Ballot Results
Comment: View Comment Results
Ballot Name:
2021-02 Modifications to VAR-002-4.1 Implementation Plan IN 1 OT
Voting Start Date:
1/4/2023 12:01:00 AM
Voting End Date:
1/13/2023 8:00:00 PM
Ballot Type:
OT
Ballot Activity:
IN
Ballot Series:
1
Total # Votes:
228
Total Ballot Pool:
270
Quorum:
84.44
Quorum Established Date:
1/13/2023 2:08:54 PM
Weighted Segment Value:
60.95
Segment | Ballot Pool | Segment Weight | Affirmative Votes | Affirmative Fraction | Negative Votes w/ Comment | Negative Fraction w/ Comment | Negative Votes w/o Comment | Abstain | No Vote |
---|---|---|---|---|---|---|---|---|---|
Segment: 1 | 74 | 1 | 34 | 0.567 | 26 | 0.433 | 0 | 7 | 7 |
Segment: 2 | 5 | 0.5 | 3 | 0.3 | 2 | 0.2 | 0 | 0 | 0 |
Segment: 3 | 61 | 1 | 29 | 0.592 | 20 | 0.408 | 0 | 4 | 8 |
Segment: 4 | 12 | 0.7 | 6 | 0.6 | 1 | 0.1 | 0 | 1 | 4 |
Segment: 5 | 66 | 1 | 30 | 0.6 | 20 | 0.4 | 0 | 4 | 12 |
Segment: 6 | 45 | 1 | 19 | 0.594 | 13 | 0.406 | 0 | 5 | 8 |
Segment: 7 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 |
Segment: 8 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 |
Segment: 9 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Segment: 10 | 5 | 0.3 | 1 | 0.1 | 2 | 0.2 | 0 | 1 | 1 |
Totals: | 270 | 5.5 | 122 | 3.352 | 84 | 2.148 | 0 | 22 | 42 |
Ballot Pool Members
Segment | Organization | Voter | Designated Proxy | Ballot | NERC Memo |
---|---|---|---|---|---|
3 | Great River Energy | Michael Brytowski | Negative | Third-Party Comments | |
3 | Snohomish County PUD No. 1 | Holly Chaney | Affirmative | N/A | |
5 | Oglethorpe Power Corporation | Donna Johnson | Affirmative | N/A | |
1 | Allete - Minnesota Power, Inc. | Jamie Monette | Negative | Third-Party Comments | |
1 | NextEra Energy - Florida Power and Light Co. | Silvia Mitchell | Abstain | N/A | |
4 | FirstEnergy - FirstEnergy Corporation | Mark Garza | Affirmative | N/A | |
3 | Tri-State G and T Association, Inc. | Ryan Walter | None | N/A | |
3 | Arkansas Electric Cooperative Corporation | Ayslynn Mcavoy | Abstain | N/A | |
6 | Southern Indiana Gas and Electric Co. | Kati Barr | Affirmative | N/A | |
1 | Western Area Power Administration | Sean Erickson | Abstain | N/A | |
6 | Omaha Public Power District | Shonda McCain | Negative | Third-Party Comments | |
1 | Lincoln Electric System | Josh Johnson | Affirmative | N/A | |
5 | AEP | Thomas Foltz | Negative | Comments Submitted | |
2 | Independent Electricity System Operator | Harishkumar Subramani Vijay Kumar | Affirmative | N/A | |
2 | Electric Reliability Council of Texas, Inc. | Andrew Gallo | Negative | Comments Submitted | |
6 | Lincoln Electric System | Eric Ruskamp | Affirmative | N/A | |
1 | AEP - AEP Service Corporation | Dennis Sauriol | Negative | Comments Submitted | |
1 | Omaha Public Power District | Doug Peterchuck | Negative | Third-Party Comments | |
6 | AEP | Justin Kuehne | Negative | Comments Submitted | |
6 | FirstEnergy - FirstEnergy Corporation | Stacey Sheehan | Affirmative | N/A | |
6 | Arkansas Electric Cooperative Corporation | Bruce Walkup | Abstain | N/A | |
1 | Great River Energy | Gordon Pietsch | Negative | Third-Party Comments | |
1 | FirstEnergy - FirstEnergy Corporation | Julie Severino | Ann Carey | Affirmative | N/A |
5 | Sacramento Municipal Utility District | Pedro Juarez | Tim Kelley | Affirmative | N/A |
3 | Pacific Gas and Electric Company | Sandra Ellis | Michael Johnson | Affirmative | N/A |
6 | Cleco Corporation | Robert Hirchak | Affirmative | N/A | |
6 | Duke Energy | John Sturgeon | Negative | Comments Submitted | |
3 | Sempra - San Diego Gas and Electric | Bryan Bennett | Abstain | N/A | |
1 | Pacific Gas and Electric Company | Marco Rios | Michael Johnson | Affirmative | N/A |
1 | Xcel Energy, Inc. | Eric Barry | Negative | Third-Party Comments | |
1 | Duke Energy | Laura Lee | Negative | Comments Submitted | |
1 | Imperial Irrigation District | Jesus Sammy Alcaraz | Abstain | N/A | |
5 | Xcel Energy, Inc. | Gerry Huitt | Negative | Third-Party Comments | |
1 | Sempra - San Diego Gas and Electric | Mohamed Derbas | Abstain | N/A | |
5 | Sempra - San Diego Gas and Electric | Jennifer Wright | Abstain | N/A | |
5 | Pacific Gas and Electric Company | Frank Lee | Michael Johnson | Affirmative | N/A |
3 | Tennessee Valley Authority | Ian Grant | Affirmative | N/A | |
1 | Con Ed - Consolidated Edison Co. of New York | Dermot Smyth | Affirmative | N/A | |
1 | Hydro-Qu?bec TransEnergie | Nicolas Turcotte | Negative | Third-Party Comments | |
6 | Public Utility District No. 2 of Grant County, Washington | M LeRoy Patterson | Affirmative | N/A | |
3 | Lincoln Electric System | Sam Christensen | Affirmative | N/A | |
5 | Lincoln Electric System | Jason Fortik | Affirmative | N/A | |
4 | Sacramento Municipal Utility District | Foung Mua | Tim Kelley | Affirmative | N/A |
6 | Dominion - Dominion Resources, Inc. | Sean Bodkin | Affirmative | N/A | |
1 | Manitoba Hydro | Nazra Gladu | Affirmative | N/A | |
1 | Minnkota Power Cooperative Inc. | Theresa Allard | Nikki Carson-Marquis | Negative | Third-Party Comments |
3 | Con Ed - Consolidated Edison Co. of New York | Peter Yost | Affirmative | N/A | |
1 | Arizona Electric Power Cooperative, Inc. | Jennifer Bray | Negative | Comments Submitted | |
1 | Dominion - Dominion Virginia Power | Candace Marshall | Affirmative | N/A | |
10 | Texas Reliability Entity, Inc. | Rachel Coyne | Negative | Comments Submitted | |
3 | Platte River Power Authority | Richard Kiess | Affirmative | N/A | |
6 | Platte River Power Authority | Sabrina Martz | Affirmative | N/A | |
3 | APS - Arizona Public Service Co. | Jessica Lopez | Affirmative | N/A | |
1 | Associated Electric Cooperative, Inc. | Mark Riley | Affirmative | N/A | |
1 | Public Utility District No. 1 of Snohomish County | Alyssia Rhoads | Affirmative | N/A | |
6 | APS - Arizona Public Service Co. | Marcus Bortman | Affirmative | N/A | |
5 | APS - Arizona Public Service Co. | Michelle Amarantos | Affirmative | N/A | |
3 | Duke Energy | Lee Schuster | Negative | Comments Submitted | |
1 | National Grid USA | Michael Jones | Affirmative | N/A | |
2 | PJM Interconnection, L.L.C. | Thomas Foster | Elizabeth Davis | Affirmative | N/A |
5 | Tri-State G and T Association, Inc. | Sergio Banuelos | None | N/A | |
1 | APS - Arizona Public Service Co. | Daniela Atanasovski | Affirmative | N/A | |
1 | Tri-State G and T Association, Inc. | Donna Wood | Affirmative | N/A | |
6 | Constellation | Kimberly Turco | Affirmative | N/A | |
5 | Manitoba Hydro | Kristy-Lee Young | Affirmative | N/A | |
6 | PSEG - PSEG Energy Resources and Trade LLC | Joseph Neglia | Affirmative | N/A | |
6 | NextEra Energy - Florida Power and Light Co. | Justin Welty | Abstain | N/A | |
6 | Manitoba Hydro | Simon Tanapat-Andre | Affirmative | N/A | |
5 | NRG - NRG Energy, Inc. | Patricia Lynch | Negative | Comments Submitted | |
1 | Seminole Electric Cooperative, Inc. | Kristine Ward | Negative | Comments Submitted | |
5 | Platte River Power Authority | Jon Osell | Affirmative | N/A | |
3 | FirstEnergy - FirstEnergy Corporation | Aaron Ghodooshim | Affirmative | N/A | |
6 | Western Area Power Administration | Chrystal Dean | Abstain | N/A | |
5 | Constellation | Alison MacKellar | Kristine Howie | Affirmative | N/A |
5 | Con Ed - Consolidated Edison Co. of New York | Helen Wang | Affirmative | N/A | |
1 | NB Power Corporation | Jeffrey Streifling | Affirmative | N/A | |
1 | CenterPoint Energy Houston Electric, LLC | Daniela Hammons | Affirmative | N/A | |
3 | Imperial Irrigation District | Glen Allegranza | Abstain | N/A | |
1 | New York Power Authority | Salvatore Spagnolo | Negative | Third-Party Comments | |
5 | Greybeard Compliance Services, LLC | Mike Gabriel | None | N/A | |
3 | Owensboro Municipal Utilities | William Berry | Affirmative | N/A | |
5 | Dominion - Dominion Resources, Inc. | Rachel Snead | Affirmative | N/A | |
6 | Imperial Irrigation District | Diana Torres | Abstain | N/A | |
3 | Salt River Project | Mathew Weber | Israel Perez | Negative | Comments Submitted |
1 | Exelon | Daniel Gacek | Negative | Comments Submitted | |
1 | BC Hydro and Power Authority | Adrian Andreoiu | Negative | Comments Submitted | |
6 | Salt River Project | Timothy Singh | Israel Perez | Negative | Comments Submitted |
5 | Salt River Project | Jennifer Bennett | Israel Perez | Negative | Comments Submitted |
5 | FirstEnergy - FirstEnergy Corporation | Robert Loy | Affirmative | N/A | |
6 | Entergy | Julie Hall | Affirmative | N/A | |
3 | Edison International - Southern California Edison Company | Romel Aquino | Negative | Comments Submitted | |
5 | Pattern Operators LP | George E Brown | Negative | Third-Party Comments | |
3 | Dominion - Dominion Resources, Inc. | Connie Schroeder | Affirmative | N/A | |
5 | Hydro-Qu?bec Production | Carl Pineault | Negative | Comments Submitted | |
1 | Berkshire Hathaway Energy - MidAmerican Energy Co. | Terry Harbour | Negative | Comments Submitted | |
10 | SERC Reliability Corporation | Dave Krueger | Affirmative | N/A | |
5 | Duke Energy | Dale Goodwine | Negative | Comments Submitted | |
1 | Long Island Power Authority | Isidoro Behar | Abstain | N/A | |
1 | PNM Resources - Public Service Company of New Mexico | Lynn Goldstein | Negative | Comments Submitted | |
6 | Evergy | Jennifer Flandermeyer | Alan Kloster | Affirmative | N/A |
1 | Public Utility District No. 1 of Chelan County | Diane E Landry | Affirmative | N/A | |
3 | PNM Resources - Public Service Company of New Mexico | Amy Wesselkamper | None | N/A | |
5 | Public Utility District No. 1 of Chelan County | Meaghan Connell | Affirmative | N/A | |
6 | Great River Energy | Brian Meloy | None | N/A | |
3 | Public Utility District No. 1 of Chelan County | Joyce Gundry | Affirmative | N/A | |
1 | Southern Company - Southern Company Services, Inc. | Matt Carden | Negative | Comments Submitted | |
3 | Southern Company - Alabama Power Company | Joel Dembowski | Negative | Comments Submitted | |
6 | Southern Company - Southern Company Generation | Ron Carlsen | Negative | Comments Submitted | |
3 | Avista - Avista Corporation | Robert Follini | Affirmative | N/A | |
6 | Public Utility District No. 1 of Chelan County | Anne Kronshage | Affirmative | N/A | |
3 | Exelon | Kinte Whitehead | Negative | Comments Submitted | |
5 | Entergy - Entergy Services, Inc. | Gail Golden | Affirmative | N/A | |
1 | Tennessee Valley Authority | Gabe Kurtz | Affirmative | N/A | |
1 | Muscatine Power and Water | Andrew Kurriger | Negative | Third-Party Comments | |
6 | Seminole Electric Cooperative, Inc. | Bret Galbraith | Negative | Comments Submitted | |
3 | Muscatine Power and Water | Seth Shoemaker | Negative | Third-Party Comments | |
1 | Platte River Power Authority | Marissa Archie | Affirmative | N/A | |
1 | Entergy | Brian Lindsey | Affirmative | N/A | |
3 | Seminole Electric Cooperative, Inc. | Marc Sedor | Negative | Comments Submitted | |
5 | Imperial Irrigation District | Tino Zaragoza | Abstain | N/A | |
6 | Muscatine Power and Water | Nicholas Burns | Negative | Third-Party Comments | |
3 | PSEG - Public Service Electric and Gas Co. | Christopher Murphy | None | N/A | |
3 | Associated Electric Cooperative, Inc. | Todd Bennett | Affirmative | N/A | |
1 | N.W. Electric Power Cooperative, Inc. | Mark Ramsey | Affirmative | N/A | |
3 | Sho-Me Power Electric Cooperative | Jarrod Murdaugh | Affirmative | N/A | |
3 | Central Electric Power Cooperative (Missouri) | Adam Weber | Affirmative | N/A | |
3 | NW Electric Power Cooperative, Inc. | Heath Henry | Affirmative | N/A | |
3 | KAMO Electric Cooperative | Tony Gott | Affirmative | N/A | |
3 | Northeast Missouri Electric Power Cooperative | Skyler Wiegmann | Affirmative | N/A | |
1 | Glencoe Light and Power Commission | Terry Volkmann | Negative | Third-Party Comments | |
3 | Berkshire Hathaway Energy - MidAmerican Energy Co. | Joseph Amato | Negative | Comments Submitted | |
5 | Nebraska Public Power District | Ronald Bender | None | N/A | |
6 | NRG - NRG Energy, Inc. | Martin Sidor | None | N/A | |
3 | M and A Electric Power Cooperative | Stephen Pogue | Negative | Third-Party Comments | |
1 | Nebraska Public Power District | Jamison Cawley | Negative | Third-Party Comments | |
3 | Entergy | James Keele | Affirmative | N/A | |
3 | CMS Energy - Consumers Energy Company | Karl Blaszkowski | Affirmative | N/A | |
5 | Southern Company - Southern Company Generation | Jim Howell, Jr. | Negative | Comments Submitted | |
1 | IDACORP - Idaho Power Company | Sean Steffensen | None | N/A | |
3 | New York Power Authority | David Rivera | Negative | Third-Party Comments | |
6 | Powerex Corporation | Raj Hundal | Negative | Third-Party Comments | |
5 | Choctaw Generation Limited Partnership, LLLP | Rob Watson | Negative | Third-Party Comments | |
6 | Black Hills Corporation | Claudine Bates | Affirmative | N/A | |
5 | Cowlitz County PUD | Deanna Carlson | Negative | Comments Submitted | |
5 | National Grid USA | Robin Berry | Affirmative | N/A | |
1 | JEA | Joseph McClung | Affirmative | N/A | |
6 | Con Ed - Consolidated Edison Co. of New York | Michael Foley | Affirmative | N/A | |
6 | Associated Electric Cooperative, Inc. | Brian Ackermann | Affirmative | N/A | |
3 | NiSource - Northern Indiana Public Service Co. | Steven Taddeucci | Affirmative | N/A | |
6 | Northern California Power Agency | Dennis Sismaet | None | N/A | |
5 | Avista - Avista Corporation | Glen Farmer | Affirmative | N/A | |
1 | Los Angeles Department of Water and Power | Pjoy Chua | Abstain | N/A | |
3 | PPL - Louisville Gas and Electric Co. | James Frank | Affirmative | N/A | |
4 | Northern California Power Agency | Marty Hostler | None | N/A | |
1 | PPL Electric Utilities Corporation | Michelle McCartney Longo | Affirmative | N/A | |
4 | Oklahoma Municipal Power Authority | Michael Watt | Abstain | N/A | |
1 | Salt River Project | Sarah Blankenship | Israel Perez | Negative | Comments Submitted |
6 | PPL - Louisville Gas and Electric Co. | Linn Oelker | None | N/A | |
1 | KAMO Electric Cooperative | Micah Breedlove | Affirmative | N/A | |
3 | Nebraska Public Power District | Tony Eddleman | Negative | Third-Party Comments | |
1 | NiSource - Northern Indiana Public Service Co. | Steve Toosevich | Affirmative | N/A | |
5 | NiSource - Northern Indiana Public Service Co. | Kathryn Tackett | Affirmative | N/A | |
1 | Portland General Electric Co. | Brooke Jockin | None | N/A | |
5 | New York Power Authority | Zahid Qayyum | Negative | Third-Party Comments | |
3 | Cowlitz County PUD | Russell Noble | Negative | Comments Submitted | |
1 | Northeast Missouri Electric Power Cooperative | Brett Douglas | Negative | Third-Party Comments | |
1 | M and A Electric Power Cooperative | William Price | Affirmative | N/A | |
1 | Lakeland Electric | Larry Watt | None | N/A | |
6 | Los Angeles Department of Water and Power | Anton Vu | None | N/A | |
1 | International Transmission Company Holdings Corporation | Michael Moltane | Allie Gavin | Abstain | N/A |
5 | Los Angeles Department of Water and Power | Glenn Barry | Abstain | N/A | |
3 | Ameren - Ameren Services | David Jendras Sr | Negative | Comments Submitted | |
1 | Tallahassee Electric (City of Tallahassee, FL) | Scott Langston | Affirmative | N/A | |
6 | Ameren - Ameren Services | Robert Quinlivan | Negative | Comments Submitted | |
1 | Ameren - Ameren Services | Tamara Evey | Negative | Comments Submitted | |
1 | SaskPower | Wayne Guttormson | None | N/A | |
3 | Lakeland Electric | Steven Marshall | None | N/A | |
5 | Omaha Public Power District | Mahmood Safi | Negative | Third-Party Comments | |
5 | Black Hills Corporation | Sheila Suurmeier | Affirmative | N/A | |
3 | Omaha Public Power District | David Heins | Negative | Third-Party Comments | |
3 | Los Angeles Department of Water and Power | Tony Skourtas | Abstain | N/A | |
5 | Ameren - Ameren Missouri | Sam Dwyer | None | N/A | |
5 | Northern California Power Agency | Jeremy Lawson | None | N/A | |
5 | Vistra Energy | Daniel Roethemeyer | Affirmative | N/A | |
7 | Luminant Mining Company LLC | Stewart Rake | None | N/A | |
1 | Avista - Avista Corporation | Mike Magruder | Affirmative | N/A | |
3 | AEP | Kent Feliks | Negative | Comments Submitted | |
5 | JEA | John Babik | None | N/A | |
1 | Austin Energy | Thomas Standifur | Affirmative | N/A | |
4 | Alliant Energy Corporation Services, Inc. | Larry Heckert | Negative | Third-Party Comments | |
3 | WEC Energy Group, Inc. | Christine Kane | Negative | Comments Submitted | |
4 | WEC Energy Group, Inc. | Matthew Beilfuss | None | N/A | |
3 | Santee Cooper | James Poston | Negative | Comments Submitted | |
1 | Santee Cooper | Chris Wagner | Negative | Comments Submitted | |
5 | Evergy | Jeremy Harris | Alan Kloster | Affirmative | N/A |
6 | WEC Energy Group, Inc. | David Boeshaar | Negative | Comments Submitted | |
3 | Northern California Power Agency | Michael Whitney | None | N/A | |
6 | Xcel Energy, Inc. | Steve Szablya | None | N/A | |
5 | WEC Energy Group, Inc. | Clarice Zellmer | Negative | Comments Submitted | |
5 | Austin Energy | Michael Dillard | Affirmative | N/A | |
6 | Santee Cooper | Glenda Horne | Negative | Comments Submitted | |
1 | Black Hills Corporation | Micah Runner | Affirmative | N/A | |
1 | Sacramento Municipal Utility District | Wei Shao | Tim Kelley | Affirmative | N/A |
10 | ReliabilityFirst | Lindsey Mannion | Negative | Comments Submitted | |
5 | Ontario Power Generation Inc. | Constantin Chitescu | Negative | Comments Submitted | |
5 | AES - AES Corporation | Ruchi Shah | Sing Tay | Negative | Comments Submitted |
10 | Northeast Power Coordinating Council | Gerry Dunbar | Abstain | N/A | |
5 | Cleco Corporation | Stephanie Huffman | None | N/A | |
3 | National Grid USA | Brian Shanahan | Affirmative | N/A | |
1 | Evergy | Kevin Frick | Alan Kloster | Affirmative | N/A |
3 | Evergy | Marcus Moor | Alan Kloster | Affirmative | N/A |
6 | Sacramento Municipal Utility District | Charles Norton | Tim Kelley | Affirmative | N/A |
1 | OTP - Otter Tail Power Company | Charles Wicklund | Negative | Third-Party Comments | |
3 | Black Hills Corporation | Josh Combs | Affirmative | N/A | |
5 | Lower Colorado River Authority | Teresa Krabe | Affirmative | N/A | |
5 | Seminole Electric Cooperative, Inc. | Melanie Wong | Negative | Comments Submitted | |
3 | OTP - Otter Tail Power Company | Wendi Olson | Negative | Third-Party Comments | |
5 | Public Utility District No. 2 of Grant County, Washington | Nikkee Hebdon | Affirmative | N/A | |
3 | DTE Energy - Detroit Edison Company | Karie Barczak | Affirmative | N/A | |
1 | Central Electric Power Cooperative (Missouri) | Michael Bax | Affirmative | N/A | |
2 | Midcontinent ISO, Inc. | Bobbi Welch | Affirmative | N/A | |
5 | Edison International - Southern California Edison Company | Selene Willis | Negative | Comments Submitted | |
1 | Sunflower Electric Power Corporation | Paul Mehlhaff | None | N/A | |
5 | DTE Energy - Detroit Edison Company | Adrian Raducea | Affirmative | N/A | |
6 | Tacoma Public Utilities (Tacoma, WA) | Terry Gifford | Jennie Wike | None | N/A |
10 | Midwest Reliability Organization | Mark Flanary | None | N/A | |
5 | PPL - Louisville Gas and Electric Co. | Julie Hostrander | Affirmative | N/A | |
6 | Austin Energy | Imane Mrini | None | N/A | |
3 | Austin Energy | Lovita Griffin | None | N/A | |
6 | New York Power Authority | Shelly Dineen | Negative | Third-Party Comments | |
5 | PSEG - PSEG Fossil LLC | Tim Kucey | Affirmative | N/A | |
4 | DTE Energy | Patricia Ireland | None | N/A | |
5 | Muscatine Power and Water | Neal Nelson | Negative | Third-Party Comments | |
6 | NiSource - Northern Indiana Public Service Co. | Joseph OBrien | Affirmative | N/A | |
6 | OGE Energy - Oklahoma Gas and Electric Co. | Ashley F Stringer | Negative | Third-Party Comments | |
5 | Dairyland Power Cooperative | Tommy Drea | Negative | Third-Party Comments | |
1 | Dairyland Power Cooperative | Steve Ritscher | Negative | Third-Party Comments | |
2 | ISO New England, Inc. | John Pearson | Kathleen Goodman | Negative | Comments Submitted |
5 | Great River Energy | Jacalynn Bentz | None | N/A | |
5 | Berkshire Hathaway - NV Energy | Dwanique Spiller | Affirmative | N/A | |
5 | NextEra Energy | Summer Esquerre | Abstain | N/A | |
3 | Colorado Springs Utilities | Hillary Dobson | Affirmative | N/A | |
1 | Lower Colorado River Authority | James Baldwin | Affirmative | N/A | |
8 | Florida Reliability Coordinating Council – Member Services Division | Vince Ordax | None | N/A | |
5 | BC Hydro and Power Authority | Helen Hamilton Harding | Negative | Comments Submitted | |
5 | Public Utility District No. 1 of Snohomish County | Becky Burden | Affirmative | N/A | |
6 | Portland General Electric Co. | Daniel Mason | Abstain | N/A | |
4 | Public Utility District No. 1 of Snohomish County | John D. Martinsen | Affirmative | N/A | |
3 | Portland General Electric Co. | Mayra Franco | None | N/A | |
5 | Bonneville Power Administration | Christopher Siewert | Affirmative | N/A | |
5 | Talen Generation, LLC | Donald Lock | Affirmative | N/A | |
5 | Orlando Utilities Commission | Dania Colon | None | N/A | |
1 | City Utilities of Springfield, Missouri | Michael Bowman | Negative | Third-Party Comments | |
3 | Bonneville Power Administration | Ken Lanehome | Affirmative | N/A | |
4 | Georgia System Operations Corporation | Benjamin Winslett | Affirmative | N/A | |
4 | Public Utility District No. 2 of Grant County, Washington | Karla Weaver | Affirmative | N/A | |
5 | Portland General Electric Co. | Ryan Olson | None | N/A | |
1 | Tacoma Public Utilities (Tacoma, WA) | John Merrell | Jennie Wike | Affirmative | N/A |
5 | NB Power Corporation | David Melanson | Affirmative | N/A | |
1 | Colorado Springs Utilities | Corey Walker | None | N/A | |
3 | JEA | Marilyn Williams | Negative | Comments Submitted | |
4 | LaGen | Wayne Messina | None | N/A | |
5 | Colorado Springs Utilities | Jeffrey Icke | None | N/A | |
4 | CMS Energy - Consumers Energy Company | Aric Root | Affirmative | N/A | |
1 | Balancing Authority of Northern California | Kevin Smith | Tim Kelley | Affirmative | N/A |
3 | Xcel Energy, Inc. | Nicholas Friebel | None | N/A | |
1 | Basin Electric Power Cooperative | David Rudolph | None | N/A | |
3 | Sacramento Municipal Utility District | Nicole Looney | Tim Kelley | Affirmative | N/A |
1 | Bonneville Power Administration | Kamala Rogers-Holliday | Affirmative | N/A | |
5 | PSEG Nuclear LLC | Tim Kucey | None | N/A |