A
5 DTE Energy - Detroit Edison Company Mohamad Elhusseini Affirmative N/A
6 Tacoma Public Utilities (Tacoma, WA) Terry Gifford Jennie Wike Affirmative N/A
10 Midwest Reliability Organization Mark Flanary Affirmative N/A
5 PPL - Louisville Gas and Electric Co. Julie Hostrander Affirmative N/A
6 Austin Energy Imane Mrini Affirmative N/A
3 Austin Energy Lovita Griffin Affirmative N/A
4 Seminole Electric Cooperative, Inc. Ken Habgood None N/A
6 New York Power Authority Shelly Dineen Affirmative N/A
5 Pattern Operators LP George E Brown Negative N/A
4 DTE Energy Patricia Ireland Affirmative N/A
5 Muscatine Power and Water Chance Back Negative N/A
6 NiSource - Northern Indiana Public Service Co. Joseph OBrien Affirmative N/A
3 Eversource Energy Vicki O'Leary Negative N/A
5 Dairyland Power Cooperative Tommy Drea None N/A
1 Dairyland Power Cooperative Karrie Schuldt None N/A
2 ISO New England, Inc. John Pearson Keith Jonassen Affirmative N/A
5 Berkshire Hathaway - NV Energy Dwanique Spiller Affirmative N/A
5 NextEra Energy Richard Vendetti Affirmative N/A
1 Pedernales Electric Cooperative, Inc. Bradley Collard None N/A
3 Colorado Springs Utilities Hillary Dobson Negative N/A
1 Lower Colorado River Authority Matt Lewis Affirmative N/A
8 Florida Reliability Coordinating Council – Member Services Division Vince Ordax Abstain N/A
5 BC Hydro and Power Authority Quincy Wang Affirmative N/A
5 Public Utility District No. 1 of Snohomish County Becky Burden Affirmative N/A
6 Portland General Electric Co. Stefanie Burke Negative N/A
4 Public Utility District No. 1 of Snohomish County John D. Martinsen Affirmative N/A
3 Portland General Electric Co. Mayra Franco None N/A
4 City Utilities of Springfield, Missouri Jerry Bradshaw Abstain N/A
5 Talen Generation, LLC Donald Lock Negative N/A
5 Orlando Utilities Commission Dania Colon None N/A
5 Brazos Electric Power Cooperative, Inc. Shari Heino Abstain N/A
1 City Utilities of Springfield, Missouri Michael Bowman None N/A
4 Georgia System Operations Corporation Katrina Lyons None N/A
4 Public Utility District No. 2 of Grant County, Washington Karla Weaver Affirmative N/A
5 Portland General Electric Co. Ryan Olson None N/A
1 Tacoma Public Utilities (Tacoma, WA) John Merrell Jennie Wike Negative N/A
5 NB Power Corporation David Melanson Affirmative N/A
1 Colorado Springs Utilities Corey Walker Negative N/A
3 JEA Marilyn Williams Affirmative N/A
5 Colorado Springs Utilities Jeffrey Icke Negative N/A
4 CMS Energy - Consumers Energy Company Aric Root None N/A
1 Balancing Authority of Northern California Kevin Smith Tim Kelley Affirmative N/A
1 Basin Electric Power Cooperative David Rudolph None N/A
3 Sacramento Municipal Utility District Nicole Looney Tim Kelley Affirmative N/A
1 Bonneville Power Administration Kamala Rogers-Holliday Negative N/A
5 Basin Electric Power Cooperative Amanda Wangler None N/A
3 Rayburn Country Electric Cooperative, Inc. Frank Owens None N/A
10 Western Electricity Coordinating Council Steven Rueckert Affirmative N/A
2 New York Independent System Operator Gregory Campoli None N/A
5 PSEG Nuclear LLC Tim Kucey Negative N/A
1 Hydro-Quebec (HQ) Nicolas Turcotte Affirmative N/A
5 Hydro-Quebec (HQ) Junji Yamaguchi Affirmative N/A