Ballot Results
Comment: View Comment Results
Ballot Name:
2010-05.3 Phase 3 of Protection Systems: Remedial Action Schemes PRC-012-2 IN 1 ST
Voting Start Date:
9/25/2015 12:01:00 AM
Voting End Date:
10/5/2015 8:00:00 PM
Ballot Type:
ST
Ballot Activity:
IN
Ballot Series:
1
Total # Votes:
267
Total Ballot Pool:
316
Quorum:
84.49
Weighted Segment Value:
48.11
Segment | Ballot Pool | Segment Weight | Affirmative Votes | Affirmative Fraction | Negative Votes w/ Comment | Negative Fraction w/ Comment | Negative Votes w/o Comment | Abstain | No Vote |
---|---|---|---|---|---|---|---|---|---|
Segment: 1 | 87 | 1 | 33 | 0.516 | 31 | 0.484 | 0 | 8 | 15 |
Segment: 2 | 9 | 0.8 | 3 | 0.3 | 5 | 0.5 | 0 | 0 | 1 |
Segment: 3 | 71 | 1 | 28 | 0.549 | 23 | 0.451 | 0 | 6 | 14 |
Segment: 4 | 23 | 1 | 8 | 0.444 | 10 | 0.556 | 0 | 3 | 2 |
Segment: 5 | 71 | 1 | 25 | 0.49 | 26 | 0.51 | 0 | 10 | 10 |
Segment: 6 | 43 | 1 | 14 | 0.424 | 19 | 0.576 | 0 | 4 | 6 |
Segment: 7 | 1 | 0.1 | 1 | 0.1 | 0 | 0 | 0 | 0 | 0 |
Segment: 8 | 2 | 0.1 | 1 | 0.1 | 0 | 0 | 0 | 1 | 0 |
Segment: 9 | 1 | 0.1 | 0 | 0 | 1 | 0.1 | 0 | 0 | 0 |
Segment: 10 | 8 | 0.6 | 3 | 0.3 | 3 | 0.3 | 0 | 1 | 1 |
Totals: | 316 | 6.7 | 116 | 3.224 | 118 | 3.476 | 0 | 33 | 49 |
Ballot Pool Members
Segment | Organization | Voter | Designated Proxy | Ballot | NERC Memo |
---|---|---|---|---|---|
3 | Austin Energy | Lisa Martin | Abstain | N/A | |
5 | Avista - Avista Corporation | Steve Wenke | Affirmative | N/A | |
4 | WEC Energy Group, Inc. | Anthony Jankowski | Negative | Comments Submitted | |
10 | Northeast Power Coordinating Council | Guy V. Zito | Negative | Comments Submitted | |
1 | Peak Reliability | Jared Shakespeare | Negative | Comments Submitted | |
4 | Austin Energy | Tina Garvey | Abstain | N/A | |
5 | APS - Arizona Public Service Co. | Stephanie Little | Negative | Comments Submitted | |
6 | Tennessee Valley Authority | Marjorie Parsons | Negative | Comments Submitted | |
6 | Cleco Corporation | Robert Hirchak | Louis Guidry | Affirmative | N/A |
5 | Pacific Gas and Electric Company | Alex Chua | Abstain | N/A | |
1 | United Illuminating Co. | Jonathan Appelbaum | Negative | Third-Party Comments | |
1 | Berkshire Hathaway Energy - MidAmerican Energy Co. | Terry Harbour | Affirmative | N/A | |
1 | Con Ed - Consolidated Edison Co. of New York | Chris de Graffenried | Negative | Comments Submitted | |
6 | Con Ed - Consolidated Edison Co. of New York | Robert Winston | Negative | Comments Submitted | |
5 | Con Ed - Consolidated Edison Co. of New York | Brian O'Boyle | Negative | Comments Submitted | |
3 | Tallahassee Electric (City of Tallahassee, FL) | John Williams | Abstain | N/A | |
6 | Seminole Electric Cooperative, Inc. | Trudy Novak | Negative | Comments Submitted | |
5 | NiSource - Northern Indiana Public Service Co. | Kathryn Tackett | None | N/A | |
3 | BC Hydro and Power Authority | Pat Harrington | Affirmative | N/A | |
4 | FirstEnergy - Ohio Edison Company | Doug Hohlbaugh | Affirmative | N/A | |
5 | Austin Energy | Jeanie Doty | Abstain | N/A | |
3 | Bonneville Power Administration | Rebecca Berdahl | Negative | Comments Submitted | |
3 | Puget Sound Energy, Inc. | Andrea Basinski | Affirmative | N/A | |
1 | BC Hydro and Power Authority | Patricia Robertson | Affirmative | N/A | |
3 | Tennessee Valley Authority | Ian Grant | Negative | Comments Submitted | |
2 | Electric Reliability Council of Texas, Inc. | Kennedy Meier | None | N/A | |
1 | National Grid USA | Michael Jones | Negative | Third-Party Comments | |
5 | Cleco Corporation | Stephanie Huffman | Louis Guidry | Affirmative | N/A |
4 | Florida Municipal Power Agency | Carol Chinn | Negative | Comments Submitted | |
3 | Florida Municipal Power Agency | Joe McKinney | Negative | Comments Submitted | |
6 | Florida Municipal Power Agency | Richard Montgomery | Negative | Comments Submitted | |
5 | Florida Municipal Power Agency | David Schumann | Negative | Comments Submitted | |
5 | Lakeland Electric | Carmen Rodriguez | None | N/A | |
1 | Beaches Energy Services | Don Cuevas | Negative | Third-Party Comments | |
3 | City of Green Cove Springs | Mark Schultz | Negative | Third-Party Comments | |
4 | Keys Energy Services | Stanley Rzad | Negative | Third-Party Comments | |
4 | City of Clewiston | Lynne Mila | Negative | Third-Party Comments | |
4 | City of New Smyrna Beach Utilities Commission | Tim Beyrle | Negative | Third-Party Comments | |
3 | Beaches Energy Services | Steven Lancaster | Negative | Third-Party Comments | |
3 | City of Leesburg | Chris Adkins | Negative | Third-Party Comments | |
3 | Lakeland Electric | Mace Hunter | Negative | Third-Party Comments | |
1 | Cleco Corporation | John Lindsey | Louis Guidry | Affirmative | N/A |
5 | BC Hydro and Power Authority | Clement Ma | Affirmative | N/A | |
1 | NextEra Energy - Florida Power and Light Co. | Mike ONeil | Negative | Comments Submitted | |
4 | Illinois Municipal Electric Agency | Bob Thomas | Negative | Comments Submitted | |
3 | National Grid USA | Brian Shanahan | Negative | Third-Party Comments | |
1 | Western Area Power Administration | Ben Hammer | None | N/A | |
4 | Seattle City Light | Hao Li | Negative | Comments Submitted | |
1 | Unisource - Tucson Electric Power Co. | Jessica Cordero | None | N/A | |
4 | Blue Ridge Power Agency | Duane Dahlquist | Affirmative | N/A | |
1 | Salt River Project | Steven Cobb | Negative | Comments Submitted | |
1 | PPL Electric Utilities Corporation | Brenda Truhe | Affirmative | N/A | |
5 | NB Power Corporation | Rob Vance | Negative | Third-Party Comments | |
5 | Dynegy Inc. | Dan Roethemeyer | Affirmative | N/A | |
10 | Midwest Reliability Organization | Russel Mountjoy | Affirmative | N/A | |
6 | Florida Municipal Power Pool | Tom Reedy | Negative | Third-Party Comments | |
4 | Utility Services, Inc. | Brian Evans-Mongeon | Negative | Third-Party Comments | |
5 | NextEra Energy | Allen Schriver | Negative | Comments Submitted | |
5 | Ameren - Ameren Missouri | Sam Dwyer | None | N/A | |
5 | Hydro-Qu?bec Production | Roger Dufresne | Abstain | N/A | |
5 | AEP | Thomas Foltz | Affirmative | N/A | |
1 | Southern Company - Southern Company Services, Inc. | Robert A. Schaffeld | Negative | Comments Submitted | |
3 | Southern Company - Alabama Power Company | R. Scott Moore | Negative | Comments Submitted | |
1 | International Transmission Company Holdings Corporation | Michael Moltane | Affirmative | N/A | |
5 | Southern Company - Southern Company Generation | William D. Shultz | Negative | Comments Submitted | |
6 | Southern Company - Southern Company Generation and Energy Marketing | John J. Ciza | Negative | Comments Submitted | |
5 | Choctaw Generation Limited Partnership, LLLP | Rob Watson | Negative | Third-Party Comments | |
3 | Grand River Dam Authority | Jeff Wells | Affirmative | N/A | |
5 | Oglethorpe Power Corporation | Donna Johnson | None | N/A | |
5 | Brazos Electric Power Cooperative, Inc. | Shari Heino | Negative | Third-Party Comments | |
3 | Georgia System Operations Corporation | Scott McGough | Affirmative | N/A | |
6 | WEC Energy Group, Inc. | David Boeshaar | None | N/A | |
1 | Tennessee Valley Authority | Howell Scott | Negative | Comments Submitted | |
1 | American Transmission Company, LLC | Andrew Pusztai | Negative | Comments Submitted | |
4 | Georgia System Operations Corporation | Guy Andrews | Affirmative | N/A | |
1 | Santee Cooper | Chris Wagner | None | N/A | |
6 | Santee Cooper | Marty Watson | None | N/A | |
3 | Santee Cooper | Vicky Budreau | None | N/A | |
5 | Los Angeles Department of Water and Power | Robert Kerrigan | None | N/A | |
5 | Tennessee Valley Authority | Brandy Spraker | Dennis Chastain | Negative | Comments Submitted |
1 | Seattle City Light | Pawel Krupa | Negative | Comments Submitted | |
5 | Seattle City Light | Mike Haynes | Negative | Comments Submitted | |
5 | SCANA - South Carolina Electric and Gas Co. | Alyssa Hubbard | None | N/A | |
6 | Dominion - Dominion Resources, Inc. | Louis Slade | Negative | Comments Submitted | |
5 | Nebraska Public Power District | Don Schmit | Negative | Comments Submitted | |
1 | Arizona Electric Power Cooperative, Inc. | John Shaver | Negative | Third-Party Comments | |
1 | Tri-State G and T Association, Inc. | Tracy Sliman | Affirmative | N/A | |
3 | Hydro One Networks, Inc. | Paul Malozewski | Negative | Comments Submitted | |
5 | Puget Sound Energy, Inc. | Lynda Kupfer | Affirmative | N/A | |
4 | Alliant Energy Corporation Services, Inc. | Larry Heckert | None | N/A | |
5 | New York Power Authority | Wayne Sipperly | Negative | Third-Party Comments | |
1 | New York Power Authority | Salvatore Spagnolo | Negative | Third-Party Comments | |
1 | Platte River Power Authority | Marissa Archie | None | N/A | |
5 | Great River Energy | Preston Walsh | Negative | Third-Party Comments | |
3 | Edison International - Southern California Edison Company | Romel Aquino | None | N/A | |
3 | Great River Energy | Brian Glover | Negative | Third-Party Comments | |
5 | Massachusetts Municipal Wholesale Electric Company | David Gordon | Abstain | N/A | |
5 | City of Independence, Power and Light Department | Jim Nail | Affirmative | N/A | |
4 | South Mississippi Electric Power Association | Matthew Dyar | None | N/A | |
2 | ISO New England, Inc. | Michael Puscas | John Pearson | Negative | Comments Submitted |
1 | Manitoba Hydro | Mike Smith | Negative | Comments Submitted | |
1 | Black Hills Corporation | Micah Runner | None | N/A | |
1 | Public Utility District No. 2 of Grant County, Washington | Michiko Sell | Affirmative | N/A | |
1 | CenterPoint Energy Houston Electric, LLC | John Brockhan | Abstain | N/A | |
1 | Georgia Transmission Corporation | Jason Snodgrass | Greg Davis | Affirmative | N/A |
2 | California ISO | Richard Vine | Negative | Comments Submitted | |
1 | Tacoma Public Utilities (Tacoma, WA) | John Merrell | Negative | Comments Submitted | |
5 | Edison International - Southern California Edison Company | Selene Willis | None | N/A | |
6 | Great River Energy | Donna Stephenson | Michael Brytowski | Negative | Third-Party Comments |
3 | NiSource - Northern Indiana Public Service Co. | Ramon Barany | Abstain | N/A | |
5 | OGE Energy - Oklahoma Gas and Electric Co. | Leo Staples | Affirmative | N/A | |
1 | PSEG - Public Service Electric and Gas Co. | Joseph Smith | Negative | Comments Submitted | |
3 | Seminole Electric Cooperative, Inc. | James Frauen | Negative | Comments Submitted | |
1 | Ameren - Ameren Services | Tamara Evey | None | N/A | |
3 | Basin Electric Power Cooperative | Jeremy Voll | Affirmative | N/A | |
5 | Basin Electric Power Cooperative | Mike Kraft | Affirmative | N/A | |
3 | Colorado Springs Utilities | Charles Morgan | Affirmative | N/A | |
6 | Colorado Springs Utilities | Shannon Fair | Affirmative | N/A | |
1 | Seminole Electric Cooperative, Inc. | Mark Churilla | Bret Galbraith | Negative | Comments Submitted |
5 | WEC Energy Group, Inc. | Linda Horn | Negative | Comments Submitted | |
9 | Commonwealth of Massachusetts Department of Public Utilities | Donald Nelson | Negative | Third-Party Comments | |
10 | ReliabilityFirst | Anthony Jablonski | Negative | Comments Submitted | |
3 | PSEG - Public Service Electric and Gas Co. | Jeffrey Mueller | Negative | Comments Submitted | |
3 | Seattle City Light | Dana Wheelock | Negative | Comments Submitted | |
3 | Con Ed - Consolidated Edison Co. of New York | Peter Yost | Negative | Comments Submitted | |
5 | Public Utility District No. 2 of Grant County, Washington | Alex Ybarra | Affirmative | N/A | |
6 | Platte River Power Authority | Sabrina Martz | None | N/A | |
1 | VELCO -Vermont Electric Power Company, Inc. | Randall Buswell | None | N/A | |
6 | Xcel Energy, Inc. | Peter Colussy | Negative | Comments Submitted | |
5 | Sacramento Municipal Utility District | Susan Gill-Zobitz | Joe Tarantino | Affirmative | N/A |
2 | BC Hydro and Power Authority | Venkataramakrishnan Vinnakota | Affirmative | N/A | |
1 | Sacramento Municipal Utility District | Tim Kelley | Joe Tarantino | Affirmative | N/A |
4 | Sacramento Municipal Utility District | Michael Ramirez | Joe Tarantino | Affirmative | N/A |
6 | Sacramento Municipal Utility District | Diane Clark | Joe Tarantino | Affirmative | N/A |
3 | Sacramento Municipal Utility District | Rachel Moore | Joe Tarantino | Affirmative | N/A |
6 | NiSource - Northern Indiana Public Service Co. | Joseph OBrien | Abstain | N/A | |
1 | Balancing Authority of Northern California | Kevin Smith | Joe Tarantino | Affirmative | N/A |
6 | Lower Colorado River Authority | Michael Shaw | Negative | Comments Submitted | |
3 | Los Angeles Department of Water and Power | Mike Anctil | Affirmative | N/A | |
5 | PSEG - PSEG Fossil LLC | Tim Kucey | Negative | Comments Submitted | |
1 | Los Angeles Department of Water and Power | faranak sarbaz | Affirmative | N/A | |
5 | Xcel Energy, Inc. | Mark Castagneri | Negative | Comments Submitted | |
1 | Bryan Texas Utilities | Mary Downs | None | N/A | |
3 | Ameren - Ameren Services | David Jendras Sr | None | N/A | |
5 | Salt River Project | Kevin Nielsen | Negative | Comments Submitted | |
3 | Muscatine Power and Water | Seth Shoemaker | Abstain | N/A | |
6 | Salt River Project | William Abraham | Negative | Comments Submitted | |
1 | Oncor Electric Delivery | Rod Kinard | Gul Khan | Negative | Comments Submitted |
3 | Salt River Project | Mathew Weber | None | N/A | |
5 | Berkshire Hathaway - NV Energy | Eric Schwarzrock | Jeffrey Watkins | Affirmative | N/A |
3 | Clark Public Utilities | Jack Stamper | Affirmative | N/A | |
7 | Luminant Mining Company LLC | Stewart Rake | Affirmative | N/A | |
2 | Independent Electricity System Operator | Leonard Kula | Negative | Comments Submitted | |
3 | JEA | Marilyn Williams | None | N/A | |
1 | Exelon | Daniel Gacek | Affirmative | N/A | |
3 | Exelon | Kinte Whitehead | Affirmative | N/A | |
5 | Exelon | Vince Catania | Affirmative | N/A | |
6 | Exelon | Dave Carlson | Affirmative | N/A | |
1 | Hydro-Qu?bec TransEnergie | Martin Boisvert | Negative | Third-Party Comments | |
1 | Great Plains Energy - Kansas City Power and Light Co. | James McBee | Douglas Webb | Affirmative | N/A |
6 | Muscatine Power and Water | Ryan Streck | Abstain | N/A | |
1 | Dairyland Power Cooperative | Robert Roddy | Abstain | N/A | |
1 | FirstEnergy - FirstEnergy Corporation | William Smith | Affirmative | N/A | |
6 | FirstEnergy - FirstEnergy Solutions | Ann Carey | Affirmative | N/A | |
3 | FirstEnergy - FirstEnergy Corporation | Theresa Ciancio | Affirmative | N/A | |
5 | Great Plains Energy - Kansas City Power and Light Co. | Harold Wyble | Douglas Webb | Affirmative | N/A |
3 | Great Plains Energy - Kansas City Power and Light Co. | Jessica Tucker | Douglas Webb | Affirmative | N/A |
5 | FirstEnergy - FirstEnergy Solutions | Robert Loy | Affirmative | N/A | |
6 | Berkshire Hathaway - PacifiCorp | Sandra Shaffer | Affirmative | N/A | |
2 | Midcontinent ISO, Inc. | Terry BIlke | Negative | Third-Party Comments | |
1 | NorthWestern Energy | Belinda Tierney | None | N/A | |
6 | Great Plains Energy - Kansas City Power and Light Co. | Chris Bridges | Douglas Webb | Affirmative | N/A |
4 | Public Utility District No. 1 of Snohomish County | John D. Martinsen | Affirmative | N/A | |
6 | Snohomish County PUD No. 1 | Kenn Backholm | Affirmative | N/A | |
5 | Public Utility District No. 1 of Snohomish County | Sam Nietfeld | Affirmative | N/A | |
1 | Public Utility District No. 1 of Snohomish County | Long Duong | Affirmative | N/A | |
3 | Snohomish County PUD No. 1 | Mark Oens | Affirmative | N/A | |
3 | CMS Energy - Consumers Energy Company | Karl Blaszkowski | Affirmative | N/A | |
5 | DTE Energy - Detroit Edison Company | Jeffrey DePriest | Abstain | N/A | |
4 | DTE Energy - Detroit Edison Company | Daniel Herring | Abstain | N/A | |
3 | DTE Energy - Detroit Edison Company | Kent Kujala | Abstain | N/A | |
3 | APS - Arizona Public Service Co. | Jeri Freimuth | Negative | Comments Submitted | |
1 | NiSource - Northern Indiana Public Service Co. | Julaine Dyke | Abstain | N/A | |
3 | MEAG Power | Roger Brand | Scott Miller | Affirmative | N/A |
1 | MEAG Power | David Weekley | Scott Miller | Affirmative | N/A |
5 | MEAG Power | Steven Grego | Scott Miller | Affirmative | N/A |
6 | Bonneville Power Administration | Alex Spain | Negative | Comments Submitted | |
1 | Edison International - Southern California Edison Company | Steven Mavis | Affirmative | N/A | |
1 | PHI - Potomac Electric Power Co. | David Thorne | Affirmative | N/A | |
2 | PJM Interconnection, L.L.C. | Mark Holman | Affirmative | N/A | |
1 | Lower Colorado River Authority | Teresa Krabe | Negative | Comments Submitted | |
6 | Talen Energy Marketing, LLC | Jennifer Hohenshilt | None | N/A | |
3 | PHI - Potomac Electric Power Co. | Mark Yerger | Affirmative | N/A | |
3 | New York Power Authority | David Rivera | Negative | Third-Party Comments | |
5 | City and County of San Francisco | Margaret Hannaford | None | N/A | |
1 | Tallahassee Electric (City of Tallahassee, FL) | Scott Langston | Abstain | N/A | |
6 | New York Power Authority | Shivaz Chopra | Negative | Third-Party Comments | |
5 | CMS Energy - Consumers Energy Company | David Greyerbiehl | Affirmative | N/A | |
1 | Entergy - Entergy Services, Inc. | Oliver Burke | Affirmative | N/A | |
3 | WEC Energy Group, Inc. | James Keller | Negative | Comments Submitted | |
4 | CMS Energy - Consumers Energy Company | Julie Hegedus | Affirmative | N/A | |
2 | Herb Schrayshuen | Herb Schrayshuen | Negative | Third-Party Comments | |
6 | APS - Arizona Public Service Co. | Bobbi Welch | Negative | Comments Submitted | |
6 | AEP - AEP Marketing | Edward P Cox | Affirmative | N/A | |
5 | Lower Colorado River Authority | Dixie Wells | Negative | Comments Submitted | |
3 | OGE Energy - Oklahoma Gas and Electric Co. | Donald Hargrove | Affirmative | N/A | |
1 | Ohio Valley Electric Corporation | Scott Cunningham | Affirmative | N/A | |
1 | OTP - Otter Tail Power Company | Charles Wicklund | Abstain | N/A | |
1 | Nebraska Public Power District | Jamison Cawley | Negative | Comments Submitted | |
3 | City of Redding | Elizabeth Hadley | Affirmative | N/A | |
1 | AEP - AEP Service Corporation | Dennis Sauriol | None | N/A | |
8 | David Kiguel | David Kiguel | Abstain | N/A | |
1 | Omaha Public Power District | Doug Peterchuck | None | N/A | |
1 | OGE Energy - Oklahoma Gas and Electric Co. | Terri Pyle | Affirmative | N/A | |
1 | SCANA - South Carolina Electric and Gas Co. | Tom Hanzlik | None | N/A | |
1 | Hydro One Networks, Inc. | Payam Farahbakhsh | Negative | Comments Submitted | |
3 | Xcel Energy, Inc. | Michael Ibold | Negative | Comments Submitted | |
1 | PNM Resources - Public Service Company of New Mexico | Laurie Williams | Affirmative | N/A | |
10 | SERC Reliability Corporation | Dave Krueger | None | N/A | |
6 | City of Redding | Marvin Briggs | Bill Hughes | Affirmative | N/A |
1 | Xcel Energy, Inc. | Dean Schiro | Negative | Comments Submitted | |
1 | Portland General Electric Co. | John Walker | Affirmative | N/A | |
3 | Eversource Energy | Mark Kenny | Negative | Comments Submitted | |
3 | SCANA - South Carolina Electric and Gas Co. | Scott Parker | None | N/A | |
3 | Avista - Avista Corporation | Scott Kinney | Affirmative | N/A | |
1 | IDACORP - Idaho Power Company | Molly Devine | Affirmative | N/A | |
4 | Public Utility District No. 2 of Grant County, Washington | Yvonne McMackin | Affirmative | N/A | |
3 | Cleco Corporation | Michelle Corley | Louis Guidry | Affirmative | N/A |
3 | Portland General Electric Co. | Thomas Ward | Affirmative | N/A | |
1 | Associated Electric Cooperative, Inc. | Phil Hart | Affirmative | N/A | |
1 | Central Electric Power Cooperative (Missouri) | Michael Bax | Affirmative | N/A | |
6 | Associated Electric Cooperative, Inc. | Brian Ackermann | Affirmative | N/A | |
3 | Associated Electric Cooperative, Inc. | Todd Bennett | Affirmative | N/A | |
1 | Colorado Springs Utilities | Shawna Speer | Affirmative | N/A | |
1 | Northeast Missouri Electric Power Cooperative | Kevin White | Affirmative | N/A | |
1 | KAMO Electric Cooperative | Micah Breedlove | None | N/A | |
6 | Portland General Electric Co. | Shawn Davis | Affirmative | N/A | |
5 | Lincoln Electric System | Kayleigh Wilkerson | Abstain | N/A | |
3 | Sho-Me Power Electric Cooperative | Jarrod Murdaugh | None | N/A | |
5 | Luminant - Luminant Generation Company LLC | Alshare Hughes | None | N/A | |
5 | Platte River Power Authority | Tyson Archie | Abstain | N/A | |
3 | Nebraska Public Power District | Tony Eddleman | Negative | Comments Submitted | |
3 | M and A Electric Power Cooperative | Stephen Pogue | Affirmative | N/A | |
1 | Sho-Me Power Electric Cooperative | Olivia Olson | None | N/A | |
3 | KAMO Electric Cooperative | Ted Hilmes | Affirmative | N/A | |
1 | APS - Arizona Public Service Co. | Michelle Amarantos | Negative | Comments Submitted | |
8 | Massachusetts Attorney General | Frederick Plett | Affirmative | N/A | |
10 | Southwest Power Pool Regional Entity | Bob Reynolds | Affirmative | N/A | |
5 | Boise-Kuna Irrigation District - Lucky Peak Power Plant Project | Mike Kukla | Negative | Third-Party Comments | |
1 | N.W. Electric Power Cooperative, Inc. | Mark Ramsey | Affirmative | N/A | |
3 | NW Electric Power Cooperative, Inc. | John Stickley | Affirmative | N/A | |
4 | MGE Energy - Madison Gas and Electric Co. | Joseph DePoorter | Abstain | N/A | |
3 | Dominion - Dominion Resources, Inc. | Connie Schroeder | Negative | Comments Submitted | |
5 | Dominion - Dominion Resources, Inc. | Randi Heise | Negative | Comments Submitted | |
1 | Dominion - Dominion Virginia Power | Larry Nash | Negative | Comments Submitted | |
5 | Omaha Public Power District | Mahmood Safi | Abstain | N/A | |
3 | AEP | Leshel Hutchings | None | N/A | |
1 | Lincoln Electric System | Doug Bantam | Abstain | N/A | |
6 | Duke Energy | Greg Cecil | Affirmative | N/A | |
5 | Manitoba Hydro | Yuguang Xiao | Negative | Comments Submitted | |
5 | Muscatine Power and Water | Mike Avesing | Abstain | N/A | |
5 | Bonneville Power Administration | Francis Halpin | Negative | Comments Submitted | |
5 | Entergy - Entergy Services, Inc. | Tracey Stubbs | Affirmative | N/A | |
5 | Duke Energy | Dale Goodwine | Affirmative | N/A | |
3 | City Utilities of Springfield, Missouri | Scott Williams | Abstain | N/A | |
1 | Long Island Power Authority | Robert Ganley | Negative | Third-Party Comments | |
3 | Public Utility District No. 1 of Okanogan County | Dale Dunckel | None | N/A | |
1 | Sunflower Electric Power Corporation | Bertha Ellen Watkins | Negative | Third-Party Comments | |
3 | Pacific Gas and Electric Company | Sandra Ellis | None | N/A | |
3 | Tacoma Public Utilities (Tacoma, WA) | John Nierenberg | None | N/A | |
6 | Manitoba Hydro | Blair Mukanik | Negative | Comments Submitted | |
6 | Austin Energy | Andrew Gallo | Abstain | N/A | |
5 | Tacoma Public Utilities (Tacoma, WA) | Chris Mattson | Negative | Comments Submitted | |
6 | Ameren - Ameren Services | Robert Quinlivan | None | N/A | |
4 | City of Redding | Nick Zettel | Affirmative | N/A | |
5 | City of Redding | Paul Cummings | Bill Hughes | Affirmative | N/A |
1 | CPS Energy | Glenn Pressler | Abstain | N/A | |
6 | Tacoma Public Utilities (Tacoma, WA) | Rick Applegate | Negative | Comments Submitted | |
3 | Central Electric Power Cooperative (Missouri) | Adam Weber | Affirmative | N/A | |
1 | Puget Sound Energy, Inc. | Theresa Rakowsky | Affirmative | N/A | |
1 | M and A Electric Power Cooperative | William Price | Affirmative | N/A | |
6 | Lincoln Electric System | Eric Ruskamp | Abstain | N/A | |
6 | Seattle City Light | Charles Freeman | Negative | Comments Submitted | |
6 | Luminant - Luminant Energy | Brenda Hampton | Affirmative | N/A | |
3 | Ocala Utility Services | Neville Bowen | None | N/A | |
5 | Talen Generation, LLC | Donald Lock | Affirmative | N/A | |
3 | PPL - Louisville Gas and Electric Co. | Charles Freibert | Affirmative | N/A | |
3 | Manitoba Hydro | Karim Abdel-Hadi | Negative | Comments Submitted | |
3 | Tri-State G and T Association, Inc. | Janelle Marriott Gill | Affirmative | N/A | |
6 | NextEra Energy - Florida Power and Light Co. | Silvia Mitchell | Negative | Comments Submitted | |
3 | Omaha Public Power District | David Heins | None | N/A | |
1 | Avista - Avista Corporation | Bryan Cox | Rich Hydzik | Affirmative | N/A |
1 | Muscatine Power and Water | Andrew Kurriger | Abstain | N/A | |
4 | Tacoma Public Utilities (Tacoma, WA) | Hien Ho | Negative | Comments Submitted | |
5 | JEA | John Babik | Affirmative | N/A | |
3 | Northeast Missouri Electric Power Cooperative | Skyler Wiegmann | None | N/A | |
10 | Texas Reliability Entity, Inc. | Rachel Coyne | Negative | Comments Submitted | |
5 | Tri-State G and T Association, Inc. | Mark Stein | Affirmative | N/A | |
10 | Western Electricity Coordinating Council | Steven Rueckert | Affirmative | N/A | |
5 | Utility System Efficiencies, Inc. (USE) | Catrina Martin | Affirmative | N/A | |
5 | U.S. Bureau of Reclamation | Erika Doot | Negative | Comments Submitted | |
1 | U.S. Bureau of Reclamation | Richard Jackson | Negative | Comments Submitted | |
1 | Great River Energy | Gordon Pietsch | None | N/A | |
4 | Seminole Electric Cooperative, Inc. | Michael Ward | Negative | Comments Submitted | |
6 | PSEG - PSEG Energy Resources and Trade LLC | Karla Barton | Negative | Comments Submitted | |
5 | OTP - Otter Tail Power Company | Cathy Fogale | Abstain | N/A | |
1 | Transmission Agency of Northern California | Amy Cuellar | Negative | Comments Submitted | |
2 | Southwest Power Pool, Inc. (RTO) | Charles Yeung | Affirmative | N/A | |
5 | NextEra Energy | Richard Vendetti | None | N/A | |
5 | Seminole Electric Cooperative, Inc. | Brenda Atkins | Negative | Comments Submitted | |
10 | Florida Reliability Coordinating Council | Peter Heidrich | Abstain | N/A | |
5 | Kissimmee Utility Authority | Mike Blough | Negative | Third-Party Comments | |
1 | Bonneville Power Administration | Donald Watkins | Negative | Comments Submitted | |
1 | Duke Energy | Doug Hils | Affirmative | N/A | |
1 | NB Power Corporation | Alan MacNaughton | Negative | Third-Party Comments | |
6 | Lakeland Electric | Paul Shipps | None | N/A |