Ballot Results
Comment: View Comment Results
Ballot Name:
2021-07 Extreme Cold Weather Grid Operations, Preparedness, and Coordination EOP-012-1 IN 1 ST
Voting Start Date:
6/8/2022 12:01:00 AM
Voting End Date:
6/21/2022 8:00:00 PM
Ballot Type:
ST
Ballot Activity:
IN
Ballot Series:
1
Total # Votes:
295
Total Ballot Pool:
313
Quorum:
94.25
Quorum Established Date:
6/20/2022 2:03:38 PM
Weighted Segment Value:
21.94
Segment | Ballot Pool | Segment Weight | Affirmative Votes | Affirmative Fraction | Negative Votes w/ Comment | Negative Fraction w/ Comment | Negative Votes w/o Comment | Abstain | No Vote |
---|---|---|---|---|---|---|---|---|---|
Segment: 1 | 87 | 1 | 14 | 0.187 | 61 | 0.813 | 0 | 8 | 4 |
Segment: 2 | 7 | 0.7 | 1 | 0.1 | 6 | 0.6 | 0 | 0 | 0 |
Segment: 3 | 68 | 1 | 11 | 0.177 | 51 | 0.823 | 0 | 1 | 5 |
Segment: 4 | 19 | 1 | 1 | 0.071 | 13 | 0.929 | 0 | 2 | 3 |
Segment: 5 | 76 | 1 | 13 | 0.181 | 59 | 0.819 | 1 | 1 | 2 |
Segment: 6 | 49 | 1 | 10 | 0.222 | 35 | 0.778 | 1 | 1 | 2 |
Segment: 7 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 |
Segment: 8 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Segment: 9 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Segment: 10 | 6 | 0.4 | 4 | 0.4 | 0 | 0 | 0 | 1 | 1 |
Totals: | 313 | 6.1 | 54 | 1.338 | 225 | 4.762 | 2 | 14 | 18 |
Ballot Pool Members
Segment | Organization | Voter | Designated Proxy | Ballot | NERC Memo |
---|---|---|---|---|---|
4 | FirstEnergy - FirstEnergy Corporation | Mark Garza | Negative | Comments Submitted | |
5 | AEP | Thomas Foltz | Negative | Comments Submitted | |
4 | Illinois Municipal Electric Agency | Mary Ann Todd | Abstain | N/A | |
6 | FirstEnergy - FirstEnergy Corporation | Tricia Bynum | Negative | Comments Submitted | |
5 | Ontario Power Generation Inc. | Constantin Chitescu | Negative | Third-Party Comments | |
3 | Dominion - Dominion Resources, Inc. | Connie Schroeder | Negative | Comments Submitted | |
5 | NB Power Corporation | David Melanson | Abstain | N/A | |
7 | Oxy - Occidental Chemical | Venona Greaff | None | N/A | |
1 | NB Power Corporation | Nurul Abser | Abstain | N/A | |
4 | MGE Energy - Madison Gas and Electric Co. | Adam Lee | Negative | Third-Party Comments | |
1 | Arkansas Electric Cooperative Corporation | Emily Corley | None | N/A | |
5 | Xcel Energy, Inc. | Gerry Huitt | Amy Casuscelli | Negative | Comments Submitted |
5 | FirstEnergy - FirstEnergy Corporation | Robert Loy | Negative | Comments Submitted | |
5 | Basin Electric Power Cooperative | Amanda Wangler | Negative | Third-Party Comments | |
6 | AEP | Justin Kuehne | Negative | Comments Submitted | |
3 | CMS Energy - Consumers Energy Company | Karl Blaszkowski | Negative | Third-Party Comments | |
1 | Ohio Valley Electric Corporation | Scott Cunningham | Negative | Third-Party Comments | |
1 | Pedernales Electric Cooperative, Inc. | Bradley Collard | Abstain | N/A | |
5 | DTE Energy - Detroit Edison Company | Adrian Raducea | Negative | Comments Submitted | |
6 | Invenergy LLC | Colin Chilcoat | Negative | Comments Submitted | |
2 | Midcontinent ISO, Inc. | Bobbi Welch | Negative | Third-Party Comments | |
1 | AEP - AEP Service Corporation | Dennis Sauriol | Negative | Comments Submitted | |
5 | Florida Municipal Power Agency | Chris Gowder | LaKenya Vannorman | Negative | Third-Party Comments |
3 | Cowlitz County PUD | Russell Noble | Negative | Comments Submitted | |
2 | PJM Interconnection, L.L.C. | Thomas Foster | Elizabeth Davis | Negative | Third-Party Comments |
4 | Indiana Municipal Power Agency | Jack Alvey | Scott Berry | Negative | Third-Party Comments |
3 | Berkshire Hathaway Energy - MidAmerican Energy Co. | Joseph Amato | Negative | Comments Submitted | |
5 | Public Utility District No. 1 of Chelan County | Meaghan Connell | Negative | Comments Submitted | |
1 | Berkshire Hathaway Energy - MidAmerican Energy Co. | Terry Harbour | Negative | Comments Submitted | |
1 | FirstEnergy - FirstEnergy Corporation | Julie Severino | Negative | Comments Submitted | |
5 | JEA | John Babik | Negative | Comments Submitted | |
5 | CMS Energy - Consumers Energy Company | David Greyerbiehl | Negative | Third-Party Comments | |
3 | Sacramento Municipal Utility District | Nicole Looney | Tim Kelley | Negative | Comments Submitted |
4 | Utility Services, Inc. | Brian Evans-Mongeon | Negative | Comments Submitted | |
1 | Balancing Authority of Northern California | Kevin Smith | Tim Kelley | Negative | Comments Submitted |
3 | Tacoma Public Utilities (Tacoma, WA) | Marc Donaldson | Jennie Wike | Negative | Comments Submitted |
4 | Tacoma Public Utilities (Tacoma, WA) | Hien Ho | Jennie Wike | Negative | Comments Submitted |
6 | Tacoma Public Utilities (Tacoma, WA) | Terry Gifford | Jennie Wike | Negative | Comments Submitted |
6 | Public Utility District No. 1 of Chelan County | Glen Pruitt | Negative | Comments Submitted | |
6 | Dominion - Dominion Resources, Inc. | Sean Bodkin | Negative | Comments Submitted | |
1 | Dominion - Dominion Virginia Power | Candace Marshall | Negative | Comments Submitted | |
1 | BC Hydro and Power Authority | Adrian Andreoiu | Affirmative | N/A | |
1 | Hydro-Qu?bec TransEnergie | Nicolas Turcotte | Negative | Comments Submitted | |
4 | CMS Energy - Consumers Energy Company | Aric Root | Negative | Third-Party Comments | |
1 | Imperial Irrigation District | Jesus Sammy Alcaraz | Denise Sanchez | Negative | Comments Submitted |
6 | Xcel Energy, Inc. | Carrie Dixon | Negative | Comments Submitted | |
1 | Bonneville Power Administration | Kamala Rogers-Holliday | Negative | Comments Submitted | |
5 | Imperial Irrigation District | Tino Zaragoza | Denise Sanchez | Negative | Comments Submitted |
6 | Bonneville Power Administration | Andrew Meyers | Negative | Comments Submitted | |
3 | Bonneville Power Administration | Ken Lanehome | Negative | Comments Submitted | |
1 | Xcel Energy, Inc. | Eric Barry | Negative | Comments Submitted | |
3 | BC Hydro and Power Authority | Hootan Jarollahi | Affirmative | N/A | |
5 | Dominion - Dominion Resources, Inc. | Rachel Snead | Negative | Comments Submitted | |
3 | Avista - Avista Corporation | Scott Kinney | Negative | Comments Submitted | |
3 | Xcel Energy, Inc. | Nicholas Friebel | Negative | Comments Submitted | |
3 | Pacific Gas and Electric Company | Sandra Ellis | Michael Johnson | Negative | Comments Submitted |
6 | Imperial Irrigation District | Diana Torres | Denise Sanchez | Negative | Comments Submitted |
1 | Public Utility District No. 1 of Chelan County | Diane E Landry | Negative | Comments Submitted | |
3 | Public Utility District No. 1 of Chelan County | Joyce Gundry | Negative | Comments Submitted | |
1 | Salt River Project | Chris Hofmann | Negative | Comments Submitted | |
5 | Vistra Energy | Daniel Roethemeyer | Negative | Comments Submitted | |
3 | Nebraska Public Power District | Tony Eddleman | Negative | Third-Party Comments | |
1 | National Grid USA | Michael Jones | Negative | Comments Submitted | |
3 | National Grid USA | Brian Shanahan | Negative | Comments Submitted | |
1 | Colorado Springs Utilities | Mike Braunstein | Negative | Comments Submitted | |
3 | Colorado Springs Utilities | Hillary Dobson | Negative | Comments Submitted | |
5 | Sacramento Municipal Utility District | Nicole Goi | Tim Kelley | Negative | Comments Submitted |
5 | Enel Green Power | Natalie Johnson | Negative | Comments Submitted | |
3 | Ameren - Ameren Services | David Jendras Sr | Negative | Comments Submitted | |
6 | NiSource - Northern Indiana Public Service Co. | Joseph OBrien | Affirmative | N/A | |
3 | M and A Electric Power Cooperative | Stephen Pogue | Negative | Third-Party Comments | |
1 | KAMO Electric Cooperative | Micah Breedlove | Negative | Third-Party Comments | |
1 | Glencoe Light and Power Commission | Terry Volkmann | Negative | Third-Party Comments | |
6 | Associated Electric Cooperative, Inc. | Brian Ackermann | Negative | Comments Submitted | |
5 | Salt River Project | Kevin Nielsen | Negative | Third-Party Comments | |
1 | Manitoba Hydro | Nazra Gladu | Affirmative | N/A | |
3 | WEC Energy Group, Inc. | Christine Kane | Negative | Comments Submitted | |
5 | Ameren - Ameren Missouri | Sam Dwyer | Negative | Comments Submitted | |
6 | Portland General Electric Co. | Daniel Mason | Affirmative | N/A | |
1 | Ameren - Ameren Services | Tamara Evey | Negative | Comments Submitted | |
3 | Manitoba Hydro | Mike Smith | Affirmative | N/A | |
4 | WEC Energy Group, Inc. | Matthew Beilfuss | Negative | Comments Submitted | |
2 | ISO New England, Inc. | John Pearson | Keith Jonassen | Negative | Comments Submitted |
3 | Associated Electric Cooperative, Inc. | Todd Bennett | Negative | Comments Submitted | |
6 | Ameren - Ameren Services | Robert Quinlivan | Negative | Comments Submitted | |
3 | Sho-Me Power Electric Cooperative | Jarrod Murdaugh | Negative | Third-Party Comments | |
5 | WEC Energy Group, Inc. | Clarice Zellmer | Negative | Comments Submitted | |
3 | Black Hills Corporation | Josh Combs | Jennifer Malon | Negative | Comments Submitted |
3 | Central Electric Power Cooperative (Missouri) | Adam Weber | Negative | Third-Party Comments | |
3 | Great River Energy | Michael Brytowski | Negative | Third-Party Comments | |
3 | DTE Energy - Detroit Edison Company | Karie Barczak | Negative | Comments Submitted | |
6 | Manitoba Hydro | Simon Tanapat-Andre | Affirmative | N/A | |
3 | KAMO Electric Cooperative | Tony Gott | Negative | Third-Party Comments | |
10 | New York State Reliability Council | Wesley Yeomans | None | N/A | |
5 | Oglethorpe Power Corporation | Donna Johnson | Negative | Comments Submitted | |
5 | Duke Energy | Dale Goodwine | Negative | Comments Submitted | |
6 | PPL - Louisville Gas and Electric Co. | Linn Oelker | Negative | Third-Party Comments | |
5 | Lower Colorado River Authority | Teresa Krabe | Negative | Comments Submitted | |
6 | WEC Energy Group, Inc. | David Boeshaar | Negative | Comments Submitted | |
3 | New York Power Authority | David Rivera | Negative | Third-Party Comments | |
3 | NiSource - Northern Indiana Public Service Co. | Steven Taddeucci | Affirmative | N/A | |
2 | New York Independent System Operator | Gregory Campoli | Negative | Third-Party Comments | |
1 | Santee Cooper | Chris Wagner | Negative | Comments Submitted | |
1 | Tennessee Valley Authority | Gabe Kurtz | Affirmative | N/A | |
1 | Great River Energy | Gordon Pietsch | Negative | Third-Party Comments | |
1 | Lower Colorado River Authority | James Baldwin | Negative | Comments Submitted | |
3 | Tennessee Valley Authority | Ian Grant | Affirmative | N/A | |
6 | Cleco Corporation | Robert Hirchak | Negative | Third-Party Comments | |
3 | Santee Cooper | James Poston | Negative | Comments Submitted | |
5 | NRG - NRG Energy, Inc. | Patricia Lynch | Negative | Comments Submitted | |
5 | Santee Cooper | Marty Watson | Negative | Comments Submitted | |
6 | Omaha Public Power District | Shonda McCain | Negative | No Comment Submitted | |
6 | Santee Cooper | Glenda Horne | Negative | Comments Submitted | |
6 | NextEra Energy - Florida Power and Light Co. | Justin Welty | Negative | Comments Submitted | |
3 | Omaha Public Power District | David Heins | Negative | Third-Party Comments | |
1 | Northeast Missouri Electric Power Cooperative | Brett Douglas | Negative | Third-Party Comments | |
5 | Tennessee Valley Authority | Darren Boehm | None | N/A | |
1 | Omaha Public Power District | Doug Peterchuck | Negative | Third-Party Comments | |
1 | N.W. Electric Power Cooperative, Inc. | Mark Ramsey | Negative | Third-Party Comments | |
3 | NW Electric Power Cooperative, Inc. | John Stickley | Negative | Third-Party Comments | |
1 | NiSource - Northern Indiana Public Service Co. | Steve Toosevich | Affirmative | N/A | |
5 | Colorado Springs Utilities | Jeffrey Icke | Negative | Comments Submitted | |
5 | NiSource - Northern Indiana Public Service Co. | Kathryn Tackett | Affirmative | N/A | |
5 | New York Power Authority | Zahid Qayyum | Negative | Third-Party Comments | |
1 | Southern Company - Southern Company Services, Inc. | Matt Carden | Affirmative | N/A | |
3 | Southern Company - Alabama Power Company | Joel Dembowski | Affirmative | N/A | |
5 | Southern Company - Southern Company Generation | Jim Howell, Jr. | Affirmative | N/A | |
6 | Southern Company - Southern Company Generation | Ron Carlsen | Affirmative | N/A | |
1 | Seminole Electric Cooperative, Inc. | Kristine Ward | Affirmative | N/A | |
5 | Acciona Energy North America | George Brown | Negative | Comments Submitted | |
4 | Seminole Electric Cooperative, Inc. | Jonathan Robbins | Affirmative | N/A | |
3 | PPL - Louisville Gas and Electric Co. | James Frank | Negative | Third-Party Comments | |
1 | Oncor Electric Delivery | Lee Maurer | Gul Khan | Abstain | N/A |
6 | Constellation | Kimberly Turco | Negative | Comments Submitted | |
1 | Tacoma Public Utilities (Tacoma, WA) | John Merrell | Jennie Wike | Negative | Comments Submitted |
6 | Northern California Power Agency | Dennis Sismaet | Negative | Comments Submitted | |
3 | OGE Energy - Oklahoma Gas and Electric Co. | Donald Hargrove | Affirmative | N/A | |
3 | Snohomish County PUD No. 1 | Holly Chaney | None | N/A | |
1 | PPL Electric Utilities Corporation | Michelle McCartney Longo | Negative | Third-Party Comments | |
3 | Imperial Irrigation District | Glen Allegranza | Denise Sanchez | Negative | Comments Submitted |
5 | Public Utility District No. 1 of Snohomish County | Sam Nietfeld | Negative | Comments Submitted | |
4 | Public Utility District No. 1 of Snohomish County | John D. Martinsen | None | N/A | |
6 | Snohomish County PUD No. 1 | John Liang | None | N/A | |
1 | Public Utility District No. 1 of Snohomish County | Alyssia Rhoads | None | N/A | |
5 | Dairyland Power Cooperative | Tommy Drea | Affirmative | N/A | |
1 | Nebraska Public Power District | Jamison Cawley | Negative | Third-Party Comments | |
1 | New York Power Authority | Salvatore Spagnolo | Negative | Third-Party Comments | |
1 | Taunton Municipal Lighting Plant | Devon Tremont | Negative | Comments Submitted | |
3 | MGE Energy - Madison Gas and Electric Co. | Ronald Bauer | Negative | Third-Party Comments | |
10 | Texas Reliability Entity, Inc. | Rachel Coyne | Affirmative | N/A | |
3 | Georgia System Operations Corporation | Scott McGough | Negative | Third-Party Comments | |
5 | Nebraska Public Power District | Ronald Bender | Negative | Third-Party Comments | |
1 | Georgia Transmission Corporation | Greg Davis | Negative | Third-Party Comments | |
3 | Sempra - San Diego Gas and Electric | Bridget Silvia | Abstain | N/A | |
1 | Sempra - San Diego Gas and Electric | Mohamed Derbas | Abstain | N/A | |
1 | NextEra Energy - Florida Power and Light Co. | Silvia Mitchell | Negative | Comments Submitted | |
6 | Florida Municipal Power Agency | Jade Bulitta | LaKenya Vannorman | Negative | Comments Submitted |
3 | Duke Energy | Lee Schuster | Negative | Comments Submitted | |
1 | Duke Energy | Laura Lee | Negative | Comments Submitted | |
1 | Central Electric Power Cooperative (Missouri) | Michael Bax | Negative | Third-Party Comments | |
1 | Pacific Gas and Electric Company | Marco Rios | Michael Johnson | Negative | Comments Submitted |
1 | IDACORP - Idaho Power Company | Sean Steffensen | None | N/A | |
1 | APS - Arizona Public Service Co. | Daniela Atanasovski | Negative | Comments Submitted | |
1 | CenterPoint Energy Houston Electric, LLC | Daniela Hammons | Negative | Comments Submitted | |
3 | APS - Arizona Public Service Co. | Jessica Lopez | Negative | Comments Submitted | |
6 | APS - Arizona Public Service Co. | Marcus Bortman | Negative | Comments Submitted | |
5 | Bonneville Power Administration | Scott Winner | Negative | Comments Submitted | |
1 | Dairyland Power Cooperative | Steve Ritscher | Negative | Third-Party Comments | |
6 | PSEG - PSEG Energy Resources and Trade LLC | Joseph Neglia | Negative | Third-Party Comments | |
5 | PPL - Louisville Gas and Electric Co. | Julie Hostrander | Negative | Third-Party Comments | |
1 | Sunflower Electric Power Corporation | Paul Mehlhaff | Negative | Third-Party Comments | |
10 | SERC Reliability Corporation | Dave Krueger | Affirmative | N/A | |
6 | Southern Indiana Gas and Electric Co. | Erin Spence | Negative | Comments Submitted | |
3 | Southern Indiana Gas and Electric Co. | Ryan Abshier | Negative | Comments Submitted | |
5 | Decatur Energy Center LLC | Shannon Ferdinand | Negative | Comments Submitted | |
4 | Oklahoma Municipal Power Authority | Michael Watt | Negative | Comments Submitted | |
5 | National Grid USA | Elizabeth Spivak | Negative | Comments Submitted | |
1 | Tri-State G and T Association, Inc. | Donna Wood | Negative | Comments Submitted | |
5 | Tri-State G and T Association, Inc. | Ryan Walter | Negative | Comments Submitted | |
4 | DTE Energy | Patricia Ireland | None | N/A | |
6 | Florida Municipal Power Pool | Aaron Casto | LaKenya Vannorman | Negative | Comments Submitted |
5 | Constellation | Alison MacKellar | Negative | Comments Submitted | |
1 | Basin Electric Power Cooperative | David Rudolph | Negative | Third-Party Comments | |
6 | Platte River Power Authority | Sabrina Martz | Negative | Third-Party Comments | |
1 | Platte River Power Authority | Matt Thompson | Negative | Third-Party Comments | |
5 | BC Hydro and Power Authority | Helen Hamilton Harding | Affirmative | N/A | |
3 | PSEG - Public Service Electric and Gas Co. | Maria Pardo | Negative | Third-Party Comments | |
5 | Pacific Gas and Electric Company | Frank Lee | Michael Johnson | Negative | Comments Submitted |
6 | Entergy | Julie Hall | Affirmative | N/A | |
5 | Entergy - Entergy Services, Inc. | Gail Golden | Affirmative | N/A | |
4 | Sacramento Municipal Utility District | Foung Mua | Tim Kelley | Negative | Comments Submitted |
5 | Platte River Power Authority | Jon Osell | Negative | Third-Party Comments | |
5 | Tacoma Public Utilities (Tacoma, WA) | Ozan Ferrin | Jennie Wike | Negative | Comments Submitted |
5 | Public Utility District No. 2 of Grant County, Washington | Amy Jones | Affirmative | N/A | |
1 | Associated Electric Cooperative, Inc. | Mark Riley | Negative | Comments Submitted | |
3 | Platte River Power Authority | Richard Kiess | Negative | Third-Party Comments | |
5 | Cowlitz County PUD | Deanna Carlson | Negative | Comments Submitted | |
5 | Berkshire Hathaway - NV Energy | Kevin Salsbury | Affirmative | N/A | |
1 | Western Area Power Administration | Sean Erickson | Kimberly Bentley | Negative | Comments Submitted |
5 | Herb Schrayshuen | Herb Schrayshuen | Affirmative | N/A | |
2 | California ISO | Darcy O'Connell | Negative | Third-Party Comments | |
3 | Ocala Utility Services | Neville Bowen | LaKenya Vannorman | Negative | Comments Submitted |
2 | Independent Electricity System Operator | Leonard Kula | Negative | Comments Submitted | |
6 | Tennessee Valley Authority | Armando Rodriguez | Affirmative | N/A | |
2 | Southwest Power Pool, Inc. (RTO) | Charles Yeung | Affirmative | N/A | |
5 | Cogentrix Energy Power Management, LLC | Gerry Adamski | Negative | Comments Submitted | |
1 | International Transmission Company Holdings Corporation | Michael Moltane | Allie Gavin | Abstain | N/A |
1 | Evergy | Allen Klassen | Alan Kloster | Negative | Third-Party Comments |
3 | Evergy | Marcus Moor | Alan Kloster | Negative | Comments Submitted |
5 | Avista - Avista Corporation | Glen Farmer | Negative | Comments Submitted | |
5 | Omaha Public Power District | Mahmood Safi | Negative | Third-Party Comments | |
5 | Brazos Electric Power Cooperative, Inc. | Shari Heino | Negative | Third-Party Comments | |
6 | Powerex Corporation | Raj Hundal | Affirmative | N/A | |
6 | Lincoln Electric System | Eric Ruskamp | Affirmative | N/A | |
1 | Lincoln Electric System | Josh Johnson | Negative | Third-Party Comments | |
6 | Evergy | Jennifer Flandermeyer | Alan Kloster | Negative | Comments Submitted |
6 | Duke Energy | Greg Cecil | Negative | Comments Submitted | |
3 | Con Ed - Consolidated Edison Co. of New York | Peter Yost | Affirmative | N/A | |
4 | Electricities of North Carolina | Marcus Freeman | None | N/A | |
1 | Con Ed - Consolidated Edison Co. of New York | Dermot Smyth | Affirmative | N/A | |
5 | Lincoln Electric System | Jason Fortik | Negative | Comments Submitted | |
5 | Con Ed - Consolidated Edison Co. of New York | Helen Wang | Affirmative | N/A | |
1 | Central Iowa Power Cooperative | Kevin Lyons | Negative | Third-Party Comments | |
5 | CPS Energy | Robert Stevens | Negative | Comments Submitted | |
1 | Exelon | Daniel Gacek | Affirmative | N/A | |
5 | NextEra Energy | Summer Esquerre | Negative | Comments Submitted | |
6 | NRG - NRG Energy, Inc. | Martin Sidor | Negative | Comments Submitted | |
3 | Exelon | Kinte Whitehead | Affirmative | N/A | |
5 | Invenergy LLC | Rhonda Jones | Negative | Comments Submitted | |
5 | Talen Generation, LLC | Donald Lock | Negative | Third-Party Comments | |
1 | OGE Energy - Oklahoma Gas and Electric Co. | Terri Pyle | Affirmative | N/A | |
5 | OGE Energy - Oklahoma Gas and Electric Co. | Patrick Wells | Affirmative | N/A | |
1 | Gainesville Regional Utilities | David Owens | LaKenya Vannorman | Negative | Comments Submitted |
4 | Florida Municipal Power Agency | Dan O'Hagan | Negative | Comments Submitted | |
5 | Associated Electric Cooperative, Inc. | Chuck Booth | Negative | Comments Submitted | |
1 | American Transmission Company, LLC | LaTroy Brumfield | Negative | Comments Submitted | |
5 | Southern Indiana Gas and Electric Co. | Larry Rogers | Affirmative | N/A | |
1 | JEA | Joseph McClung | Negative | Comments Submitted | |
6 | Public Utility District No. 2 of Grant County, Washington | M LeRoy Patterson | Affirmative | N/A | |
3 | CPS Energy | Glenn Pressler | Negative | Comments Submitted | |
4 | Northern California Power Agency | Marty Hostler | Negative | Comments Submitted | |
3 | Northern California Power Agency | Michael Whitney | Negative | Comments Submitted | |
10 | Western Electricity Coordinating Council | Steven Rueckert | Affirmative | N/A | |
3 | Lincoln Electric System | Angelica Valencia | Negative | Comments Submitted | |
6 | Austin Energy | Lisa Martin | Negative | Comments Submitted | |
10 | Northeast Power Coordinating Council | Gerry Dunbar | Abstain | N/A | |
6 | Great River Energy | Donna Stephenson | Negative | Third-Party Comments | |
6 | Los Angeles Department of Water and Power | Anton Vu | Abstain | N/A | |
1 | Seattle City Light | Michael Jang | Abstain | N/A | |
5 | Great River Energy | Jacalynn Bentz | Negative | Third-Party Comments | |
5 | Black Hills Corporation | Derek Silbaugh | Jennifer Malon | Negative | Comments Submitted |
5 | APS - Arizona Public Service Co. | Michelle Amarantos | Negative | Comments Submitted | |
3 | Orlando Utilities Commission | Ballard Mutters | Negative | Third-Party Comments | |
1 | Lakeland Electric | Larry Watt | Negative | Third-Party Comments | |
3 | Owensboro Municipal Utilities | William Berry | Affirmative | N/A | |
3 | FirstEnergy - FirstEnergy Corporation | Aaron Ghodooshim | Negative | Comments Submitted | |
5 | PSEG - PSEG Fossil LLC | Tim Kucey | Negative | Third-Party Comments | |
1 | Arizona Electric Power Cooperative, Inc. | Jennifer Bray | Negative | Comments Submitted | |
5 | Los Angeles Department of Water and Power | Robert Kerrigan | None | N/A | |
3 | Los Angeles Department of Water and Power | Fausto Serratos | None | N/A | |
10 | Midwest Reliability Organization | William Steiner | Affirmative | N/A | |
1 | PNM Resources - Public Service Company of New Mexico | Lynn Goldstein | Affirmative | N/A | |
1 | Minnkota Power Cooperative Inc. | Theresa Allard | Negative | Third-Party Comments | |
5 | TransAlta Corporation | Ashley Scheelar | Negative | Comments Submitted | |
6 | Lakeland Electric | Paul Shipps | Negative | Third-Party Comments | |
1 | Avista - Avista Corporation | Mike Magruder | Negative | Comments Submitted | |
3 | Clark Public Utilities | Jack Stamper | Affirmative | N/A | |
6 | Salt River Project | Pam Syrjala | Negative | Comments Submitted | |
5 | Portland General Electric Co. | Ryan Olson | Affirmative | N/A | |
5 | Northern California Power Agency | Jeremy Lawson | Negative | Comments Submitted | |
1 | Portland General Electric Co. | Brooke Jockin | Affirmative | N/A | |
4 | Alliant Energy Corporation Services, Inc. | Larry Heckert | Negative | Comments Submitted | |
3 | Lakeland Electric | Steven Marshall | None | N/A | |
6 | Con Ed - Consolidated Edison Co. of New York | Michael Foley | Affirmative | N/A | |
1 | M and A Electric Power Cooperative | William Price | Negative | Third-Party Comments | |
3 | AEP | Kent Feliks | Negative | Comments Submitted | |
5 | Greybeard Compliance Services, LLC | Mike Gabriel | Negative | Third-Party Comments | |
1 | OTP - Otter Tail Power Company | Charles Wicklund | Negative | Third-Party Comments | |
1 | SaskPower | Wayne Guttormson | Abstain | N/A | |
5 | OTP - Otter Tail Power Company | Tammy Kubela | Negative | No Comment Submitted | |
3 | Edison International - Southern California Edison Company | Romel Aquino | None | N/A | |
3 | Salt River Project | Zack Heim | Negative | Third-Party Comments | |
3 | OTP - Otter Tail Power Company | Wendi Olson | Negative | Third-Party Comments | |
1 | Sacramento Municipal Utility District | Wei Shao | Tim Kelley | Negative | Comments Submitted |
5 | U.S. Bureau of Reclamation | Wendy Kalidass | Negative | Comments Submitted | |
1 | U.S. Bureau of Reclamation | Richard Jackson | Negative | Comments Submitted | |
5 | Tenaska, Inc. | Mark Young | Negative | Comments Submitted | |
6 | Black Hills Corporation | Claudine Bates | Negative | Comments Submitted | |
3 | Entergy | James Keele | Affirmative | N/A | |
5 | Edison International - Southern California Edison Company | Selene Willis | Affirmative | N/A | |
5 | Austin Energy | Michael Dillard | Negative | Comments Submitted | |
3 | Austin Energy | Michael Dieringer | Negative | Comments Submitted | |
4 | Austin Energy | Tony Hua | Negative | Comments Submitted | |
1 | Austin Energy | Thomas Standifur | Negative | Comments Submitted | |
1 | Entergy | Brian Lindsey | Affirmative | N/A | |
5 | LS Power Development, LLC | Mark Spencer | Negative | Comments Submitted | |
6 | Muscatine Power and Water | Nicholas Burns | Negative | Third-Party Comments | |
3 | Muscatine Power and Water | Seth Shoemaker | Negative | Third-Party Comments | |
1 | Black Hills Corporation | Micah Runner | Jennifer Malon | Negative | Comments Submitted |
1 | Muscatine Power and Water | Andrew Kurriger | Negative | Third-Party Comments | |
1 | Edison International - Southern California Edison Company | Jose Avendano Mora | Affirmative | N/A | |
6 | Edison International - Southern California Edison Company | Stephanie Kenny | None | N/A | |
3 | Tri-State G and T Association, Inc. | Janelle Marriott Gill | Negative | Comments Submitted | |
1 | Corn Belt Power Cooperative | Larry brusseau | Negative | Third-Party Comments | |
4 | American Public Power Association | John McCaffrey | Abstain | N/A | |
6 | Berkshire Hathaway - PacifiCorp | Lindsay Wickizer | Negative | Comments Submitted | |
1 | Orlando Utilities Commission | Aaron Staley | Affirmative | N/A | |
1 | Long Island Power Authority | Isidoro Behar | Abstain | N/A | |
3 | Florida Municipal Power Agency | Carl Turner | LaKenya Vannorman | Negative | Comments Submitted |
1 | VELCO -Vermont Electric Power Company, Inc. | Randall Buswell | None | N/A | |
6 | Sacramento Municipal Utility District | Charles Norton | Tim Kelley | Negative | Comments Submitted |
3 | JEA | Marilyn Williams | None | N/A | |
1 | PSEG - Public Service Electric and Gas Co. | Kyle Down | Negative | Third-Party Comments |