Ballot Results
Comment: View Comment Results
Ballot Name:
2019-02 BES Cyber System Information Access Management CIP-011-3 AB 3 ST
Voting Start Date:
4/30/2021 12:01:00 AM
Voting End Date:
5/10/2021 8:00:00 PM
Ballot Type:
ST
Ballot Activity:
AB
Ballot Series:
3
Total # Votes:
231
Total Ballot Pool:
273
Quorum:
84.62
Quorum Established Date:
5/10/2021 4:43:25 PM
Weighted Segment Value:
81.39
Segment | Ballot Pool | Segment Weight | Affirmative Votes | Affirmative Fraction | Negative Votes w/ Comment | Negative Fraction w/ Comment | Negative Votes w/o Comment | Abstain | No Vote |
---|---|---|---|---|---|---|---|---|---|
Segment: 1 | 77 | 1 | 39 | 0.796 | 10 | 0.204 | 2 | 10 | 16 |
Segment: 2 | 2 | 0.2 | 2 | 0.2 | 0 | 0 | 0 | 0 | 0 |
Segment: 3 | 59 | 1 | 38 | 0.826 | 8 | 0.174 | 0 | 5 | 8 |
Segment: 4 | 17 | 1 | 10 | 1 | 0 | 0 | 0 | 3 | 4 |
Segment: 5 | 67 | 1 | 43 | 0.811 | 10 | 0.189 | 0 | 7 | 7 |
Segment: 6 | 44 | 1 | 22 | 0.688 | 10 | 0.313 | 0 | 5 | 7 |
Segment: 7 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Segment: 8 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 0 |
Segment: 9 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Segment: 10 | 6 | 0.6 | 4 | 0.4 | 2 | 0.2 | 0 | 0 | 0 |
Totals: | 273 | 5.8 | 158 | 4.721 | 40 | 1.079 | 2 | 31 | 42 |
Ballot Pool Members
Segment | Organization | Voter | Designated Proxy | Ballot | NERC Memo |
---|---|---|---|---|---|
3 | Con Ed - Consolidated Edison Co. of New York | Peter Yost | Affirmative | N/A | |
6 | Con Ed - Consolidated Edison Co. of New York | Cristhian Godoy | Affirmative | N/A | |
4 | Utility Services, Inc. | Brian Evans-Mongeon | None | N/A | |
3 | Ameren - Ameren Services | David Jendras | Affirmative | N/A | |
3 | WEC Energy Group, Inc. | Thomas Breene | Affirmative | N/A | |
5 | Ontario Power Generation Inc. | Constantin Chitescu | Affirmative | N/A | |
5 | Edison International - Southern California Edison Company | Selene Willis | Affirmative | N/A | |
3 | MEAG Power | Roger Brand | Abstain | N/A | |
5 | Con Ed - Consolidated Edison Co. of New York | Avani Pandya | Affirmative | N/A | |
1 | MEAG Power | David Weekley | Abstain | N/A | |
1 | IDACORP - Idaho Power Company | Mike Marshall | Abstain | N/A | |
4 | Seminole Electric Cooperative, Inc. | Jonathan Robbins | Abstain | N/A | |
1 | Con Ed - Consolidated Edison Co. of New York | Dermot Smyth | Affirmative | N/A | |
6 | WEC Energy Group, Inc. | David Hathaway | Affirmative | N/A | |
2 | Independent Electricity System Operator | Leonard Kula | Affirmative | N/A | |
5 | Massachusetts Municipal Wholesale Electric Company | Anthony Stevens | Affirmative | N/A | |
3 | Sempra - San Diego Gas and Electric | Bridget Silvia | Affirmative | N/A | |
3 | Basin Electric Power Cooperative | Jeremy Voll | Negative | Comments Submitted | |
3 | Edison International - Southern California Edison Company | Romel Aquino | Negative | Comments Submitted | |
5 | NRG - NRG Energy, Inc. | Patricia Lynch | Affirmative | N/A | |
1 | National Grid USA | Michael Jones | Affirmative | N/A | |
1 | Western Area Power Administration | sean erickson | Barry Jones | Negative | Comments Submitted |
1 | Edison International - Southern California Edison Company | Jose Avendano Mora | Affirmative | N/A | |
1 | Ameren - Ameren Services | Tamara Evey | None | N/A | |
6 | Ameren - Ameren Services | Robert Quinlivan | Affirmative | N/A | |
6 | Black Hills Corporation | Claudine Bates | None | N/A | |
3 | National Grid USA | Brian Shanahan | Affirmative | N/A | |
5 | Ameren - Ameren Missouri | Sam Dwyer | Affirmative | N/A | |
1 | Balancing Authority of Northern California | Kevin Smith | Joe Tarantino | Affirmative | N/A |
6 | Sacramento Municipal Utility District | Jamie Cutlip | Joe Tarantino | Affirmative | N/A |
5 | Sacramento Municipal Utility District | Nicole Goi | Joe Tarantino | Affirmative | N/A |
4 | Sacramento Municipal Utility District | Beth Tincher | Joe Tarantino | Affirmative | N/A |
1 | Sacramento Municipal Utility District | Arthur Starkovich | Joe Tarantino | Affirmative | N/A |
3 | Sacramento Municipal Utility District | Nicole Looney | Joe Tarantino | Affirmative | N/A |
1 | International Transmission Company Holdings Corporation | Michael Moltane | Gail Elliott | Affirmative | N/A |
6 | Seattle City Light | Brian Belger | Abstain | N/A | |
3 | Puget Sound Energy, Inc. | Nicolas Pacholski | Affirmative | N/A | |
6 | PPL - Louisville Gas and Electric Co. | Linn Oelker | Affirmative | N/A | |
3 | PPL - Louisville Gas and Electric Co. | James Frank | Affirmative | N/A | |
3 | APS - Arizona Public Service Co. | Jessica Lopez | Affirmative | N/A | |
4 | Seattle City Light | Hao Li | Abstain | N/A | |
5 | Puget Sound Energy, Inc. | Lynn Murphy | Abstain | N/A | |
6 | Western Area Power Administration | Erin Green | Negative | Comments Submitted | |
5 | Sempra - San Diego Gas and Electric | Jennifer Wright | Affirmative | N/A | |
3 | Tennessee Valley Authority | Ian Grant | Affirmative | N/A | |
1 | Tennessee Valley Authority | Gabe Kurtz | Affirmative | N/A | |
1 | Nebraska Public Power District | Jamison Cawley | None | N/A | |
10 | New York State Reliability Council | ALAN ADAMSON | Affirmative | N/A | |
1 | City Utilities of Springfield, Missouri | Michael Bowman | Affirmative | N/A | |
4 | City Utilities of Springfield, Missouri | John Allen | Affirmative | N/A | |
5 | Avista - Avista Corporation | Glen Farmer | Affirmative | N/A | |
1 | SaskPower | Wayne Guttormson | Abstain | N/A | |
1 | Allete - Minnesota Power, Inc. | Jamie Monette | None | N/A | |
1 | APS - Arizona Public Service Co. | Daniela Atanasovski | Affirmative | N/A | |
10 | Midwest Reliability Organization | William Steiner | Negative | Comments Submitted | |
5 | APS - Arizona Public Service Co. | Michelle Amarantos | Affirmative | N/A | |
6 | Public Utility District No. 2 of Grant County, Washington | LeRoy Patterson | Affirmative | N/A | |
6 | APS - Arizona Public Service Co. | Marcus Bortman | Affirmative | N/A | |
5 | Public Utility District No. 2 of Grant County, Washington | Amy Jones | Affirmative | N/A | |
1 | Dairyland Power Cooperative | Steve Ritscher | Abstain | N/A | |
3 | Berkshire Hathaway Energy - MidAmerican Energy Co. | Darnez Gresham | Negative | Comments Submitted | |
3 | Tacoma Public Utilities (Tacoma, WA) | Marc Donaldson | Jennie Wike | Affirmative | N/A |
6 | Tennessee Valley Authority | Marjorie Parsons | Affirmative | N/A | |
5 | Austin Energy | Michael Dillard | Affirmative | N/A | |
1 | Puget Sound Energy, Inc. | Chelsey Neil | None | N/A | |
5 | San Miguel Electric Cooperative, Inc. | Lana Smith | Affirmative | N/A | |
4 | WEC Energy Group, Inc. | Matthew Beilfuss | Affirmative | N/A | |
5 | Platte River Power Authority | Tyson Archie | Affirmative | N/A | |
1 | Glencoe Light and Power Commission | Terry Volkmann | Negative | No Comment Submitted | |
1 | Network and Security Technologies | Nicholas Lauriat | Roger Fradenburgh | Negative | Comments Submitted |
1 | Public Utility District No. 1 of Pend Oreille County | Kevin Conway | Abstain | N/A | |
1 | Seattle City Light | Michael Jang | Abstain | N/A | |
1 | Eversource Energy | Quintin Lee | Affirmative | N/A | |
6 | Basin Electric Power Cooperative | Jerry Horner | Negative | Comments Submitted | |
1 | Minnkota Power Cooperative Inc. | Theresa Allard | Andy Fuhrman | Affirmative | N/A |
3 | Associated Electric Cooperative, Inc. | Todd Bennett | Affirmative | N/A | |
3 | Platte River Power Authority | Wade Kiess | Affirmative | N/A | |
6 | Associated Electric Cooperative, Inc. | Brian Ackermann | Affirmative | N/A | |
1 | Central Electric Power Cooperative (Missouri) | Michael Bax | None | N/A | |
3 | M and A Electric Power Cooperative | Stephen Pogue | Affirmative | N/A | |
1 | KAMO Electric Cooperative | Micah Breedlove | Affirmative | N/A | |
5 | Associated Electric Cooperative, Inc. | Brad Haralson | Affirmative | N/A | |
3 | Northeast Missouri Electric Power Cooperative | Skyler Wiegmann | Affirmative | N/A | |
3 | KAMO Electric Cooperative | Tony Gott | Affirmative | N/A | |
3 | Sho-Me Power Electric Cooperative | Jarrod Murdaugh | Affirmative | N/A | |
1 | Sho-Me Power Electric Cooperative | Peter Dawson | None | N/A | |
5 | Florida Municipal Power Agency | Chris Gowder | None | N/A | |
4 | Florida Municipal Power Agency | Dan O'Hagan | None | N/A | |
3 | Florida Municipal Power Agency | Carl Turner | None | N/A | |
6 | Florida Municipal Power Agency | Jade Bulitta | None | N/A | |
1 | Northeast Missouri Electric Power Cooperative | Kevin White | Affirmative | N/A | |
1 | N.W. Electric Power Cooperative, Inc. | Mark Ramsey | Affirmative | N/A | |
3 | NW Electric Power Cooperative, Inc. | John Stickley | Affirmative | N/A | |
1 | Hydro One Networks, Inc. | Payam Farahbakhsh | Mark Ciufo | Affirmative | N/A |
6 | Platte River Power Authority | Sabrina Martz | Affirmative | N/A | |
5 | Los Angeles Department of Water and Power | Glenn Barry | Abstain | N/A | |
1 | Tacoma Public Utilities (Tacoma, WA) | John Merrell | Jennie Wike | Affirmative | N/A |
5 | Brazos Electric Power Cooperative, Inc. | Shari Heino | Abstain | N/A | |
5 | Herb Schrayshuen | Herb Schrayshuen | Affirmative | N/A | |
3 | Lakeland Electric | Steve Marshall | None | N/A | |
3 | Georgia System Operations Corporation | Scott McGough | Affirmative | N/A | |
1 | Manitoba Hydro | Bruce Reimer | Negative | Comments Submitted | |
1 | Long Island Power Authority | Isidoro Behar | None | N/A | |
5 | Manitoba Hydro | Yuguang Xiao | Negative | Comments Submitted | |
3 | Manitoba Hydro | Mike Smith | None | N/A | |
3 | Los Angeles Department of Water and Power | Tony Skourtas | None | N/A | |
1 | Tri-State G and T Association, Inc. | Donna Wood | Affirmative | N/A | |
4 | FirstEnergy - FirstEnergy Corporation | Mark Garza | Affirmative | N/A | |
3 | Tri-State G and T Association, Inc. | Janelle Marriott Gill | Affirmative | N/A | |
5 | Talen Generation, LLC | Donald Lock | Affirmative | N/A | |
1 | Lakeland Electric | Larry Watt | None | N/A | |
5 | Lakeland Electric | George Kerst | None | N/A | |
6 | OGE Energy - Oklahoma Gas and Electric Co. | Sing Tay | Affirmative | N/A | |
3 | Eversource Energy | Christopher McKinnon | Affirmative | N/A | |
1 | Tallahassee Electric (City of Tallahassee, FL) | Scott Langston | Abstain | N/A | |
5 | Oglethorpe Power Corporation | Donna Johnson | Affirmative | N/A | |
1 | Los Angeles Department of Water and Power | faranak sarbaz | None | N/A | |
1 | Black Hills Corporation | Micah Runner | None | N/A | |
5 | Black Hills Corporation | Derek Silbaugh | Affirmative | N/A | |
1 | Seminole Electric Cooperative, Inc. | Bret Galbraith | Abstain | N/A | |
6 | NiSource - Northern Indiana Public Service Co. | Joe O'Brien | Negative | Comments Submitted | |
3 | NiSource - Northern Indiana Public Service Co. | Steven Taddeucci | Negative | Comments Submitted | |
6 | New York Power Authority | Erick Barrios | Affirmative | N/A | |
6 | Talen Energy Marketing, LLC | Jennifer Hohenshilt | None | N/A | |
1 | FirstEnergy - FirstEnergy Corporation | Julie Severino | Affirmative | N/A | |
1 | M and A Electric Power Cooperative | William Price | Affirmative | N/A | |
3 | Dominion - Dominion Resources, Inc. | Connie Schroeder | Negative | Comments Submitted | |
3 | Muscatine Power and Water | Seth Shoemaker | Abstain | N/A | |
6 | Muscatine Power and Water | Nick Burns | Abstain | N/A | |
3 | OGE Energy - Oklahoma Gas and Electric Co. | Donald Hargrove | Affirmative | N/A | |
3 | Westar Energy | Bryan Taggart | None | N/A | |
6 | Westar Energy | Grant Wilkerson | None | N/A | |
5 | Southern Company - Southern Company Generation | James Howell | Affirmative | N/A | |
6 | Manitoba Hydro | Blair Mukanik | Negative | Comments Submitted | |
5 | Tennessee Valley Authority | M Lee Thomas | Affirmative | N/A | |
3 | FirstEnergy - FirstEnergy Corporation | Aaron Ghodooshim | Affirmative | N/A | |
1 | OGE Energy - Oklahoma Gas and Electric Co. | Terri Pyle | Affirmative | N/A | |
3 | Black Hills Corporation | Don Stahl | Affirmative | N/A | |
6 | PSEG - PSEG Energy Resources and Trade LLC | Joseph Neglia | Affirmative | N/A | |
3 | Nebraska Public Power District | Tony Eddleman | Affirmative | N/A | |
5 | Northern California Power Agency | Jeremy Lawson | Negative | Comments Submitted | |
3 | CMS Energy - Consumers Energy Company | Karl Blaszkowski | Affirmative | N/A | |
5 | CMS Energy - Consumers Energy Company | David Greyerbiehl | Affirmative | N/A | |
4 | Georgia System Operations Corporation | Benjamin Winslett | Affirmative | N/A | |
1 | New York Power Authority | Salvatore Spagnolo | Affirmative | N/A | |
1 | OTP - Otter Tail Power Company | Charles Wicklund | None | N/A | |
5 | PSEG - PSEG Fossil LLC | Tim Kucey | Affirmative | N/A | |
5 | OTP - Otter Tail Power Company | Tammy Kubela | None | N/A | |
3 | OTP - Otter Tail Power Company | Wendi Olson | None | N/A | |
3 | Owensboro Municipal Utilities | Thomas Lyons | Abstain | N/A | |
4 | MGE Energy - Madison Gas and Electric Co. | Joseph DePoorter | Abstain | N/A | |
5 | Entergy - Entergy Services, Inc. | Gail Golden | Affirmative | N/A | |
6 | Portland General Electric Co. | Daniel Mason | Affirmative | N/A | |
1 | Muscatine Power and Water | Andy Kurriger | Abstain | N/A | |
3 | New York Power Authority | David Rivera | Affirmative | N/A | |
1 | BC Hydro and Power Authority | Adrian Andreoiu | Affirmative | N/A | |
1 | NiSource - Northern Indiana Public Service Co. | Steve Toosevich | Negative | Comments Submitted | |
5 | NiSource - Northern Indiana Public Service Co. | Kathryn Tackett | Negative | Comments Submitted | |
3 | BC Hydro and Power Authority | Hootan Jarollahi | Affirmative | N/A | |
6 | Los Angeles Department of Water and Power | Anton Vu | Abstain | N/A | |
1 | Omaha Public Power District | Doug Peterchuck | Negative | Comments Submitted | |
10 | SERC Reliability Corporation | Dave Krueger | Affirmative | N/A | |
1 | Platte River Power Authority | Matt Thompson | Affirmative | N/A | |
5 | JEA | John Babik | None | N/A | |
2 | Electric Reliability Council of Texas, Inc. | Brandon Gleason | Affirmative | N/A | |
6 | Seminole Electric Cooperative, Inc. | David Reinecke | Abstain | N/A | |
5 | Imperial Irrigation District | Tino Zaragoza | Denise Sanchez | Affirmative | N/A |
1 | Sunflower Electric Power Corporation | Paul Mehlhaff | Negative | No Comment Submitted | |
6 | Imperial Irrigation District | Diana Torres | Denise Sanchez | Affirmative | N/A |
1 | Public Utility District No. 1 of Chelan County | Ginette Lacasse | Affirmative | N/A | |
5 | Public Utility District No. 1 of Chelan County | Meaghan Connell | Affirmative | N/A | |
1 | Imperial Irrigation District | Jesus Sammy Alcaraz | Denise Sanchez | Affirmative | N/A |
3 | Public Utility District No. 1 of Chelan County | Joyce Gundry | Affirmative | N/A | |
5 | BC Hydro and Power Authority | Helen Hamilton Harding | Affirmative | N/A | |
1 | PNM Resources - Public Service Company of New Mexico | Lynn Goldstein | None | N/A | |
1 | NB Power Corporation | Nurul Abser | Affirmative | N/A | |
5 | Dairyland Power Cooperative | Tommy Drea | Abstain | N/A | |
1 | Berkshire Hathaway Energy - MidAmerican Energy Co. | Terry Harbour | Negative | Comments Submitted | |
5 | Hydro-Qu?bec Production | Carl Pineault | Affirmative | N/A | |
5 | Tacoma Public Utilities (Tacoma, WA) | Ozan Ferrin | Jennie Wike | Affirmative | N/A |
3 | Imperial Irrigation District | Glen Allegranza | Denise Sanchez | Affirmative | N/A |
5 | Portland General Electric Co. | Ryan Olson | Affirmative | N/A | |
3 | Portland General Electric Co. | Dan Zollner | Affirmative | N/A | |
5 | PPL - Louisville Gas and Electric Co. | JULIE HOSTRANDER | Affirmative | N/A | |
5 | Berkshire Hathaway - NV Energy | Kevin Salsbury | Negative | Comments Submitted | |
3 | Pacific Gas and Electric Company | Sandra Ellis | Michael Johnson | Affirmative | N/A |
1 | Pacific Gas and Electric Company | Marco Rios | Michael Johnson | Affirmative | N/A |
1 | Santee Cooper | Chris Wagner | Abstain | N/A | |
6 | Santee Cooper | Marty Watson | Abstain | N/A | |
3 | Santee Cooper | James Poston | Abstain | N/A | |
5 | Santee Cooper | Tommy Curtis | Abstain | N/A | |
5 | WEC Energy Group, Inc. | Clarice Zellmer | Affirmative | N/A | |
6 | Dominion - Dominion Resources, Inc. | Sean Bodkin | Negative | Comments Submitted | |
1 | PPL Electric Utilities Corporation | Michelle Longo | Affirmative | N/A | |
1 | Gainesville Regional Utilities | David Owens | None | N/A | |
5 | Lincoln Electric System | Kayleigh Wilkerson | Affirmative | N/A | |
4 | Tacoma Public Utilities (Tacoma, WA) | Hien Ho | Jennie Wike | Affirmative | N/A |
6 | Northern California Power Agency | Dennis Sismaet | Negative | Comments Submitted | |
1 | Portland General Electric Co. | Brooke Jockin | Affirmative | N/A | |
5 | Pacific Gas and Electric Company | Ed Hanson | Michael Johnson | Affirmative | N/A |
6 | Tacoma Public Utilities (Tacoma, WA) | Terry Gifford | Jennie Wike | Affirmative | N/A |
6 | Great River Energy | Donna Stephenson | None | N/A | |
1 | NextEra Energy - Florida Power and Light Co. | Mike ONeil | Affirmative | N/A | |
1 | Southern Company - Southern Company Services, Inc. | Matt Carden | Affirmative | N/A | |
5 | Choctaw Generation Limited Partnership, LLLP | Rob Watson | None | N/A | |
3 | Seminole Electric Cooperative, Inc. | Jeremy Lorigan | Abstain | N/A | |
5 | Dominion - Dominion Resources, Inc. | Rachel Snead | Negative | Comments Submitted | |
5 | Nebraska Public Power District | Ronald Bender | Affirmative | N/A | |
10 | Northeast Power Coordinating Council | Guy V. Zito | Affirmative | N/A | |
6 | Berkshire Hathaway - PacifiCorp | Lindsay Wickizer | Negative | Comments Submitted | |
6 | Powerex Corporation | Raj Hundal | None | N/A | |
1 | American Transmission Company, LLC | LaTroy Brumfield | Affirmative | N/A | |
4 | Alliant Energy Corporation Services, Inc. | Larry Heckert | Affirmative | N/A | |
5 | New York Power Authority | Zahid Qayyum | Affirmative | N/A | |
4 | Public Utility District No. 2 of Grant County, Washington | Karla Weaver | Affirmative | N/A | |
1 | Exelon | Daniel Gacek | Affirmative | N/A | |
3 | Exelon | Kinte Whitehead | Affirmative | N/A | |
5 | Exelon | Cynthia Lee | Affirmative | N/A | |
6 | Exelon | Becky Webb | Affirmative | N/A | |
1 | Entergy - Entergy Services, Inc. | Oliver Burke | Affirmative | N/A | |
3 | City Utilities of Springfield, Missouri | Duan Gavel | Affirmative | N/A | |
5 | Enel Green Power | Mat Bunch | Abstain | N/A | |
6 | Xcel Energy, Inc. | Carrie Dixon | Negative | Third-Party Comments | |
5 | Xcel Energy, Inc. | Gerry Huitt | Negative | Third-Party Comments | |
1 | Xcel Energy, Inc. | Dean Schiro | Negative | Third-Party Comments | |
4 | CMS Energy - Consumers Energy Company | Aric Root | Affirmative | N/A | |
1 | Memphis Light, Gas and Water Division | Allan Long | None | N/A | |
1 | Bonneville Power Administration | Kammy Rogers-Holliday | Affirmative | N/A | |
6 | Bonneville Power Administration | Andrew Meyers | Affirmative | N/A | |
3 | Bonneville Power Administration | Ken Lanehome | Affirmative | N/A | |
5 | Bonneville Power Administration | Scott Winner | Affirmative | N/A | |
5 | Great River Energy | Jacalynn Bentz | Negative | Comments Submitted | |
1 | Georgia Transmission Corporation | Greg Davis | Affirmative | N/A | |
3 | Snohomish County PUD No. 1 | Holly Chaney | Affirmative | N/A | |
4 | Public Utility District No. 1 of Snohomish County | John Martinsen | Affirmative | N/A | |
5 | Public Utility District No. 1 of Snohomish County | Sam Nietfeld | Affirmative | N/A | |
6 | Snohomish County PUD No. 1 | John Liang | Affirmative | N/A | |
1 | Public Utility District No. 1 of Snohomish County | Alyssia Rhoads | Affirmative | N/A | |
5 | AEP | Thomas Foltz | Negative | Comments Submitted | |
1 | AEP - AEP Service Corporation | Dennis Sauriol | Negative | Comments Submitted | |
1 | Oncor Electric Delivery | Lee Maurer | Byron Booker | None | N/A |
6 | AEP | JT Kuehne | Negative | Comments Submitted | |
10 | ReliabilityFirst | Anthony Jablonski | Affirmative | N/A | |
3 | Austin Energy | W. Dwayne Preston | Affirmative | N/A | |
5 | Cogentrix Energy Power Management, LLC | Gerry Adamski | Affirmative | N/A | |
5 | Seminole Electric Cooperative, Inc. | Trena Haynes | Affirmative | N/A | |
5 | Cowlitz County PUD | Deanna Carlson | Abstain | N/A | |
8 | Florida Reliability Coordinating Council – Member Services Division | Vince Ordax | Abstain | N/A | |
3 | AEP | Kent Feliks | Negative | Comments Submitted | |
6 | Lakeland Electric | Paul Shipps | Affirmative | N/A | |
10 | Texas Reliability Entity, Inc. | Rachel Coyne | Negative | Comments Submitted | |
6 | Duke Energy | Greg Cecil | Negative | Comments Submitted | |
5 | Duke Energy | Dale Goodwine | Negative | Comments Submitted | |
3 | Duke Energy | Lee Schuster | Negative | Comments Submitted | |
4 | National Rural Electric Cooperative Association | Paul McCurley | None | N/A | |
4 | Arkansas Electric Cooperative Corporation | Alice Wright | None | N/A | |
1 | Arkansas Electric Cooperative Corporation | Jennifer Loiacano | None | N/A | |
6 | Arkansas Electric Cooperative Corporation | Bruce Walkup | None | N/A | |
3 | Arkansas Electric Cooperative Corporation | Ayslynn McAvoy | None | N/A | |
5 | Arkansas Electric Cooperative Corporation | Adrian Harris | None | N/A | |
1 | East Kentucky Power Cooperative | Amber Skillern | Negative | Third-Party Comments | |
3 | East Kentucky Power Cooperative | Patrick Woods | Negative | Third-Party Comments | |
1 | Duke Energy | Laura Lee | Negative | Comments Submitted | |
1 | Arizona Electric Power Cooperative, Inc. | Jennifer Bray | Affirmative | N/A | |
5 | East Kentucky Power Cooperative | David Meade | Negative | Third-Party Comments | |
3 | Wabash Valley Power Association | Susan Sosbe | None | N/A | |
5 | SunPower | Bradley Collard | None | N/A | |
6 | Evergy | Thomas ROBBEN | Affirmative | N/A | |
1 | Evergy | Allen Klassen | Affirmative | N/A | |
3 | Evergy | Marcus Moor | Affirmative | N/A | |
5 | Evergy | Derek Brown | Affirmative | N/A | |
5 | FirstEnergy - FirstEnergy Corporation | Robert Loy | Affirmative | N/A | |
6 | FirstEnergy - FirstEnergy Corporation | Ann Carey | Affirmative | N/A |