Ballot Name: Project 2023-06 CIP-014 Risk Assessment Refinement CIP-014-4 AB 3 ST
Voting Start Date: 7/11/2025 12:01:00 AM
Voting End Date: 7/21/2025 8:00:00 PM
Ballot Type: ST
Ballot Activity: AB
Ballot Series: 3
Total # Votes: 243
Total Ballot Pool: 293
Quorum: 82.94
Quorum Established Date: 7/21/2025 3:28:20 PM
Weighted Segment Value: 57.27

Segment Ballot Pool Segment Weight Affirmative Votes Affirmative Fraction Negative Votes w/ Comment Negative Fraction w/ Comment Negative Votes w/o Comment Abstain No Vote
Segment: 1 85 1 28 0.467 32 0.533 0 11 14
Segment: 2 7 0.2 2 0.2 0 0 0 4 1
Segment: 3 67 1 27 0.563 21 0.438 0 8 11
Segment: 4 15 0.8 6 0.6 2 0.2 0 5 2
Segment: 5 66 1 18 0.45 22 0.55 0 10 16
Segment: 6 46 1 16 0.471 18 0.529 0 6 6
Segment: 7 0 0 0 0 0 0 0 0 0
Segment: 8 0 0 0 0 0 0 0 0 0
Segment: 9 0 0 0 0 0 0 0 0 0
Segment: 10 7 0.5 4 0.4 1 0.1 0 2 0
Totals: 293 5.5 101 3.15 96 2.35 0 46 50
Segment Organization Voter Designated Proxy Ballot NERC Memo
6 Salt River Project Israel Perez Timothy Singh Negative Comments Submitted
1 Georgia Transmission Corporation Greg Davis Stephen Stafford Negative Comments Submitted
10 ReliabilityFirst Tremayne Brown Greg Sorenson Negative Comments Submitted
5 Dairyland Power Cooperative Tommy Drea Abstain N/A
4 Georgia System Operations Corporation Katrina Lyons Negative Third-Party Comments
3 Con Ed - Consolidated Edison Co. of New York Lincoln Burton Negative Comments Submitted
6 Southern Indiana Gas and Electric Co. Kati Barr Abstain N/A
1 National Grid USA Jacqueline Ryan Abstain N/A
5 National Grid USA Robin Berry Abstain N/A
3 National Grid USA Brian Shanahan Abstain N/A
5 Lower Colorado River Authority Joseph Scott Negative Comments Submitted
1 Allete - Minnesota Power, Inc. Hillary Creurer Negative Comments Submitted
3 Bonneville Power Administration Ron Sporseen Negative Comments Submitted
10 Midwest Reliability Organization Mark Flanary Affirmative N/A
5 Berkshire Hathaway - NV Energy Dwanique Spiller None N/A
2 Electric Reliability Council of Texas, Inc. Kennedy Meier Abstain N/A
5 Imperial Irrigation District Tino Zaragoza Denise Sanchez Affirmative N/A
5 Southern Indiana Gas and Electric Co. Larry Rogers Abstain N/A
3 Southern Indiana Gas and Electric Co. Ryan Snyder Abstain N/A
5 Sempra - San Diego Gas and Electric Jennifer Wright Negative Third-Party Comments
1 City Utilities of Springfield, Missouri Michael Bowman None N/A
4 City Utilities of Springfield, Missouri Jerry Bradshaw Affirmative N/A
4 FirstEnergy - FirstEnergy Corporation Mark Garza Negative Comments Submitted
1 Tacoma Public Utilities (Tacoma, WA) John Merrell Jennie Wike Affirmative N/A
5 Con Ed - Consolidated Edison Co. of New York Michelle Pagano Negative Comments Submitted
1 FirstEnergy - FirstEnergy Corporation Theresa Ciancio Negative Comments Submitted
6 Portland General Electric Co. Stefanie Burke Abstain N/A
3 OGE Energy - Oklahoma Gas and Electric Co. Donald Hargrove Affirmative N/A
6 Con Ed - Consolidated Edison Co. of New York Jason Chandler Negative Comments Submitted
6 FirstEnergy - FirstEnergy Corporation Stacey Sheehan Negative Comments Submitted
5 OGE Energy - Oklahoma Gas and Electric Co. Patrick Wells Affirmative N/A
1 OGE Energy - Oklahoma Gas and Electric Co. Terri Pyle Affirmative N/A
6 OGE Energy - Oklahoma Gas and Electric Co. Ashley F Stringer Affirmative N/A
1 Lower Colorado River Authority Matt Lewis None N/A
1 International Transmission Company Holdings Corporation Michael Moltane Gail Elliott Negative Comments Submitted
6 Platte River Power Authority Sabrina Martz Affirmative N/A
1 NextEra Energy - Florida Power and Light Co. Silvia Mitchell Negative Comments Submitted
3 Arkansas Electric Cooperative Corporation Ayslynn Mcavoy Abstain N/A
1 Public Utility District No. 2 of Grant County, Washington Joanne Anderson Abstain N/A
6 Arkansas Electric Cooperative Corporation Bruce Walkup Abstain N/A
1 Network and Security Technologies Nick Lauriat Abstain N/A
1 Arkansas Electric Cooperative Corporation Lily Green None N/A
1 Dairyland Power Cooperative Karrie Schuldt Abstain N/A
5 Oklahoma Municipal Power Authority Patrick Tuttle Abstain N/A
3 Sempra - San Diego Gas and Electric Bryan Bennett Negative Third-Party Comments
1 Evergy Kevin Frick Alan Kloster Negative Comments Submitted
1 Con Ed - Consolidated Edison Co. of New York Dermot Smyth Negative Comments Submitted
5 NextEra Energy Richard Vendetti Negative Comments Submitted
3 Edison International - Southern California Edison Company Romel Aquino None N/A
6 Imperial Irrigation District Diana Torres Denise Sanchez Affirmative N/A
6 Black Hills Corporation Josh Schumacher Negative Comments Submitted
3 NextEra Energy - Florida Power and Light Co. Karen Demos Negative Comments Submitted
3 Ameren - Ameren Services David Jendras Sr Nick Leathers Affirmative N/A
1 Portland General Electric Co. Brooke Jockin Abstain N/A
1 Nebraska Public Power District Jamison Cawley Negative Comments Submitted
5 Southern Company - Southern Company Generation Leslie Burke None N/A
6 Southern Company - Southern Company Generation and Energy Marketing Matthew O'neal None N/A
6 Ameren - Ameren Services Robert Quinlivan Affirmative N/A
3 Avista - Avista Corporation Robert Follini Affirmative N/A
3 Southern Company - Alabama Power Company Joel Dembowski None N/A
1 Southern Company - Southern Company Services, Inc. Matt Carden None N/A
5 Ameren - Ameren Missouri Sam Dwyer Affirmative N/A
5 APS - Arizona Public Service Co. Andrew Smith Negative Comments Submitted
1 Ameren - Ameren Services Tamara Evey Affirmative N/A
6 APS - Arizona Public Service Co. Marcus Bortman Brandon Smith Negative Comments Submitted
1 APS - Arizona Public Service Co. Daniela Atanasovski Negative Comments Submitted
3 Evergy Marcus Moor Alan Kloster Negative Comments Submitted
3 APS - Arizona Public Service Co. Jessica Lopez Negative Comments Submitted
2 Midcontinent ISO, Inc. Kirsten Rowley Abstain N/A
3 FirstEnergy - FirstEnergy Corporation Aaron Ghodooshim Negative Comments Submitted
3 Berkshire Hathaway Energy - MidAmerican Energy Co. Amy Key Affirmative N/A
3 Imperial Irrigation District George Kirschner Denise Sanchez Affirmative N/A
1 PPL Electric Utilities Corporation Michelle McCartney Longo Negative Third-Party Comments
6 Berkshire Hathaway - PacifiCorp Lindsay Wickizer Affirmative N/A
5 Oglethorpe Power Corporation Donna Johnson Abstain N/A
1 Berkshire Hathaway Energy - MidAmerican Energy Co. Thomas Breen Affirmative N/A
6 NextEra Energy - Florida Power and Light Co. Justin Welty Negative Comments Submitted
3 NiSource - Northern Indiana Public Service Co. Steven Taddeucci Affirmative N/A
3 Salt River Project Mathew Weber Timothy Singh Negative Comments Submitted
4 Alliant Energy Corporation Services, Inc. Angela Dockter Lexi Dobrzysnki Abstain N/A
5 Platte River Power Authority Jon Osell None N/A
1 Platte River Power Authority Marissa Archie Affirmative N/A
5 Black Hills Corporation Sheila Suurmeier Negative Comments Submitted
3 Snohomish County PUD No. 1 Holly Chaney Affirmative N/A
6 New York Power Authority Shelly Dineen Negative Comments Submitted
1 PSEG - Public Service Electric and Gas Co. Karen Arnold None N/A
1 CenterPoint Energy Houston Electric, LLC Daniela Hammons Negative Comments Submitted
6 Western Area Power Administration Jennifer Neville Negative Comments Submitted
3 Exelon Kinte Whitehead Affirmative N/A
1 Exelon Daniel Gacek Affirmative N/A
2 Southwest Power Pool, Inc. (RTO) Joshua Phillips Abstain N/A
10 Western Electricity Coordinating Council Steven Rueckert Affirmative N/A
3 Los Angeles Department of Water and Power Fausto Serratos Affirmative N/A
6 Los Angeles Department of Water and Power Anton Vu Affirmative N/A
1 Los Angeles Department of Water and Power Jonathon Flores Affirmative N/A
3 Puget Sound Energy, Inc. Kelley Sargent Negative Comments Submitted
5 Los Angeles Department of Water and Power Robert Kerrigan Affirmative N/A
3 Black Hills Corporation Josh Combs Negative Comments Submitted
5 Evergy Jeremy Harris Alan Kloster Negative Comments Submitted
10 SERC Reliability Corporation Dave Krueger Abstain N/A
1 Hydro-Quebec (HQ) Nicolas Turcotte Chantal Mazza Negative Comments Submitted
1 Western Area Power Administration Ben Hammer Negative Comments Submitted
1 Bonneville Power Administration Kamala Rogers-Holliday Negative Comments Submitted
3 Entergy James Keele Affirmative N/A
1 Sempra - San Diego Gas and Electric Mo Derbas Negative Third-Party Comments
6 Entergy Julie Hall None N/A
6 Dominion - Dominion Resources, Inc. Bill Garvey Negative Comments Submitted
1 Dominion - Dominion Virginia Power Steven Belle Negative Comments Submitted
5 Dominion - Dominion Resources, Inc. Barbara Marion Negative Comments Submitted
1 Entergy Brian Lindsey Affirmative N/A
6 Evergy Tiffany Lake Alan Kloster Negative Comments Submitted
5 Associated Electric Cooperative, Inc. Chuck Booth Affirmative N/A
5 Portland General Electric Co. Ryan Olson Abstain N/A
3 Portland General Electric Co. Mayra Franco Abstain N/A
5 Entergy - Entergy Services, Inc. Gail Golden Affirmative N/A
3 Omaha Public Power District David Heins Affirmative N/A
1 Central Iowa Power Cooperative Kevin Lyons None N/A
1 Xcel Energy, Inc. Eric Barry Negative Third-Party Comments
3 MGE Energy - Madison Gas and Electric Co. Benjamin Widder Abstain N/A
5 Hydro-Quebec (HQ) Junji Yamaguchi Chantal Mazza Negative Comments Submitted
6 Xcel Energy, Inc. Patrick Flaherty Negative Third-Party Comments
1 Black Hills Corporation Trevor Rombough Negative Comments Submitted
3 Muscatine Power and Water Seth Shoemaker Abstain N/A
3 Great River Energy Michael Brytowski Affirmative N/A
6 Muscatine Power and Water Nicholas Burns Abstain N/A
1 BC Hydro and Power Authority Patricia Robertson Abstain N/A
5 Xcel Energy, Inc. Gerry Huitt Negative Third-Party Comments
2 ISO New England, Inc. John Pearson Affirmative N/A
3 Eversource Energy Vicki O'Leary Affirmative N/A
3 City Utilities of Springfield, Missouri Jessica Morrissey Abstain N/A
6 Public Utility District No. 1 of Chelan County Tamarra Hardie Negative Comments Submitted
1 Unisource - Tucson Electric Power Co. Jessica Cordero Negative Comments Submitted
3 BC Hydro and Power Authority Ming Jiang Abstain N/A
2 PJM Interconnection, L.L.C. Thomas Foster Elizabeth Davis Abstain N/A
5 New York Power Authority Zahid Qayyum Negative Comments Submitted
1 Long Island Power Authority Isidoro Behar Negative Comments Submitted
1 Muscatine Power and Water Andrew Kurriger Abstain N/A
4 Northern California Power Agency Marty Hostler None N/A
5 Cowlitz County PUD Deanna Carlson None N/A
1 IDACORP - Idaho Power Company Sean Steffensen Affirmative N/A
5 Colorado Springs Utilities Jeffrey Icke Affirmative N/A
3 Dominion - Dominion Virginia Power Victoria Crider Negative Comments Submitted
1 Public Utility District No. 1 of Chelan County Robert Witham Negative Comments Submitted
1 Imperial Irrigation District Jesus Sammy Alcaraz Denise Sanchez Affirmative N/A
5 Northern California Power Agency Jeremy Lawson Chris Carnesi None N/A
5 Public Utility District No. 1 of Chelan County Rebecca Wickel Negative Comments Submitted
5 Lincoln Electric System Brittany Millard Affirmative N/A
3 Northern California Power Agency Michael Whitney Chris Carnesi None N/A
3 Public Utility District No. 1 of Chelan County Joyce Gundry Negative Comments Submitted
1 Lincoln Electric System Josh Johnson Affirmative N/A
3 Lincoln Electric System Sam Christensen Affirmative N/A
2 California ISO Darcy O'Connell Affirmative N/A
6 Lincoln Electric System Eric Ruskamp Affirmative N/A
6 Northern California Power Agency Dennis Sismaet Chris Carnesi None N/A
1 Glencoe Light and Power Commission Terry Volkmann Negative Third-Party Comments
6 PPL - Louisville Gas and Electric Co. Linn Oelker Negative Third-Party Comments
1 SaskPower Wayne Guttormson Abstain N/A
1 Tallahassee Electric (City of Tallahassee, FL) Scott Langston None N/A
5 PPL - Louisville Gas and Electric Co. Julie Hostrander None N/A
1 Duke Energy Katherine Street Affirmative N/A
5 BC Hydro and Power Authority Vijay Raghunathan Abstain N/A
3 PPL - Louisville Gas and Electric Co. James Frank Negative Third-Party Comments
5 Duke Energy Dale Goodwine Affirmative N/A
6 Snohomish County PUD No. 1 John Liang Affirmative N/A
5 Sacramento Municipal Utility District Ryder Couch Tim Kelley Affirmative N/A
6 Sacramento Municipal Utility District Charles Norton Tim Kelley Affirmative N/A
5 Buckeye Power, Inc. Kevin Zemanek Ryan Strom Affirmative N/A
3 Duke Energy - Florida Power Corporation Marcelo Pesantez None N/A
4 Sacramento Municipal Utility District Foung Mua Tim Kelley Affirmative N/A
1 Oncor Electric Delivery Byron Booker Lucinda Bradshaw None N/A
1 Public Utility District No. 1 of Snohomish County Alyssia Rhoads Affirmative N/A
5 Constellation Alison MacKellar Abstain N/A
1 VELCO -Vermont Electric Power Company, Inc. Randall Buswell Abstain N/A
4 Western Power Pool Kevin Conway Abstain N/A
6 Constellation Kimberly Turco Abstain N/A
3 Seminole Electric Cooperative, Inc. Usama Tahir Negative Comments Submitted
3 Platte River Power Authority Richard Kiess Affirmative N/A
1 Seminole Electric Cooperative, Inc. Khang Le Negative Comments Submitted
1 Balancing Authority of Northern California Kevin Smith Tim Kelley Affirmative N/A
1 New York Power Authority Daniel Valle Affirmative N/A
3 Nebraska Public Power District Tony Eddleman Negative Comments Submitted
1 Santee Cooper Chris Wagner Negative Comments Submitted
5 Electric Power Supply Association Bill Zuretti None N/A
5 Santee Cooper Carey Salisbury Negative Comments Submitted
6 Santee Cooper Marty Watson Negative Comments Submitted
3 Santee Cooper Vicky Budreau Negative Comments Submitted
1 Tri-State G and T Association, Inc. Donna Wood Affirmative N/A
3 Tri-State G and T Association, Inc. Amanda Skubal Affirmative N/A
1 Seattle City Light Michael Jang Affirmative N/A
10 Texas Reliability Entity, Inc. Rachel Coyne Affirmative N/A
1 Eversource Energy Joshua London Affirmative N/A
6 Duke Energy John Sturgeon Affirmative N/A
4 Buckeye Power, Inc. Jason Procuniar Ryan Strom Affirmative N/A
1 Hydro One Networks, Inc. Emma Halilovic Negative Comments Submitted
3 AEP Jodi Yeary Negative Comments Submitted
1 Sunflower Electric Power Corporation Paul Mehlhaff Abstain N/A
2 New York Independent System Operator Gregory Campoli None N/A
5 Tri-State G and T Association, Inc. Sergio Banuelos Affirmative N/A
3 Seattle City Light Zenon O'young-Chu Affirmative N/A
5 Greybeard Compliance Services, LLC Mike Gabriel None N/A
6 Bonneville Power Administration Tanner Brier Negative Comments Submitted
5 Great River Energy Jacalynn Bentz Affirmative N/A
6 Powerex Corporation Raj Hundal Abstain N/A
5 DTE Energy George Goddard None N/A
5 Seminole Electric Cooperative, Inc. Melanie Wong Negative Comments Submitted
6 Edison International - Southern California Edison Company Stephanie Kenny Negative Comments Submitted
5 Edison International - Southern California Edison Company Selene Willis Negative Comments Submitted
5 NRG - NRG Energy, Inc. Michael Scalise None N/A
1 NB Power Corporation Jeffrey Streifling Negative Comments Submitted
6 Seattle City Light Daren Brubaker Affirmative N/A
1 Tennessee Valley Authority David Plumb Negative Comments Submitted
3 Tennessee Valley Authority Ian Grant None N/A
5 Tennessee Valley Authority Darren Boehm Negative Comments Submitted
5 Nebraska Public Power District Ronald Bender Negative Third-Party Comments
3 Associated Electric Cooperative, Inc. Todd Bennett Affirmative N/A
3 NW Electric Power Cooperative, Inc. Heath Henry Affirmative N/A
1 Northeast Missouri Electric Power Cooperative Brett Douglas Affirmative N/A
3 M and A Electric Power Cooperative Gary Dollins Affirmative N/A
6 Associated Electric Cooperative, Inc. Brian Ackermann Affirmative N/A
5 Public Utility District No. 1 of Snohomish County Becky Burden Affirmative N/A
3 PSEG - Public Service Electric and Gas Co. Christopher Murphy None N/A
4 Utility Services, Inc. Carver Powers Affirmative N/A
5 PSEG Nuclear LLC Sharon Brown Abstain N/A
1 Sho-Me Power Electric Cooperative Oskar Olson None N/A
1 N.W. Electric Power Cooperative, Inc. Mark Ramsey Affirmative N/A
3 Georgia System Operations Corporation Scott McGough None N/A
3 KAMO Electric Cooperative Tony Gott Affirmative N/A
1 Associated Electric Cooperative, Inc. Mark Riley Affirmative N/A
1 NiSource - Northern Indiana Public Service Co. Alison Nickells Affirmative N/A
5 Salt River Project Matthew Jaramilla Timothy Singh Negative Comments Submitted
5 Seattle City Light Chris Shultz None N/A
6 PSEG - PSEG Energy Resources and Trade LLC Laura Wu None N/A
3 Sho-Me Power Electric Cooperative Jarrod Murdaugh Affirmative N/A
4 Public Utility District No. 1 of Snohomish County John D. Martinsen Affirmative N/A
4 Public Utility District No. 2 of Grant County, Washington Karla Weaver Abstain N/A
3 Northeast Missouri Electric Power Cooperative Skyler Wiegmann None N/A
5 NiSource - Northern Indiana Public Service Co. Kathryn Tackett Affirmative N/A
1 Edison International - Southern California Edison Company Robert Blackney Negative Comments Submitted
1 Pedernales Electric Cooperative, Inc. Bradley Collard None N/A
5 AEP Thomas Foltz Negative Comments Submitted
6 AEP Randy Calhoun None N/A
1 AEP - AEP Service Corporation Dennis Sauriol None N/A
6 NiSource - Northern Indiana Public Service Co. Eugene Johnson Affirmative N/A
1 Manitoba Hydro Nazra Gladu Negative Comments Submitted
3 Colorado Springs Utilities Hillary Dobson Affirmative N/A
3 Xcel Energy, Inc. Nicholas Friebel Joseph Gatten Negative Third-Party Comments
3 MEAG Power Roger Brand Rebika Yitna Negative Comments Submitted
5 Austin Energy Michael Dillard Affirmative N/A
6 Austin Energy Imane Mrini Affirmative N/A
1 Austin Energy Thomas Standifur Affirmative N/A
3 Austin Energy Lovita Griffin None N/A
1 M and A Electric Power Cooperative William Price Affirmative N/A
1 OTP - Otter Tail Power Company Charles Wicklund None N/A
5 OTP - Otter Tail Power Company Stacy Wahlund None N/A
4 Seattle City Light Robert Jones Affirmative N/A
10 Northeast Power Coordinating Council Ruida Shu Abstain N/A
3 Buckeye Power, Inc. Tom Schmidt Ryan Strom Affirmative N/A
1 Salt River Project Laura Somak Timothy Singh Negative Comments Submitted
5 Talen Generation, LLC Donald Lock None N/A
3 OTP - Otter Tail Power Company Tony Huseby None N/A
5 U.S. Bureau of Reclamation Wendy Kalidass Affirmative N/A
1 U.S. Bureau of Reclamation Richard Jackson Phillip Martinez Affirmative N/A
6 Seminole Electric Cooperative, Inc. Bret Galbraith Negative Comments Submitted
3 Central Electric Power Cooperative (Missouri) Adam Weber Affirmative N/A
5 FirstEnergy - FirstEnergy Corporation Matthew Augustin Negative Comments Submitted
3 New York Power Authority Richard Machado Negative Comments Submitted
6 Cleco Corporation Robert Hirchak Clay Walker None N/A
1 Colorado Springs Utilities Corey Walker Affirmative N/A
3 Sacramento Municipal Utility District Nicole Looney Tim Kelley Affirmative N/A
6 Tennessee Valley Authority Jeffrey Powell Negative Comments Submitted
1 American Transmission Company, LLC Amy Wilke Affirmative N/A
5 CMS Energy - Consumers Energy Company David Greyerbiehl Abstain N/A
4 Arkansas Electric Cooperative Corporation Jenni Sudduth Abstain N/A
5 Pacific Gas and Electric Company Tyler Brun Bob Cardle Negative Comments Submitted
6 Omaha Public Power District Shonda McCain Affirmative N/A
1 Lakeland Electric Larry Watt None N/A
5 Omaha Public Power District Kayleigh Wilkerson Affirmative N/A
1 Southwestern Power Administration Angela Wheat Abstain N/A
4 WEC Energy Group, Inc. Candace Morakinyo Abstain N/A
10 New York State Reliability Council Wesley Yeomans Affirmative N/A
5 Avista - Avista Corporation Glen Farmer None N/A
6 Great River Energy Brian Meloy Affirmative N/A
3 Pacific Gas and Electric Company Sandra Ellis Bob Cardle Negative Comments Submitted
1 Sacramento Municipal Utility District Wei Shao Tim Kelley Affirmative N/A
1 Pacific Gas and Electric Company Marco Rios Bob Cardle Negative Comments Submitted
5 NB Power Corporation - New Brunswick Power Transmission Corporation David Melanson Negative Comments Submitted
4 Oklahoma Municipal Power Authority Michael Watt None N/A
1 Minnkota Power Cooperative Inc. Theresa Allard Nikki Carson-Marquis Negative Comments Submitted
3 Orlando Utilities Commission Ballard Mutters None N/A
5 JEA John Babik None N/A
1 Great River Energy Gordon Pietsch None N/A
5 California Department of Water Resources ASM Mostafa None N/A
3 TXNM Energy Scott Thompson Affirmative N/A