2016-03 Cyber Security Supply Chain Risk Management | CIP-013-1

Description:

Start Date: 01/19/2017
End Date: 03/06/2017

Associated Ballots:

Ballot Name Project Standard Pool Open Pool Close Voting Start Voting End
2016-03 Cyber Security Supply Chain Risk Management CIP-013-1 IN 1 ST 2016-03 Cyber Security Supply Chain Risk Management CIP-013-1 01/19/2017 02/17/2017 02/24/2017 03/06/2017
2016-03 Cyber Security Supply Chain Risk Management CIP-013-1 Non-binding Poll IN 1 NB 2016-03 Cyber Security Supply Chain Risk Management CIP-013-1 Non-binding Poll 01/19/2017 02/17/2017 02/24/2017 03/06/2017

Filter:

Hot Answers

- 0 - 0

Southern Company strongly encourages the SDT to consider the below edits, which use phrasing directly from the FERC Order.  If R1 is intended to address the true supply chain procurement side of things, then the proposed edits provided below appropriately scope this requirement at the ‘main R’ level.  The Order 829 Summary, and paragraphs 10 and 24 of the Order specify controls for vendors that supply “industrial control systems” products and services.  Therefore, R1 should be focused on to what vendors and what software/firmware this requirement should be limited.  The expansion of scope at this stage to propose including all impact classifications of BES Cyber Systems and their associated EACMS, PACS, and PCAs is above and beyond the Order, in our opinion.  It’s absolutely unmanageable if not restricted somehow to higher level systems.  In CIP audits, “BES Cyber Systems” immediately turn into a list of hundreds or thousands of "programmable electronic devices." 

 

The proposed edits provided below move the “planning and procurement” phases of the lifecycle up from sub-requirements 1.1 and 1.1.1 to the main requirement so that all of the sub-requirements under R1 are appropriately scoped as well.  Without this, for example, R1.2 applies to all risks at all times throughout the entire lifecycle of all devices.  It’s cleaner to have the ‘main R’ be about the plan and setting the scope of the plan, and then have the sub-requirements address the plan(s) specifics.  Consistent with Order 829, language from the rationale section addressing the “forward-looking” nature of this new requirement(s) has been incorporated into the main R1 requirement itself.  Modifications highlighted below in R1.2.5 are recommended to eliminate redundancy and avoid confusion, while also addressing the specifics in the Order for dealing with “cyber incidents.”  The order of the sub-requirements of R1.2 have also been adjusted to more clearly align with the planning and procurement life-cycle, while at the same time continuing to address directives in the Order.

 

Additionally, Southern Company agrees with comments submitted by Georgia Transmission Corporation (GTC), specifically with regard to defining the term “Supply Chain” in accordance with the Order-referenced NIST 800-53 defined term which establishes the applicable time horizon for this Standard, and removal of references to Electronic Access Control and Monitoring Systems, Physical Access Control Systems, and Protected Cyber Assets.

 

Modify the R1 language as follows:

 

R1. Each Responsible Entity shall implement one or more documented supply chain risk management plan(s) that address controls for mitigating planning and procurement cyber security risks for industrial control system vendor products and services used in BES Cyber Systems.  Implementation of the cyber security risk management plan(s) does not require the Responsible Entity to renegotiate or abrogate existing contracts.  The plan(s) shall address:  [Violation Risk Factor: Medium] [Time Horizon: Operations Planning]

1.1 Process(es) for the identification and assessment of risk(s) of industrial control system vendor products and services.

1.2 Methods to evaluate controls to address identified risk(s) in R1.1, that includes the following:

1.2.1  Coordination of remote access controls for (i) vendor-initiated Interactive Remote Access and (ii) system-to-system remote access with a vendor(s);

1.2.2  Process(es) for notification when vendor employee remote or onsite access should no longer be granted;

1.2.3  Process(es) for verifying software integrity and authenticity of all software and patches that are intended for use;

1.2.4  Process(es) for disclosure of known vulnerabilities in vendor products;

1.2.5  Process(es) for notification of and coordination of response to vendor-related cyber security incidents; and

1.2.6  Other process(es) to address risk(s) as determined in Part 1.1, if applicable.

Southern Company, Segment(s) 1, 3, 5, 6, 8/3/2016

- 0 - 0

Other Answers

Dennis Minton, 1/19/2017

- 0 - 0

Dennis Minton, 1/19/2017

- 0 - 0

Dennis Minton, 1/19/2017

- 0 - 0

Dennis Minton, 1/19/2017

- 0 - 0

Tom Anthony, On Behalf of: Tom Anthony, , Segments 1, 3

- 0 - 0

Tom Anthony, On Behalf of: Tom Anthony, , Segments 1, 3

- 0 - 0

Glen Farmer, Avista - Avista Corporation, 5, 2/6/2017

- 0 - 0

Russel Mountjoy, 2/24/2017

- 0 - 1

As stated in FERC Order 829, section 59, “The new or modified Reliability Standard must address the provision and verification of relevant security concepts in future contracts for industrial control system hardware, software, and computing and networking services associated with bulk electric system operations”.   R1 does not align with the above FERC directive.  FERC clearly insisted that future contracts will address the five attributes of section 59. 

 

If Future is added, the NSRF request that “Future” needs to be better defined.  If a company has a contract that is multi-year and each year a new Purchase Order is issued, the contract is not new or revised.  There needs to be direction given on how to implement the requirements of the standard going forward.

 

If Future is not added, then the NSRF request a possible foot note stating… that R1 applies to all contracts (agreements) starting on the date of enforcement of CIP-013-1.  As FERC has stated in FERC Order 693, section 253, Entities need to satisfy the Requirements in order to be compliant.

 

The SDT should update R1 to clearly state this, such as;

 

“R1.  Each Responsible Entity shall implement one or more documented supply chain risk management plan(s) that address controls for mitigating cyber security risks to future contracts concerning the procurement of BES Cyber Systems and, if applicable, associated Electronic Access Control or Monitoring Systems, Physical Access Control Systems, and Protected Cyber Assets. The plan(s) shall address: “

 

This proposed update aligns with FEERC Order 829, section 59 and clearly informs the applicable entity in what is required in future endeavors.  R1 will fulfill the FERC directive of having supply chain risk management plans for future procurement, which falls in line with the SDT’s “Notional BES Cyber System Life cycle” model.  The NSRF does not agree with the “if applicable” wording and the addition of :” associated Electronic Access Control or Monitoring Systems, Physical Access Control Systems, and Protected Cyber Assets”, as this is not within the FERC Order.

 

R1.1 and its parts seem to be disjointed.  The NSRF understands to have a Plan (R1) to mitigate cyber security risks to the future procurement of BES Cyber Systems, etc.  Within the Plan, entities are to use controls in their BES Cyber System planning and development “phase” (which is taken as the Entity’s internal processes of wants and needs).  To have controls during the “planning and development” phase will not have an impact on the procurement of a BES Cyber System, etc., since nothing is occurring; this is a planning phase, only.  Entities are only discussing their wants and needs.  This is similar to the caveat within the NERC Defined term of Operating Instruction; (A discussion of general information and of potential options or alternatives to resolve Bulk Electric System operating concerns is not a command and is not considered an Operating Instruction.)  R1.1 has two parts that should address what is required to occur within the plan concerning the objective of R1.1. 

 

Recommend R1.1 to read “The use of controls for BES Cyber Systems to:”

 

R1.1.1 Identify and assess risk(s) during the procurement and deployment of vendor products and services; and” (unchanged for the proposed draft).  This updated wording of R1.1, directs the use of controls within the plan of R1 and R1.1 states use controls to accomplish the attributes of R1.1.1.

 

 

Then R1.1.2, states the Entity is to “…evaluate methods to address identified risk(s)”.  As written, the Entity is to review (address?) their methods to mitigate identified risk(s).   Without saying, does this part need to be within the proposed Standard?  The intent is to mitigate any known risks, not evaluate methods to identify risk(s).  This could be viewed as an entity’s method of industry trends to see what new “processes” there are to “evaluate methods to address identified risk(s).  Or is this required in order to keep the “how and what” an entity does up to date and current with known “identify and assess” practices.  If so, please clarify.

 

It may be less ambiguous if R1.1.2 is rewritten to read; “Evaluate mitigation methods to address identified risk(s)”.  This clearly supports R1 where the Requirement states “…controls for mitigating cyber security risks…”.

 

Request that R1.2.parts be updated so Entities will clearly know their expectations under this proposed Standard:

 

R1.2.1, Process(es) for receiving notification of vendor identified security events; or “Process(es) for receiving notification and release notes of vendor identified security events;

Justification: this updated wording will establish agreed upon processes between the vendor and entity.

 

R1.2.2, Process(es) for being notified cation when vendor employee remote or onsite access should no longer be granted;

Justification: this updated wording will establish agreed upon processes between the vendor and entity and that the entity need to be kept current on who is authorized by the vendor and allowed by the entity to access BES Cyber Systems.

 

1.2.3, Process(es) for disclosure of known applicable system vulnerabilities;

Justification: this updated wording will establish agreed upon processes between the vendor and entity and not present a catch 22 when a vendor does not share applicable system vulnerabilities.  We also request the “applicable system” be added (as above).  Entities may have other vulnerabilities that will not impact the entity’s applicable system. 

 

1.2.4, Coordination of response to vendor-related cyber security incidents;

No change.

1.2.5. Process(es) for verifying software integrity and authenticity of all applicable software and patches that are intended for use;

Justification: this updated wording will establish agreed upon processes between the vendor and entity and relates R1.2.3 since the vendor disclosed a vulnerability.  Suggest rewording to ensure that it only applies to situations where the vendor provides means to verify software, since standard does not impose requirements on vendors, Responsible Entity would otherwise be forced into non-compliance.

 

1.2.6. Coordination of remote access controls for (i) vendor-initiated Interactive Remote Access and (ii) system-to-system remote access with a vendor(s); and

No change.

 

1.2.7. Other pProcess(es) to address risk(s) as determined in Part 1.1.2, if applicable.

Justification: The use of the word “other” is too broad based and could be viewed as all processes, even those outside of the NERC arena.  With the clause of “... in Part 1.1.2, if applicable” clearly points to the identified risks of R1.1.2.

 

Within R1, R1.2, the SDT added the clause, “if applicable” as it relates to EACMS, PACS and PCA’s and the NSRF has concerns with this.  As written in the proposed Standard’s rational box, this item is covered in P.59.  FERC Order 829, P. 59, in part states:

 

“59. The new or modified Reliability Standard must address the provision and verification of relevant security concepts in future contracts for industrial control system hardware, software, and computing and networking services associated with bulk electric system operations”.

 

FERC does not state the use of EACMS, PACS and PCA’s, but rather “…must address the provision and verification of relevant security concepts in future contracts for industrial control system hardware, software, and computing and networking services associated with bulk electric system operations” (emphasis added).

 

By the SDT interpreting P 59 to mean EACMS, PACS and PCA’s, this unnecessarily expands the scope of this proposed Standard above and beyond the FERC directive.  The NSRF views this as, 1) future contracts concerning security concepts and 2) that support BES operations, which is the BES Cyber Systems identified per CIP-002-5.1a, only.  Notwithstanding that EACMAS and PACS is not associated with Low impact BES Cyber Systems.  Recommend that R1 and R1.2 have the “if applicable, EACMS, PACS and PCA’s” clause deleted.  This will allow the Responsible Entity to have their own risk based controls within their supply chain risk management plan(s) based on the definition of BES Cyber System.

 

Additional NSRF concerns:

The following statement is taken directly from the Rationale for Requirement R1:  “Obtaining specific controls in the negotiated contract may not be feasible and is not considered failure to implement an entity's plan.” This, in our opinion, is not conveyed in the written standard’s requirement. Though vendors are not intended to be affected by this standard’s requirements, Registered Entities will be forced to shy away from purchasing software from companies that cannot meet this standard. We see Regional Entities’ Enforcement teams having a difficult time in upholding any possible violations with this standard.

R1. Comments

When it states “if applicable, associated Electronic Access Control or Monitoring Systems, Physical Access Control Systems, and Protected Cyber Assets” what is their intent with the word applicable? It should either be applied or not applied to the systems. If the intent is to give the decision to the Registered Entities make this clearer, or remove the non-BCSs, completely.

R1.1.2 Comments

Add “mitigation” to methods. The intent is to alleviate an identified assessed risk.

MRO NSRF, Segment(s) 1, 2, 3, 4, 5, 6, 2/24/2017

- 2 - 0

The standard as written doesn’t clearly address the objectives as listed in its Requirements. It also creates confusion and possible double jeopardy with other CIP Standards.

faranak sarbaz, Los Angeles Department of Water and Power, 1, 2/27/2017

- 0 - 0

  • Recommend rewording Requirement 1 to: “Each Responsible Entity shall implement one or more documented supply chain risk management plan(s) that address controls for mitigating cyber security risks to BES Cyber Systems and, if applicable, associated Electronic Access Control or Monitoring Systems, Physical Access Control Systems, and Protected Cyber Assets, to specifically address the risk of introduction of malicious code through the supply-chain process. The plan(s) shall address:”        This addition clearly scopes the plan without relying on the title alone to hint at the proper scope.
  • Is 1.1.2 only evaluating or is it evaluating and implementing? 

Richard Kinas, 2/28/2017

- 1 - 0

The expressions, “Identify and assess risk(s),” in R1.1.1 and, “Evaluate methods to address identified risk(s),” in R1.1.2 are unsuitably vague. 

TFE opportunity is needed, nor should there be any obligation to impose measures on vendors (see our “additional comments” responses).

Terms such as, “vendor security event,” should be defined or removed.

R1.2.2 conflicts with CIP-004-6 R5 and should therefore be deleted.

R1.2.5 is largely duplicative of R3 and R5 of the standard.  They should be made consistent, or one of them should be deleted.

R1.2.6 is largely duplicative of R4 of the standard.  They should be made consistent, or one of them should be deleted.

The R1 Rationale statement that CIP-013-1, “does not require the Responsible Entity to renegotiate or abrogate existing contracts,” implies that no action needs to be taken for existing PEDs.  This point should be made explicit in the standard per se, but our “additional comments” concerns would still apply for replacing or upgrading existing equipment. 

Donald Lock, 2/28/2017

- 0 - 0

See APPA's, TAP's, and USI's comments.

Marty Hostler, Northern California Power Agency, 4, 2/28/2017

- 1 - 0

R1 is applicable to all BES Cyber Systems and, as applicable, EACMS PACS and PCA.  The philosophy used by preceding CIP standard drafting teams has been to write any requirements for low impact BES Cyber Systems in Attachment 1 of CIP-003 R2.  AEP believes this is a practice that results in a greater potential for compliance of all Responsible Entities.  AEP recommends that the essence of R1 be rewritten to address the lower risk associated with low impact BES Cyber Systems and moved to CIP-003 R2 Attachment 1.  In addition,  CIP-013-1 R1 should be rewritten to be only applicable to high and medium impact BES Cyber Systems

Thomas Foltz, AEP, 5, 3/2/2017

- 0 - 0

Rachel Coyne, Texas Reliability Entity, Inc., 10, 3/2/2017

- 0 - 0

Mike Smith, Manitoba Hydro , 3, 3/2/2017

- 0 - 0

Change/add language to emphasize that failure to obtain the cyber security controls from a vendor doesn’t translate to being out of compliance. Entity should have the ability to mitigate risks posed by vendors. IID feels that the SDT should consider modifications to current CIP standards where the topic is already addressed.

 

Jesus Sammy Alcaraz, Imperial Irrigation District, 1, 3/2/2017

- 0 - 0

  1. The standard lacks clarity on addressing R1.2 sub-requirements where no relationship of any sort exists between a RE and vendors whose products may be installed on applicable systems.

    Many software and hardware components utilized on BES Cyber Systems, associated EACMS, PCA, and PACS systems are provided without any contractual agreement other than acceptance of a End-User-License-Agreement (EULA) upon installation.

    For example, the Java Resource Environment, which is provided by Oracle Corporation, is utilized by many products. However, there is no agreement or financial transaction associated with the acquisition of Java.

This is even further complicated where open-source software is utilized for which no formal organization holds responsibility.

Finally, some proprietary software is acquired without any contractual arrangements due to low acquisition costs, such as an SSH client for less than $200.

In the case where there is a lack of relationship and/or financial interest in establishment of a formal agreement, how can RE address the provided requirements?

      2.  What incentive does a vendor have to disclose their vulnerabilities to a client?  Wouldn’t this disclosure ultimately serve to publicize       the vulnerabilities?

Responsible entities can request this cooperation, but verification that the vendor is disclosing all vulnerabilities is not possible.

Tennessee Valley Authority, Segment(s) 1, 3, 5, 6, 9/1/2016

- 0 - 0

During the CIP-013-1 webinar on Feb 2, the SDT indicated several times that it is not the intention of R1 to force vendors to perform actions so that entities can comply with the standard.  R1.2.1, R1.2.2, R1.2.3 would force vendors to develop internal processes to notify entities of any changes relating to the requirements which would force vendors to take independent action to notify entities of any changes.  Also, during the procurement phase, why would vendors reveal potential security flaws in their product above and beyond normal security patch notifications while they are competing against other vendors for the entities business?  This seems like wishful thinking.  Also, entities have processes in place already for other CIP requirements to fully prepare an asset for deployment into the ESP.  We don’t grab equipment off of the back of the delivery truck and deploy it into the ESP immediately so what is the point of knowing about security flaws in their products during procurement?  Any security flaws are probably already addressed with patches that will be downloaded and installed when preparing the asset for deployment.  Also, a vulnerability assessment has to be performed against the asset and CIP-007/CIP-005 security controls have to be checked prior to deployment.  1.2.1, 1.2.3, 1.2.4 appear to be redundant with CIP-007 R2 security patch management.  Is the SDT expecting vendors to provide information about security/design flaws above and beyond the normal security patch notifications?  If so, what kind of information would that be?

1.2.5 is troublesome as well (and it seems to be a duplicate of R3).  Entities typically use update or proxy servers to discover and identify applicable security patches.  For example, we use Windows Update Server Services to identify patches and roll them out once testing and approvals are complete.  Do we need to check the check sums of the identified patches or can we trust that the update servers are authenticating the software?

 

Eric Ruskamp, Lincoln Electric System, 6, 3/2/2017

- 0 - 0

SCE agrees with this requirement in concept.  However, as written, this requirement contains several issues that SCE believes should be resolved.  The language of CIP-013-1 Requirement R1 does not clearly state what is required and is open to several interpretations.  For example, Requirement R1, 1.1 requires the use of controls to identify and assess risks during the procurement and deployment of vendor products and services.  However, consistent with the COSO framework, a risk methodology identifies and assesses risks, and controls are used to mitigate those identified risks.  In addition, the requirement and its subparts do not define the security objective.  This lack of clarity in the language of Requirement R1 may pose issues during audit.  We recommend the following language to clarify the requirement consistent with intent of the FERC Order No. 829 directives:

 

R1.  Each Responsible Entity shall define, document, and implement one or more supply chain risk management methodologies(s) that address objectives, risks, and controls for mitigating cyber security risks to BES Cyber Systems and, if applicable, associated Electronic Access Control or Monitoring Systems, Physical Access Control Systems, and Protected Cyber Assets. The defined methodologies(s) shall define controls used to mitigate the risks of entering into contracts with vendors who pose significant risks to responsible entity’s information systems, of procuring products that fail to meet minimum security criteria, and of failing to receive adequate notice from compromised vendors, and shall include:  [Violation Risk Factor: Medium] [Time Horizon: Operations Planning]

 

1.1  The use of controls in procuring vendor product(s) or service(s) that address the following items, to the extent each item applies to the Responsible Entity's BES Cyber Systems and, if applicable, associated Electronic Access Control or Monitoring Systems, Physical Access Control Systems, and Protected Cyber Assets:

1.1.1       Process(es) for notification of vendor security events;

1.1.2       Process(es) for notification when vendor employee remote or onsite access should no longer be granted;

1.1.3       Process(es) for disclosure of known vulnerabilities;

1.1.4       Coordination of response to vendor-related cyber security incidents;

1.1.5       Process(es) for verifying software integrity and authenticity of all software and patches that are intended for use;

1.1.6       Coordination of remote access controls for (i) vendor-initiated Interactive Remote Access and (ii) system-to-system remote access with a vendor(s); and

1.1.7       Other process(es) to address risk(s) as determined, if applicable.

Deborah VanDeventer, On Behalf of: Edison International - Southern California Edison Company, WECC, Segments 1, 3, 5, 6

- 0 - 0

Please refer to comments submitted by Deborah VanDeventer on behalf of Southern California Edison.

Romel Aquino, Edison International - Southern California Edison Company, 3, 3/2/2017

- 0 - 0

Duke Energy requests further clarification from the drafting team on R1 and whether it applies to Low impact BES Cyber Assets. Since the current language of the requirement is silent on the level of applicability, an entity may assume that R1 applies to all High, Medium, and Low Impact BES Cyber Systems. Duke Energy disagrees with the concept of applying R1 to Low Impact BES Cyber Systems. At the outset, Low Impact BES Cyber Systems have been subject to a risk assessment and classified as Low Impact since they pose a minimal threat to the BES. Also, a Responsible Entity is not obligated to have an inventory list of its Low Impact BES Cyber Systems. In the rationale section of R5, it is even mentioned that a list of Low Impact BES Cyber Assets is not required. Without a list of Low Impact BES Cyber Systems, we fail to see how a Responsible Entity could demonstrate compliance with R1. For this reason, coupled with the fact that the Low Impact BES Cyber Systems pose a minimal risk to the BES, we do not believe R1 should be applicable to Low Impact BES Cyber Systems, and the requirement language should reflect the applicability.

Duke Energy requests confirmation that the rationale provided in R1 (and throughout the standard) be included in the standard, even after the standard has been finalized and approved. We feel that some of the language in the rationale is very useful, and that some of the language is warranted in the requirement(s) themselves. Specifically, the phrase used in the rationale of R1:

“Obtaining specific controls in the negotiated contract may not be feasible and is not considered failure to implement an entity's plan.”

We feel that this language is significant enough as it pertains to R1.2 and the possibility of disagreement between an Entity and an external party, that it should be placed somewhere in the standard.

Lastly, we recommend the drafting team consider developing this standard similarly to CIP-002-5.1a with regards to the leveraging of a bright-line model of risk assessment.  This will ensure that entities are assessing risk consistently of their vendors and removes the potential disagreement in audit that a regulator finds that the entity’s risk determination is incorrect based on a different set of subjective criteria.  This was the justification needed to move from the risk-based assessment methodology (RBAM) in CIP Versions 1 – 3 to the bright-line criteria developed in CIP Version 5.

Duke Energy , Segment(s) 1, 5, 6, 4/10/2014

- 0 - 0

Requirement R1 states “supply chain risk management plan(s)” while M1, R2, M2 states “supply chain cyber security risk management plan(s)”.  ReliabilityFirst recommends the SDT use consistent language so that there is no confusion on terminology.

Anthony Jablonski, ReliabilityFirst , 10, 3/3/2017

- 0 - 0

We have four concerns with the proposed requirement.

 

First, CIP-013 should follow the other CIP Standards with respect to Low BES Cyber Assets.  R1 should clearly exclude Low BES Cyber Assets and refer to R5 for those assets, and all requirements related to Low BES Cyber Systems should be consolidated into R5.   

 

Second, we are concerned that the difference in wording between R 1.1 which refers only to BES Cyber Systems, and R1.2 which includes EACMS, PACS and PCAs, is confusing and can cause inconsistencies in implementation.     R1.1, and subsequently R1.2, should be rewritten to help with this.  Please consider the following suggestions:

 

            From: “1.1 The use of controls in BES Cyber System planning and development to:”

            To:       "1.1 The use of controls in planning and development to:”

 

 

            From: “1.2 The use of controls in procuring vendor product(s) or service(s) that address the

                        Following items, to the extent each item applies to the Responsible Entity’s BES Cyber

                        Systems and if applicable, associated Electronic Access Control or Monitoring Systems,

                        Physical Access Control Systems, and Protected Cyber Assets:”

            To:      1.2 The use of controls in procuring vendor product(s) or service(s):  “ 

 

Third, we believe that the term “cyber security incident” in R1.2.4 should be capitalized to be clear that it is to be interpreted as the NERC-defined term “Cyber Security Incident”. 

 

Fourth, for consistency and clarity, we request the term ‘supply chain risk management’ be ‘supply chain cyber security risk management’ throughout the standard and guidance.

PPL NERC Registered Affiliates, Segment(s) 3, 1, 5, 6, 2/9/2017

- 2 - 0

See NPCC comments.

ALAN ADAMSON, New York State Reliability Council, 10, 3/3/2017

- 0 - 0

Please refer to comments submitted by Deborah VanDeventer on behalf of Southern California Edison

Thomas Rafferty, 3/3/2017

- 0 - 0

AECI contends that R1 should be separated into two distinct requirements.  R1 should be revised to require the Responsible Entity to develop and document supply chain risk management plan(s) that address controls for mitigating cyber security risks to BES Cyber Systems...  The SDT should then develop an additional requirement (R2) to require the Responsible Entity to implement the documented supply chain risk management plan(s) documented in R1.

In addition to the comments above, AECI supports the following comments submitted by the MRO NRSF:

“As stated in FERC Order 829, section 59, “The new or modified Reliability Standard must address the provision and verification of relevant security concepts in future contracts for industrial control system hardware, software, and computing and networking services associated with bulk electric system operations”.   R1 does not align with the above FERC directive.  FERC clearly insisted that future contracts will address the five attributes of section 59.

 If Future is added, the NSRF request that “Future” needs to be better defined.  If a company has a contract that is multi-year and each year a new Purchase Order is issued, the contract is not new or revised.  There needs to be direction given on how to implement the requirements of the standard going forward.

 If Future is not added, then the NSRF request a possible foot note stating… that R1 applies to all contracts (agreements) starting on the date of enforcement of CIP-013-1.  As FERC has stated in FERC Order 693, section 253, Entities need to satisfy the Requirements in order to be compliant.”

Furthermore, AECI urges the SDT to use the supply chain definition from NIST Special Publication 800-53 Rev.4 that was identified in paragraph 32, footnote 61 in this requirement.

Mark Riley, Associated Electric Cooperative, Inc., 1, 3/3/2017

- 0 - 0

CHPD has been engaging in dialogue with peers of trade associations such as Large Public Power Council to address the CIP-013 standard development activities.  We continue to be a strong supporter of efforts that ensure the security of the bulk electric system.  We appreciate the great strides that the SDT has made in the development of this standard to address the elements of the FERC Order while balancing reasonable responsibilities as required by the electric industry in support of the security objectives.        

CHPD does not agree with including all BES Cyber Systems in Requirement R1.  Using a risk-based approach, CHPD requests limiting this requirement to high and medium only.  As the current low impact requirements do not require entities to conduct an inventory of equipment and software or identify systems, CHPD believes this requirement will place substantial additional administrative burden on entities with low impact assets.  If a risk management plan is to be required low, with a reduced set of requirements to address their lower risk, CHPD  requests that those requirements be included as an element of R5 so all the low impact requirements are together or, ideally, included in CIP-003 along with the content of R5.

CHPD requests that the SDT add the following language from the rationale to the language of the standard: “Implementation of the cyber security risk management plan(s) does not require the Responsible Entity to renegotiate or abrogate existing contracts.”  

CHPD is concerned about compliance obligations for procurement activities associated with multi-party wide-area contracts such as state & city negotiated contracts.  An exception, comparable to a CIP Exceptional Circumstance, should be included in the standard for these kinds of procurement activities (see CHPD’s response to Question #9 for additional information on exceptions).

CHPD notes that the Rationale for R1 includes a definition of the term “vendors”.  This definition is also included in the Technical Guidance and Examples document.  This term should be officially added to the NERC Glossary of Terms and capitalized when used.

For R1.1.2 CHPD requests changing the word evaluate to determine.

For R1.2.1 CHPD requests that the words Security Event and the definition from the Technical Guidance and Examples document be placed in the NERC Glossary of Terms and capitalized when used.

For R1.2.1 CHPD requests that the SDT provide clarification on the language in the guidance document related to 1.2.1.  The document references the “process for notification” which is very different than the “request vendor cooperation” language.  The requirement as written would require that a process be defined and implemented.  CHPD requests additional language in the requirement that addresses “entities are not required to validate a vendor is adhering to its processes and a failure of a vendor to follow a defined process is not a violation of this Requirement.”

Mick Neshem, 3/3/2017

- 0 - 0

Platte River Power Authority (PRPA) has been engaging in dialogue with peers of trade associations such as Large Public Power Council to address the CIP-013 standard development activities.  We continue to be a strong supporter of efforts that ensure the security of the bulk electric system.  We appreciate the great strides that the SDT has made in the development of this standard to address the elements of the FERC Order while balancing reasonable responsibilities as required by the electric industry in support of the security objectives.        

PRPA does not agree with including all BES Cyber Systems in Requirement R1.  Using a risk-based approach, PRPA requests limiting this requirement to high and medium only.  As the current low impact requirements do not require entities to conduct an inventory of equipment and software or identify systems, PRPA believes this requirement will place substantial additional administrative burden on entities with low impact assets.  If a risk management plan is to be required, low with a reduced set of requirements to address their lower risk, PRPA requests that those requirements be included as an element of R5 so all the low impact requirements are together or, ideally, included in CIP-003 along with the content of R5.

PRPA requests that the SDT add the following language from the rationale to the language of the standard: “Implementation of the cyber security risk management plan(s) does not require the Responsible Entity to renegotiate or abrogate existing contracts.”  

PRPA is concerned about compliance obligations for procurement activities associated with multi-party wide-area contracts such as state & city negotiated contracts.  An exception, comparable to a CIP Exceptional Circumstance, should be included in the standard for these kinds of procurement activities (see PRPA’s response to Question #9 for additional information on exceptions).

PRPA notes that the Rationale for R1 includes a definition of the term “vendors”.  This definition is also included in the Technical Guidance and Examples document.  This term should be officially added to the NERC Glossary of Terms and capitalized when used.

For R1.1.2 PRPA requests changing the word evaluate to determine.

For R1.2.1 PRPA requests that the words Security Event and the definition from the Technical Guidance and Examples document be placed in the NERC Glossary of Terms and capitalized when used.

For R1.2.1 PRPA requests that the SDT provide clarification on the language in the guidance document related to 1.2.1.  The document references the “process for notification” which is very different than the “request vendor cooperation” language.  The requirement as written would require that a process be defined and implemented.  PRPA requests additional language in the requirement that addresses “entities are not required to validate a vendor is adhering to its processes and a failure of a vendor to follow a defined process is not a violation of this Requirement.”

Tyson Archie, Platte River Power Authority, 5, 3/3/2017

- 1 - 0

Please refer to comments submitted by Deborah VanDeventer on behalf of Southern California Edison.

Steven Mavis, 3/3/2017

- 0 - 0

Austin Energy (AE) has been engaging in dialogue with peers of trade associations such as Large Public Power Council to address the CIP-013 standard development activities.  We continue to be a strong supporter of efforts that ensure the security of the bulk electric system.  We appreciate the great strides that the SDT has made in the development of this standard to address the elements of the FERC Order while balancing reasonable responsibilities as required by the electric industry in support of the security objectives.        

AE does not agree with including all BES Cyber Systems in Requirement R1.  Using a risk-based approach, XXX requests limiting this requirement to high and medium only.  As the current low impact requirements do not require entities to conduct an inventory of equipment and software or identify systems, XXX believes this requirement will place substantial additional administrative burden on entities with low impact assets.  If a risk management plan is to be required low, with a reduced set of requirements to address their lower risk, XXX requests that those requirements be included as an element of R5 so all the low impact requirements are together or, ideally, included in CIP-003 along with the content of R5.

AE requests that the SDT add the following language from the rationale to the language of the standard: “Implementation of the cyber security risk management plan(s) does not require the Responsible Entity to renegotiate or abrogate existing contracts.”  

AE is concerned about compliance obligations for procurement activities associated with multi-party wide-area contracts such as state & city negotiated contracts.  An exception, comparable to a CIP Exceptional Circumstance, should be included in the standard for these kinds of procurement activities (see XXX’s response to Question #9 for additional information on exceptions).

AE notes that the Rationale for R1 includes a definition of the term “vendors”.  This definition is also included in the Technical Guidance and Examples document.  This term should be officially added to the NERC Glossary of Terms and capitalized when used.

For R1.1.2 AE requests changing the word evaluate to determine.

For R1.2.1 AE requests that the words Security Event and the definition from the Technical Guidance and Examples document be placed in the NERC Glossary of Terms and capitalized when used.

For R1.2.1 AE requests that the SDT provide clarification on the language in the guidance document related to 1.2.1.  The document references the “process for notification” which is very different than the “request vendor cooperation” language.  The requirement as written would require that a process be defined and implemented.  AE requests additional language in the requirement that addresses “entities are not required to validate a vendor is adhering to its processes and a failure of a vendor to follow a defined process is not a violation of this Requirement.”

Andrew Gallo, 3/3/2017

- 2 - 0

  1. The Rational for Requirement R1 includes a definition of the term “vendors”.  This definition is also included in the Guidelines and Examples document.  This term should be officially defined in the standard or added to the NERC Glossary of Terms and capitalized when used.
  2.  It is not clear if R1 applies to high, medium and low since R3, R4 and R5 specify the impact level.  The high, medium, low impact level applicability would be much easier to understand if this standard were written to be consistent with CIP-004 through CIP-011 through the use of Applicability Tables.
  3. R1.1 is vague in the language used with terms like “assess risk” and “evaluate”.  The need to revise CIP-002 shows the difficulties that have occurred when entities are required to assess risk.  Request that the SDT encourage NERC to include in the CIP-013 RSAW, language similar to that used in the CIP-003-7(i) RSAW, Attachment 1 Section 4, possible Notes to Auditor:“The entity must document its determination as to what are the supply chain risks. Once this determination has been made and documented, the audit team’s professional judgement cannot override the determination made by the Responsible Entity. “
  4. For R1: This requirement requires both the development and the implementation of a plan.    We recommend modifying this requirement into three steps which follows the CIP-014 structure – Entity to 1) identify risk, 2) develop a plan, 3) develop an implementation timeline. The timeline should use fixed dates or intervals and not dates that are linked to the completion of other compliance activities  
  5. For R1: We recommend stating the responsible entity is not required to renegotiate or abrogate existing contracts. The rationale from R1 states that “Obtaining specific controls in the negotiated contract may not be feasible and is not considered failure to implement an entity's plan.” This should be incorporated into the Requirement itself.
  6. For R1.1 and the R1 Rationale:  The R1 Rationale and the Guidance document list “planning, acquisition and deployment” and versions of these terms in the diagram.  R1.1 uses “planning and development”.  The meaning of “development” has not been clarified and is not part of the process addressed by this standard.  Suggest that “development” be clarified or removed.
  7. The standard as written addresses Vendor Risk Management and no other supply chain risks such as sole source and international dependencies.  Suggest changing the name, purpose, and other areas of the standard from supply chain” to “vendor”.
  8. For R1.1.2:

    1. We recommend changing evaluate to Determine. We also seek further clarification of the intent. As, written the requirement is ambiguous:

      1. Is the intent to have the entity evaluate potential methods to mitigate risk? or;

      2. to evaluate the effectiveness of mitigating that risk? or;

      3. is it meant to identify what controls you have to mitigate the risks you have?

    2. The evaluation of methods is a administrative task and similar to other tasks removed from the NERC standards as part of the Paragraph 81 project.

       

  9. For R1.2.1:  The words “Security Event” are in quotes the first time that they are used in the Guidelines and Examples document (page 6).  If the Guidelines and Examples document is providing a definition to be applied here, then this should be an officially defined term either in the standard or in the NERC glossary.  The s definition provided in the glossary is “any identified, threatened, attempted or successful breach of vendor’s components, software or systems” and “that have potential adverse impacts to the availability or reliability of BES Cyber Systems” It is unclear if the second portion is meant to be part of the definition.  Many cyber systems, like firewalls, are under constant threat and attempts to breach the systems security.  Suggest replacing “vendor security event” with “identification of a new security vulnerability”.  Vendors may not be able to determine if a vulnerability “could have potential adverse impact to the availability or reliability of BES Cyber System”.  This clause would only be applicable in determining when an entity would notify a vendor.

  10. For R1.2.1: Page 6, line 12 of the Guidance and Examples document list both notification of security events from the vendor and notifications from the entity.  The R1.2.1 language is unclear in requiring both types of notifications. 

  11. For R1.2.1: The requirement for the” process for notification” is very different than the “request vendor cooperation” guidance given on page 6, line 22 of the guidance document. 

  12. For R1.2.2: The requirement for the ”process for notification” is very different than the “request vendor cooperation” guidance given on page 6, line 22 of the guidance document  The requirement as written would require that a process be defined and implemented.  The failure of a vendor to notify the entity would, at a minimum be a violation of the entities process or maybe even a compliance violation as a failure to implement the process.  Would like to see an additional statement in the requirement language that “A failure of a vendor to follow a defined process is not a violation of this Requirement.”

  13. Page 6, line 12 of the guidance details the notification of the vendor by the entity. It is unclear that the R1.2.1 requires notification by the entity to the vendor as detail in the guidance document. 

  14. Recommend that “Security Event” be changed to require the reporting of only newly identified security vulnerabilities.

  15. Change 1.2.7 from pointing to 1.1.2 to 1.1.1.  Remove 1.2 since 1.2.7 covers 1.2.

  16. Do not agree with the current draft language that includes all High, Medium and Low BES Cyber Systems in Requirement R1. Suggests limiting this requirement to High and Medium only as the current Low Impact requirements do not require entities to conduct an inventory of equipment and software or identify systems. As written, this requirement will place additional administrative burden on entities and the impacts are not fully understood. If controls are needed for low impact, suggest moving these to R5 to consolidate all low impact into a single requirement.

  17. The SDT needs to make sure that there is no duplication in the standards.  Provide guidance on how areas that seem to overlap like Interactive Remote Access and CIP-005.

  18. Request the SDT to consider adding the following language from the rationale to the language of the standard “Implementation of the cyber security risk management plan(s) does not require the Responsible Entity to renegotiate or abrogate existing contracts.” 

  19. The Rationale for R1, it states that R1, P1.1 addresses P 56 of Order No. 829.  P 56 calls for a risk assessment of the entities internal systems with this language “how a responsible entity will include security considerations as part of its information system planning and system development lifecycle processes”. R1, P1.1.1 calls for a risk assessment of the vendors systems with this language “procurement and deployment of vendor products and services.”  The language in the order does not match the language in the standard and therefore suggest that the language be consistent to provide clarity.

  20. There could be an impact of contract requirements on the ability of public utilities to piggyback on wide-area contracts such as those of National Association of State Procurement Officials (NASPO) Cooperative, Western States Contracting Alliance (WSCA), Washington State Department of Enterprise Service, and others. Recommend that a exclusion be permitted in the case of such contracts, which are important to provide flexibility and negotiating strength for public utilities throughout the country.  Include language that provides an exclusion for contracts that are covered by other laws or regulations.

  21. The requirement should not reference the word “mitigation”.  Suggest that “mitigate” be replace with “address” as listed in R1.2.

  22. Request clarification - May a responsible entity's procurement plan identify and mitigate risks without requiring vendor involvement for each identified risk?

Brian Evans-Mongeon, Utility Services, Inc., 4, 3/3/2017

- 0 - 0

Public Utility District No. 1 of Chelan County (CHPD) has been engaging in dialogue with peers of trade associations such as Large Public Power Council to address the CIP-013 standard development activities.  We continue to be a strong supporter of efforts that ensure the security of the bulk electric system.  We appreciate the great strides that the SDT has made in the development of this standard to address the elements of the FERC Order while balancing reasonable responsibilities as required by the electric industry in support of the security objectives.        

 

CHPD does not agree with including all BES Cyber Systems in Requirement R1.  Using a risk-based approach, CHPD requests limiting this requirement to high and medium only.  As the current low impact requirements do not require entities to conduct an inventory of equipment and software or identify systems, CHPD believes this requirement will place substantial additional administrative burden on entities with low impact assets.  If a risk management plan is to be required low, with a reduced set of requirements to address their lower risk, CHPD  requests that those requirements be included as an element of R5 so all the low impact requirements are together or, ideally, included in CIP-003 along with the content of R5.

 

CHPD requests that the SDT add the following language from the rationale to the language of the standard: “Implementation of the cyber security risk management plan(s) does not require the Responsible Entity to renegotiate or abrogate existing contracts.”  

 

CHPD is concerned about compliance obligations for procurement activities associated with multi-party wide-area contracts such as state & city negotiated contracts.  An exception, comparable to a CIP Exceptional Circumstance, should be included in the standard for these kinds of procurement activities (see CHPD’s response to Question #9 for additional information on exceptions).

 

CHPD notes that the Rationale for R1 includes a definition of the term “vendors”.  This definition is also included in the Technical Guidance and Examples document.  This term should be officially added to the NERC Glossary of Terms and capitalized when used.

 

For R1.1.2 CHPD requests changing the word evaluate to determine.

 

For R1.2.1 CHPD requests that the words Security Event and the definition from the Technical Guidance and Examples document be placed in the NERC Glossary of Terms and capitalized when used.

 

For R1.2.1 CHPD requests that the SDT provide clarification on the language in the guidance document related to 1.2.1.  The document references the “process for notification” which is very different than the “request vendor cooperation” language.  The requirement as written would require that a process be defined and implemented.  CHPD requests additional language in the requirement that addresses “entities are not required to validate a vendor is adhering to its processes and a failure of a vendor to follow a defined process is not a violation of this Requirement.”

Janis Weddle, 3/3/2017

- 0 - 0

The Public Utility District No. 1 of Chelan County (CHPD) has been engaging in dialogue with peers of trade associations such as Large Public Power Council to address the CIP-013 standard development activities.  We continue to be a strong supporter of efforts that ensure the security of the bulk electric system.  We appreciate the great strides that the SDT has made in the development of this standard to address the elements of the FERC Order while balancing reasonable responsibilities as required by the electric industry in support of the security objectives.        

CHPD does not agree with including all BES Cyber Systems in Requirement R1.  Using a risk-based approach, CHPD requests limiting this requirement to high and medium only.  As the current low impact requirements do not require entities to conduct an inventory of equipment and software or identify systems, CHPD believes this requirement will place substantial additional administrative burden on entities with low impact assets.  If a risk management plan is to be required low, with a reduced set of requirements to address their lower risk, CHPD  requests that those requirements be included as an element of R5 so all the low impact requirements are together or, ideally, included in CIP-003 along with the content of R5.

CHPD requests that the SDT add the following language from the rationale to the language of the standard: “Implementation of the cyber security risk management plan(s) does not require the Responsible Entity to renegotiate or abrogate existing contracts.”  

CHPD is concerned about compliance obligations for procurement activities associated with multi-party wide-area contracts such as state & city negotiated contracts.  An exception, comparable to a CIP Exceptional Circumstance, should be included in the standard for these kinds of procurement activities (see CHPD’s response to Question #9 for additional information on exceptions).

CHPD notes that the Rationale for R1 includes a definition of the term “vendors”.  This definition is also included in the Technical Guidance and Examples document.  This term should be officially added to the NERC Glossary of Terms and capitalized when used.

For R1.1.2 CHPD requests changing the word evaluate to determine.

For R1.2.1 CHPD requests that the words Security Event and the definition from the Technical Guidance and Examples document be placed in the NERC Glossary of Terms and capitalized when used.

For R1.2.1 CHPD requests that the SDT provide clarification on the language in the guidance document related to 1.2.1.  The document references the “process for notification” which is very different than the “request vendor cooperation” language.  The requirement as written would require that a process be defined and implemented.  CHPD requests additional language in the requirement that addresses “entities are not required to validate a vendor is adhering to its processes and a failure of a vendor to follow a defined process is not a violation of this Requirement.”

Haley Sousa, 3/3/2017

- 0 - 0

For all Questions - I support the comments of Andrew Gallo, Austin Energy

Jeanie Doty, 3/3/2017

- 0 - 0

I support the comments of Andrew Gallo at Austin Energy.

W. Dwayne Preston, 3/3/2017

- 0 - 0

We agree with the LPPC/APPA comments.

JEA Voters, Segment(s) , 3/3/2017

- 0 - 0

While in overall agreement with Requirement 1, ACEC does have the following concerns:

1.  Part 1.1  requires the Responsible Entity to identify and assess risk(s) and evaluate methods to address identified risks. This requirement specifically changes the methodology for risk assessment defined in CIP-002-5.1. As noted in the Background section (Section 6) of the standard, "This general process of categorization of BES Cyber Systems based on impact on the reliable operation of the BES is consistent with risk management approaches for the purpose of application of cyber security requirements in the remainder of the Version 5 CIP Cyber Security Standards." This view of risk based upon the impact of BES Cyber Assets based upon the impact to the BES, not the devices cyber security risk, was defended by NERC and approved by FERC in Order 791 approving Version 5 of the CIP Standards. Based upon this, it would be consistent with CIP-002-5.1 to remove Part 1.1 of Requirement 1, modify requirement R1, Part 1.2.7 to state "other process(es) to address risk(s) as determined in CIP-002-5.1 R1, Parts 1.1 and 1.2" and to add to requirement R1 that it only applies to high and medium impact BES Cyber Systems as used in R3 and R4.

2.  In the Rationale for Requirement R1, the term vendor is defined as "(i) developers or manufacturers of information systems, system components, or information system services; (ii) product resellers; or (iii) system integrators." ACEC is concerned that by including product resellers or vendors, who have no direct or indirect control of these areas, misapplication of the procurement language in this Standard would impose unrealistic obligations, standards of care, and potential liability on professional services related to the supply chain.  As a consequence, services currently provided by engineering firms may be uninsurable under current professional liability insurance policies.  Other industries supporting the supply chain have raised similar concerns, noting that the effect of this approach will be to stifle competition, impair innovation, and increase costs.

Specifically, the guidance language in this Standard includes "integrator" requirements that impose responsibilities on engineering firms and other supply chain elements for control of software development; personnel management systems; industrial system controls (SCADA); and long­ term or post-contract reporting/remediation requirements (vulnerability testing and mitigation). Engineering firms do not typically develop such software and hardware, yet the guidance language suggests they should assume such liability for their use.  They also do not monitor and report vulnerabilities for vendor software and hardware.  This "one-size-fits-all" approach amounts to a significant reallocation of risk, imposing liability on engineering firms that they can neither manage, nor price.  The result will be fewer firms willing to perform services for this industry. This requirement should be modified to limit the scope and responsibilities to the vendor and end user to ensure risk is apportioned to the responsible parties.

Alan Farmer, On Behalf of: ACEC/Burns & McDonnell, NA - Not Applicable, Segments NA - Not Applicable

- 0 - 0

R1.1 The lack of guidelines and technical basis within a balloted and approved standard itself (not in a separate document) will result in many different interpretations and expectations on how to meet the requirement.  As demonstrated in the measures section, the section lacks specificity as potentially every correspondence with a vendor is subject to data request and audit. 

Who is the vendor?  Is it the manufacturer/software company, the reseller the hardware/software is acquired from, the shipping company, the integrator, others?  For temporary staff, is the contract employee a vendor? These are just example questions.

A lack of guidelines and technical basis within the standard itself could result in a broad interpretation of R1.1 that provides higher risk with little or no additional security.  As entities will have to guess the auditor’s interpretation, it increases the likelihood that a standard will be violated due to poor definition.

R1.2 This requirement should define a specific minimum security standard in a manner that avoids the inefficiencies from hundreds of entities performing the same analysis.  This inefficiency adds costs to entities and to vendors for items that will be passed on to entities.  As written, only concepts are presented, not a minimum specification that entities and vendors can effectively use to cost effectively demonstrate compliance in a consistent manner across the industry.

Michael Haff, On Behalf of: Seminole Electric Cooperative, Inc., FRCC, Segments 1, 3, 4, 5, 6

- 0 - 0

CHPD has been engaging in dialogue with peers of trade associations such as Large Public Power Council to address the CIP-013 standard development activities.  We continue to be a strong supporter of efforts that ensure the security of the bulk electric system.  We appreciate the great strides that the SDT has made in the development of this standard to address the elements of the FERC Order while balancing reasonable responsibilities as required by the electric industry in support of the security objectives.        

 

CHPD does not agree with including all BES Cyber Systems in Requirement R1.  Using a risk-based approach, CHPD requests limiting this requirement to high and medium only.  As the current low impact requirements do not require entities to conduct an inventory of equipment and software or identify systems, CHPD believes this requirement will place substantial additional administrative burden on entities with low impact assets.  If a risk management plan is to be required low, with a reduced set of requirements to address their lower risk, CHPD  requests that those requirements be included as an element of R5 so all the low impact requirements are together or, ideally, included in CIP-003 along with the content of R5.

 

CHPD requests that the SDT add the following language from the rationale to the language of the standard: “Implementation of the cyber security risk management plan(s) does not require the Responsible Entity to renegotiate or abrogate existing contracts.”  

 

CHPD is concerned about compliance obligations for procurement activities associated with multi-party wide-area contracts such as state & city negotiated contracts.  An exception, comparable to a CIP Exceptional Circumstance, should be included in the standard for these kinds of procurement activities (see CHPD’s response to Question #9 for additional information on exceptions).

 

CHPD notes that the Rationale for R1 includes a definition of the term “vendors”.  This definition is also included in the Technical Guidance and Examples document.  This term should be officially added to the NERC Glossary of Terms and capitalized when used.

 

For R1.1.2 CHPD requests changing the word evaluate to determine.

 

For R1.2.1 CHPD requests that the words Security Event and the definition from the Technical Guidance and Examples document be placed in the NERC Glossary of Terms and capitalized when used.

 

For R1.2.1 CHPD requests that the SDT provide clarification on the language in the guidance document related to 1.2.1.  The document references the “process for notification” which is very different than the “request vendor cooperation” language.  The requirement as written would require that a process be defined and implemented.  CHPD requests additional language in the requirement that addresses “entities are not required to validate a vendor is adhering to its processes and a failure of a vendor to follow a defined process is not a violation of this Requirement.”

Chad Bowman, 3/3/2017

- 0 - 0

SRP has an active role on the CIP-013 SDT with an employee serving as a member of the team as well as our support staff who are participating in the SDT meetings.  In addition, SRP has been engaging in dialogue with peers of trade associations such as LPPC to address the CIP-013 standard development activities.

SRP continues to be a strong supporter of efforts that ensure the security of the Bulk Electric System.  We appreciate the great strides that the SDT has made in the development of this standard to address the elements of the FERC Order, while balancing reasonable responsibilities as required by the electric industry in support of the security objectives.

SRP does not agree with including all BES Cyber Systems in Requirement R1.  Using a risk-based approach, SRP requests limiting this requirement to high and medium only.  As the current low impact requirements do not require entities to conduct an inventory of equipment and software or identify systems, SRP believes this requirement will place substantial additional administrative burden on entities with low impact assets.  If a risk management plan is to be required for low impact assets, with a reduced set of requirements to address their lower risk, SRP requests that those requirements be included as an element of R5 so all the low impact requirements are together or, ideally, included in CIP-003 along with the content of R5.

SRP requests that the SDT add the following language from the rationale to the language of the standard: “Implementation of the cyber security risk management plan(s) does not require the Responsible Entity to renegotiate or abrogate existing contracts.”

SRP is concerned about compliance obligations for procurement activities associated with multi-party wide-area contracts.  An exception, comparable to a CIP Exceptional Circumstance, should be included in the standard for these kinds of procurement activities (see SRP’s response to Question #9 for additional information on exceptions).

SRP notes that the Rationale for R1 includes a definition of the term “vendors”.  This definition is also included in the Technical Guidance and Examples document.  This term should be officially added to the NERC Glossary of Terms and capitalized when used.

For R1.1.2 SRP requests changing the word evaluate to determine.

For R1.2.1 SRP requests that the words Security Event and the definition from the Technical Guidance and Examples document be placed in the NERC Glossary of Terms and capitalized when used.

For R1.2.1 SRP requests that the SDT provide clarification on the language in the guidance document related to 1.2.1.  The document references the “process for notification” which is very different than the “request vendor cooperation” language.  The requirement as written would require that a process be defined and implemented.  SRP requests additional language in the requirement that addresses “entities are not required to validate a vendor is adhering to its processes and a failure of a vendor to follow a defined process is not a violation of this Requirement.”

Lona Calderon, On Behalf of: Salt River Project, WECC, Segments 1, 3, 5, 6

- 1 - 0

Please refer to comments submitted by Deborah VanDeventer on behalf of Southern California Edison

Kenya Streeter, Edison International - Southern California Edison Company, 6, 3/3/2017

- 0 - 0

No objections to R1.1. Although the actual language of R1.2 seems sound, how does this language in the R1 rationale section , "For example, entities can implement the plan by including applicable procurement items from their plan in Requests for Proposals (RFPs) and in negotiations with vendors. Obtaining specific controls in the negotiated contract may not be feasible and is not considered failure to implement an entity's plan" (Section B, p. 5) manage risks associated with Supply Chain Management vendors? Where is the incentive  for an entity to actively pursue vendor negotiations to minimize risks during the procurement phase? Merely adding control elements to an RFP that are not subsequently incorporated through vendor negotiations into a product or Service Level Agreement [SLA] seems to be nothing more than an academic exercise. At a minimum, under the current rationale the entity should provide working documents (as described in M1) of the negotiations process to demonstrate compliance with R1.2?

Steven Rueckert, Western Electricity Coordinating Council, 10, 3/3/2017

- 0 - 0

The following language from the rational box for Requirement R1 does not seem to incentivize an entity to actively pursue vendor negotiations to minimize risks during the procurement phase.

For example, entities can implement the plan by including applicable procurement items from their plan in Requests for Proposals (RFPs) and in negotiations with vendors. Obtaining specific controls in the negotiated contract may not be feasible and is not considered failure to implement an entity's plan.”

Merely adding control elements to an RFP that are not incorporated through vendor negotiations seems to be nothing more than an academic exercise. At a minimum, under the current rational, the entity should provide working documents of the negotiations process to demonstrate compliance with R1.2. Extending the initial review and update, as necessary

John Hagen, 3/3/2017

- 0 - 0

  • The extent of the “supply chain risk management plan” should be more clearly defined.  The Requirement language goes beyond what is typically considered “supply chain” activities (i.e. activities involving the transformation of natural resources, raw materials, and components into a finished product that is delivered to the end customer) and includes ongoing operational protections.  The Standard should more clearly define what is meant by “supply chain” and limit the associated Requirement to mitigating the associated risks.  All other operational related protections should be addressed within the existing CIP Standard that already cover the related protections (e.g. remote access controls should be included in CIP-007 and not in a supply chain standard).

  • The R1 Supply Chain Risk Management plan is applicable to BES Cyber Systems of all impact levels (and any associated EACMS, PACs, and PCAs). The following recommendations are provided:

    • The inclusion of Low Impact BES Cyber Systems in the scope of the Supply Chain Risk Management Plan should be reconsidered.  The existing CIP-002-5.1 and CIP-003-6 only requires an entity to identify asset(s) containing Low Impact BCS and does not require a documented inventory of low impact BCS/BCA or even a documented list of system/asset types.  The expectations of the Requirement would make it very difficult for an Entity to demonstrate compliance without a list of Low Impact BCS/BCA.

    • If after reconsideration it is still deemed necessary to include Low Impact BCS within the scope of the Supply Chain Risk Management Plan, the supply chain Requirement should be removed from CIP-013 and added to CIP-003 with the rest of the requirements that are applicable to Low Impact BCS.  SDTs have made conscious decisions to keep all Requirements applicable to Low Impact BCS within the CIP-003 Standard and not have them sprinkled throughout all the CIP Standards.  Additional time should be taken in developing the standard to remain consistent with this approach. (Note: Reference the CIP-003-7i draft CIP Standard related to low impact BES System Transient Cyber Assets.)

  • For consistency with other CIP Standards, CIP-003 R1.1 should be expanded to include supply chain risk management as part of the collective cyber security policies to be reviewed and approved by the CIP Sr. Manager at least every 15 months.

  • Use of the “Notional BES Cyber System Life Cycle” model is problematic.  Entities plan and assess future cyber systems, but acquire, configure, deploy, and maintain individual cyber assets. 

  • R1 – 1.2.1, 1.2.3, 1.2.4 references to vendor security events, vulnerabilities, and incidents are undefined and potentially overly broad.  Auditors may not collectively or individually agree with an individual RE’s assessment of how these terms are defined and used within their R1 Plan.

  • R1 – appears to overlap with parts of several existing CIP Standards, including: CIP-003-6 R2 Att. 1, Section 3; CIP-004-6 R4.1 - 4.4 and R5.1 - 5.5; CIP-005-5 R2.1 - 2.3; CIP-007-6 R2.1, R5.1, 5.5, 5.6, 5.7; and CIP-010-2 R1.1.  Expanding the scope of these existing CIP programs with a new Standard could unintentionally disrupt or conflict with current security architectures and/or critical operations.  FE recommends that the SDT consider making coordinated modifications to the scope and applicability of CIP-003, 004, 005, 007 and 010, at some future date, rather than extending existing requirements to a new Standard, i.e. CIP-013.  FE suggests that the scope of the Supply Chain Standard include the administrative controls needed to address Order 829, and the operational and technical security controls remain in the existing CIP standards.

  • Measures and Evidence – Since the R1 requires an entity to show that the plan has been implemented, M1 does not adequately describe the evidence required to demonstrate implementation of the plan, i.e. especially for technical sub-requirements.  (For example the evidence that an entity has implemented, “1.2.1 Process(es) for notification of vendor security events,” would likely require a process map for how vendor notifications are received, processed and resolved.  Additionally, an auditor would likely want a sample of actual dated notifications from several vendors with dated evidence of consistent action and resolution.)  FE recommends that the SDT provide additional guidance on evidence types, formats etc… similar to what was provided in CIP-003-6 Attachment 2.

Aaron Ghodooshim, FirstEnergy - FirstEnergy Corporation, 3, 3/3/2017

- 0 - 0

Please refer to RSC- NPCC comments

Si Truc Phan, On Behalf of: Hydro-Qu?bec TransEnergie, NPCC, Segments 1

- 0 - 0

Support FirstEnergy Comments submitted by Aaron Ghodooshim – Segment 4). 

Aubrey Short, 3/3/2017

- 0 - 0

R1, R2, and R5 contain obligations that apply to low impact BES Cyber Systems.  With the inherent low risk that comes with these systems, Basin Electric questions whether the same protections for highs and mediums should be applicable to lows, especially in context of R1.  Basin Electric would prefer low impact requirements be included in CIP-003 rather than CIP-013.  Basin Electric is concerned the inclusion of lows will necessitate maintaining a list of low BES Cyber Systems and possibly a list of low BES Cyber Assets.

 

As stated in FERC Order 829, section 59, “The new or modified Reliability Standard must address the provision and verification of relevant security concepts in future contracts for industrial control system hardware, software, and computing and networking services associated with bulk electric system operations”.   R1 does not align with the above FERC directive.  FERC clearly insisted that future contracts will address the five attributes of section 59. 

 

If Future is added, Basin Electric requests that “Future” needs to be better defined.  If a company has a contract that is multi-year and each year a new Purchase Order is issued, the contract is not new or revised.  There needs to be direction given on how to implement the requirements of the standard going forward.

 

If Future is not added, then Basin Electric requests a possible foot note stating… that R1 applies to all contracts (agreements) starting on the date of enforcement of CIP-013-1.  As FERC has stated in FERC Order 693, section 253, Entities need to satisfy the Requirements in order to be compliant.

 

The SDT should update R1 to clearly state this, such as:

“R1.  Each Responsible Entity shall implement one or more documented supply chain risk management plan(s) that address controls for mitigating cyber security risks to future contracts concerning the procurement of BES Cyber Systems and, if applicable, associated Electronic Access Control or Monitoring Systems, Physical Access Control Systems, and Protected Cyber Assets. The plan(s) shall address: “

 

This proposed update aligns with FERC Order 829, section 59 and clearly informs the applicable entity in what is required in future endeavors.  R1 will fulfill the FERC directive of having supply chain risk management plans for future procurement, which falls in line with the SDT’s “Notional BES Cyber System Life cycle” model.  Basin Electric does not agree with the “if applicable” wording and the addition of :” associated Electronic Access Control or Monitoring Systems, Physical Access Control Systems, and Protected Cyber Assets”, as this is not within the FERC Order.

 

R1.1 and its parts seem to be disjointed.  Basin Electric understands to have a Plan (R1) to mitigate cyber security risks to the future procurement of BES Cyber Systems, etc.  Within the Plan, entities are to use controls in their BES Cyber System planning and development “phase” (which is taken as the Entity’s internal processes of wants and needs).  To have controls during the “planning and development” phase will not have an impact on the procurement of a BES Cyber System, etc., since nothing is occurring; this is a planning phase, only.  Entities are only discussing their wants and needs.  This is similar to the caveat within the NERC Defined term of Operating Instruction; (A discussion of general information and of potential options or alternatives to resolve Bulk Electric System operating concerns is not a command and is not considered an Operating Instruction.)  R1.1 has two parts that should address what is required to occur within the plan concerning the objective of R1.1. 

 

Recommend R1.1 to read “The use of controls for BES Cyber Systems to:”

 

R1.1.1 Identify and assess risk(s) during the procurement and deployment of vendor products and services; and” (unchanged for the proposed draft).  This updated wording of R1.1, directs the use of controls within the plan of R1 and R1.1 states use controls to accomplish the attributes of R1.1.1.

 

 

Then R1.1.2, states the Entity is to “…evaluate methods to address identified risk(s)”.  As written, the Entity is to review (address?) their methods to mitigate identified risk(s).   Without saying, does this part need to be within the proposed Standard?  The intent is to mitigate any known risks, not evaluate methods to identify risk(s).  This could be viewed as an entity’s method of industry trends to see what new “processes” there are to “evaluate methods to address identified risk(s).  Or is this required in order to keep the “how and what” an entity does up to date and current with known “identify and assess” practices.  If so, please clarify.

 

It may be less ambiguous if R1.1.2 is rewritten to read; “Evaluate mitigation methods to address identified risk(s)”.  This clearly supports R1 where the Requirement states “…controls for mitigating cyber security risks…”.

 

Request that R1.2.parts be updated so Entities will clearly know their expectations under this proposed Standard:

 

Please add clarification to what is meant by vendor “services” as stated in R1.2.

 

R1.2.1, Process(es) for receiving notification of vendor identified security events; or “Process(es) for receiving notification and release notes of vendor identified security events;

Justification: this updated wording will establish agreed upon processes between the vendor and entity.

 

R1.2.2, Process(es) for being notified when vendor employee remote or onsite access should no longer be granted;

Justification: this updated wording will establish agreed upon processes between the vendor and entity and that the entity need to be kept current on who is authorized by the vendor and allowed by the entity to access BES Cyber Systems.

 

1.2.3, Process(es) for disclosure of known applicable system vulnerabilities;

Justification: this updated wording will establish agreed upon processes between the vendor and entity and not present a catch 22 when a vendor does not share applicable system vulnerabilities.  We also request the “applicable system” be added (as above).  Entities may have other vulnerabilities that will not impact the entity’s applicable system. 

 

1.2.5. Process(es) for verifying software integrity and authenticity of all applicable software and patches that are intended for use;

Justification: this updated wording will establish agreed upon processes between the vendor and entity and relates R1.2.3 since the vendor disclosed a vulnerability.  Suggest rewording to ensure that it only applies to situations where the vendor provides means to verify software, since standard does not impose requirements on vendors, Responsible Entity would otherwise be forced into non-compliance.

 

1.2.7. Process(es) to address risk(s) as determined in Part 1.1.2, if applicable.

Justification: The use of the word “other” is too broad based and could be viewed as all processes, even those outside of the NERC arena.  With the clause of “... in Part 1.1.2, if applicable” clearly points to the identified risks of R1.1.2.

 

Within R1, R1.2, the SDT added the clause, “if applicable” as it relates to EACMS, PACS and PCA’s and Basin Electric has concerns with this.  As written in the proposed Standard’s rational box, this item is covered in P.59.  FERC Order 829, P. 59, in part states:

 

“59. The new or modified Reliability Standard must address the provision and verification of relevant security concepts in future contracts for industrial control system hardware, software, and computing and networking services associated with bulk electric system operations”.

 

FERC does not state the use of EACMS, PACS and PCA’s, but rather “…must address the provision and verification of relevant security concepts in future contracts for industrial control system hardware, software, and computing and networking services associated with bulk electric system operations” (emphasis added).

 

By the SDT interpreting P 59 to mean EACMS, PACS and PCA’s, this unnecessarily expands the scope of this proposed Standard above and beyond the FERC directive.  Basin Electric views this as, 1) future contracts concerning security concepts and 2) that support BES operations, which is the BES Cyber Systems identified per CIP-002-5.1a, only.  Notwithstanding that EACMAS and PACS is not associated with Low impact BES Cyber Systems.  Recommend that R1 and R1.2 have the “if applicable, EACMS, PACS and PCA’s” clause deleted.  This will allow the Responsible Entity to have their own risk based controls within their supply chain risk management plan(s) based on the definition of BES Cyber System.

 

The following statement is taken directly from the Rationale for Requirement R1:  “Obtaining specific controls in the negotiated contract may not be feasible and is not considered failure to implement an entity's plan.” This is not conveyed in the written standard’s requirement. Though vendors are not intended to be affected by this standard’s requirements, Registered Entities will be forced to shy away from purchasing software from companies that cannot meet this standard. We see Regional Entities’ Enforcement teams having a difficult time in upholding any possible violations with this standard.

 

Mike Kraft, 3/3/2017

- 0 - 0

For R1.1.2: We seek further clarification of the intent. As, written the requirement is ambiguous:

    1. Is the intent to have the entity evaluate potential methods to mitigate risk? or;

    2. To evaluate the effectiveness of mitigating that risk? or;

    3. Is it meant to identify the controls in place to mitigate the identified risks?

       

Revise R1.2.1 as follows, “Process(es) for notification of vendor security events that affect BES reliability;”

For R1.2.1: Page 6 of the Guidance and Examples document list both notification from the vendor and notifications from the entity.  The R1.2.1 language is unclear in requiring both notifications. Request an update to the Guidance and Examples or the Requirement, for consistency.

It is not clear if R1 applies to High, Medium and Low since R3, R4 and R5 specify the impact level.  This standard should be written using the Applicability Tables used in CIP-003 through CIP-011.

R1.1 is vague in the language used with terms like “assess risk” and “evaluate”.

Concern that the Entity interpretation can be very different than Auditor interpretation. Once an entity has completed its risk evaluation, this determination cannot be overturned by the Regional Entity. 

Requirements overlap with existing CIP standards and create double jeopardy situations. Change 1.2.7 from pointing to 1.1.2 to 1.1.1

The following statements from the R1 Rationale box are important caveats for compliance and should be included in the Requirement text:

  • “Implementation of the cyber security risk management plan(s) does not require the Responsible Entity to renegotiate or abrogate existing contracts.”

  • “Obtaining specific controls in the negotiated contract may not be feasible and is not considered failure to implement an entity's plan.”

Con Edison, Segment(s) 1, 3, 5, 6, 0, 6/24/2016

- 0 - 0

Seminole Electric comments submitted by Michael Haff

Michael Ward, 3/3/2017

- 0 - 0

OSI Open Systems International, On Behalf of: OSI Open Systems International, NA - Not Applicable, Segments NA - Not Applicable

- 0 - 0

See overview comments and comments specific to Req2uirement R1, in attached file.

William Harris, 3/4/2017

Resilient Societies CIP 013-1 Comments 03042017.docx

- 0 - 0

Both the draft guidance document and the “Rationale for Requirement R1” section of the draft Standard contain the statement, “Obtaining specific controls in the negotiated contract may not be feasible and is not considered failure to implement an entity's plan.” However, there is nothing in any Requirement or any Requirement Part containing such language. Language similar to existing technical feasibility language in CIP-002 through CIP-011 should be added.

N&ST considers requirement part 1.2.2 redundant with existing CIP-004-6 Requirements R4 and R5 and recommends that either it be deleted from this Standard or modified to indicate a Responsible Entity may address it with existing CIP-004 access management procedures.

N&ST considers requirement part 1.2.6 redundant with existing CIP-005-5 Requirements R1 and R2 and recommends that either it be deleted from this Standard or modified to indicate a Responsible Entity may address it with existing CIP-005 procedures for Electronic Access Points and for Interactive Remote Access.

N&ST also recommends that all “Vendor remote access” requirements relevant to supply chain management be presented in one top-level requirement, not in two (R1 and R4).

N&ST also recommends that all “Software integrity and authenticity” requirements be presented in one top-level requirement, not two (R1 and R3).

Nicholas Lauriat, Network and Security Technologies, 1, 3/4/2017

- 0 - 0

We recommend the drafting team remove the phrase “if applicable, associated Electronic Access Control or Monitoring Systems, Physical Access Control Systems, and Protected Cyber Assets” from the language of Requirement R1 and Section 1.2 because, we feel that this language is inconsistent with FERC Order 829 Directive language.  Also, we suggest that the drafting team add some clarity to the sub-parts of Section 1.2 so that the industry will clearly know their expectations.

In reference to Requirement R1 and contracts, we suggest that the term “future contracts” be included in the proposed language of the Requirement. Also, we suggest the drafting team develop a definition for the term “future contracts” that would potentially include the phrase “new or modified contracts on or after the date of Enforcement” in the proposed definition.

SPP’s proposed language revision to R1:

“Each Responsible Entity shall implement one or more documented supply chain risk management plan(s) that address controls for mitigating cyber security risks to future contracts pertaining to the procurement of the BES Cyber System.”

Finally, we feel that the Measurement and Requirement language is inconsistent with the sub-part language. In the second sentence of the Requirement and Measurement the term “mitigating” is used, and we suggest replacing the term with “addressing”. We need to ensure all of our risk management options are available to us.  

SPP Standards Review Group, Segment(s) , 3/5/2017

- 0 - 0

Preston Walker, On Behalf of: PJM Interconnection, L.L.C., SERC, RF, Segments 2

- 0 - 0

With Vectren's commitment to safety, reliability, and compliance excellence, we appreciate the opportunity to provide comments.  Vectren supports attention to the threat of inadequate supply chain risk management procedures and offer these comments to that end.  We propose the SDT modify standard language based on Vectren's proposed language below:  

 

R1.       Each Responsible Entity shall implement one or more documented supply chain risk management plan(s) that address controls for mitigating cyber security risks to industrial control systems project planning that include processes to identify and evaluate risks during the procurement process.  For control system procurement activities related to industrial control systems covered by NERC CIP Standards CIP-002 through CIP-012 and CIP-014 that shall include: 

1.1  Planning, including the implementation of controls to identify, evaluate, and assess risks during the procurement and deployment of products and services.

1.2  Criteria for products and services that address:

     1.2.1.  Disclosing known product vulnerabilities;

     1.2.2.  Verifying product integrity and authenticity of software patches; and

     1.2.3.  Controlling vendor-initiated interactive remote access and

                 machine‑to‑machine remote access.

 

In the event the SDT does not accept the above changes, Vectren asks the following comments be considered:

 

R1

1.2 - How do we address these requirements with large companies (Microsoft, Oracle, etc.)?  How do we document the decision to stay with a preferred source that refuses to comply or cannot comply?  Is there a threshold or risk level? 
1.2.1 - "Vendor security events" is too broad of a statement.  Does this include physical security events as well?  Vectren recommends placing some type of a boundary around this statement. How do we document the decision to stay with the vendor if they refuse to comply?  Is this identifying for 1.2.4 coordination?  How does vendor security event relate to vendor-related cyber security incidents – is it the same?

1.2.3 – Technical Guidance & Examples states that for the duration of the relationship with the vendor cooperation in access to documentation regarding identified security breaches.  Standard states R1 and R2 are for the procurement of products, not operation/maintenance.
1.2.4 - "vendor-related cyber security incidents" is too broad of a statement.  Place some type of a boundary around this statement.  Coordinate with vendor, internally, what is our responsibility?  If Microsoft has a phishing attempt, what does that mean to the utility?  Is that an event for the utility?  What is the trigger for the utility to implement their plan?
1.2.6 - Would an Entity-owned anti-virus server that provides signature updates to assets be considered "vendor initiated" system-to-system remote access?
Add the forward-looking language to the standard, itself.

Propose to remove security events.  Would this require contract language that requires vendor to notify utility within 24 hours of a security event?

- 0 - 0

Requirement 1 should state specifically, as to its purpose, to prevent the introduction of malware or malicious code through the supply-chain process.

There should be an official NERC definition of the term ‘Vendor(s)’.  Although the Rational and Guidelines for each define the term, there should be a more official definition in order to provide appropriate guidance for the auditors when evaluating compliance to this standard.  

 

What does Requirement 1.1.2 mean?  ... The plan(s) shall address: The use of controls … to: Evaluate methods to address identified risk(s).  If a risk is identified during procurement and deployment, are we only required to evaluate methods to address those risks – or address the risks?  This is incredibly confusing and leaves this requirement wide-open to interpretation.

The rational for Requirement R5 is identified as being based on FERC Order 829 (page 48), which specifically addresses Vendor Remote Access to BES Cyber Systems, without respect to applicability – Sections 76-80.  Multiple requirements are referenced in Standards CIP-004, CIP-005 and CIP-007 that are only applicable to High and/or Medium Impact BESCS with weaknesses identified by not directly addressing vendor initiated machine-to-machine remote access.  In the final sentence of Section 80, it is noted that vendor remote access is not adequately addressed in the ‘Approved’ standards and, therefore, is an objective that must be addressed in the supply chain management plans.  Again, there is no reference to applicability, whereas the meat of the directive covers approved standards that reference Medium and High impact BESCS. 

The scope and content of the already approved standards is the appropriate place to account for this weakness. A full impact and applicability analysis should be performed prior to proposed modification(s).

John Williams, 3/6/2017

- 2 - 0

The draft Requirement R1.2 language creates compliance concerns due to the need for Responsible Entities to negotiate commercial contracts with vendors that commit the vendors to undertake the tasks necessary for R1.2, particularly in circumstances where only a single vendor has the capability of providing the necessary services for Cyber Assets covered by CIP-013-1.  For example, unless a vendor agrees to notify the Responsible Entity of vendor-identified vulnerabilities in the Cyber Assets provided or maintained by the vendor, Responsible Entities cannot comply with R1.2.3. 

Responsible Entities could encounter scenarios where:

•    Vendors may refuse to comply with the Responsible Entity’s vendor controls;

•    Vendors may demand an unreasonably high payment for compliance with the Responsible Entity’s vendor controls;

•    Vendors may agree to Responsible Entity controls but fail to take the steps necessary to implement those controls in a compliant manner; or 

•    Software/firmware made by a vendor no longer in business and unable to assist the Responsible Entity in the integrity and authenticity verification process.

 To ensure that compliance with CIP-013-1 does not place Responsible Entities in an untenable negotiating position, a compliance “safety valve” is necessary to allow Responsible Entities to comply with the Standard even in the absence of vendor assent to the Responsible Entity’s required controls.  Such a “safety valve” would be consistent with the current draft guidance on CIP-013-1 R1.2, which states that “[o]btaining specific controls in the negotiated contract may not be feasible and is not considered failure to implement an entity’s plan.” 

Guidance language in the G&TB portion of a Standard is helpful, but the “safety valve” concept should be included within the language of the Requirement itself because only that language forms the basis of a compliance assessment. 

Exelon has sent ideas under separate cover to the Drafting Team Chair outlining three options for providing the necessary “safety valve” along with proposed text edits to the requirements.  In short, these options include a technical feasibility exception, a commercial feasibility exception or a simple exception documentation process.

Daniel Gacek, Exelon, 1, 3/6/2017

- 0 - 0

With Vectren's commitment to safety, reliability, and compliance excellence, we appreciate the opportunity to provide comments.  Vectren supports attention to the threat of inadequate supply chain risk management procedures and offer these comments to that end.  Vectren proposes that the SDT modify standard language based on Vectren's proposed language below:  

 R1.       Each Responsible Entity shall implement one or more documented supply chain risk management plan(s) that address controls for mitigating cyber security risks to industrial control systems project planning that include processes to identify and evaluate risks during the procurement process.  For control system procurement activities related to industrial control systems covered by NERC CIP Standards CIP-002 through CIP-012 and CIP-014 that shall include: 

1.1  Planning, including the implementation of controls to identify, evaluate, and assess risks during the procurement and deployment of products and services.

1.2  Criteria for products and services that address:

     1.2.1.  Disclosing known product vulnerabilities;

     1.2.2.  Verifying product integrity and authenticity of software patches; and

     1.2.3.  Controlling vendor-initiated interactive remote access and

                 machine‑to‑machine remote access.

 

In the event the SDT does not accept the above changes, Vectren asks the following comments be considered:

R1

1.2 - How do we address these requirements with large companies (Microsoft, Oracle, etc.)?  How do we document the decision to stay with a preferred source that refuses to comply or cannot comply?  Is there a threshold or risk level? 

1.2.1 - "Vendor security events" is too broad of a statement.  Does this include physical security events as well?  Vectren recommends placing some type of a boundary around this statement. How do we document the decision to stay with the vendor if they refuse to comply?  Is this identifying for 1.2.4 coordination?  How does vendor security event relate to vendor-related cyber security incidents – is it the same?

1.2.3 – Technical Guidance & Examples states that for the duration of the relationship with the vendor cooperation in access to documentation regarding identified security breaches.  Standard states R1 and R2 are for the procurement of products, not operation/maintenance.

1.2.4 - "vendor-related cyber security incidents" is too broad of a statement.  Place some type of a boundary around this statement.  Coordinate with vendor, internally, what is our responsibility?  If Microsoft has a phishing attempt, what does that mean to the utility?  Is that an event for the utility?  What is the trigger for the utility to implement their plan?

1.2.6 - Would an Entity-owned anti-virus server that provides signature updates to assets be considered "vendor initiated" system-to-system remote access?

Add the forward-looking language to the standard, itself.

Propose to remove security events.  Would this require contract language that requires vendor to notify utility within 24 hours of a security event? 

 

Fred Frederick, 3/6/2017

- 0 - 0

We commend the drafting team for attempting to meet the directives and respect their effort and commitment to that end. We agree with now acting FERC chair LaFleur’s comments in her dissent on  Order 829, “The Commission is issuing a general directive in the Final Rule, in the hope that the standards team will do what the Commission clearly could not do: translate general supply chain concerns into a clear, auditable, and enforceable standard within the framework of section 215 of the Federal Power Act.” 

 

We do not agree with the approach in R1 (and R2) of creating “plans” and the intent of the plans to “cover the procurement aspects of all four objectives.”

 

Order 829’s four objectives did not include creating “plans.” All four of the directives either direct or use examples of specific operational cyber security controls which are best addressed as revisions to CIP-002 through -011.

 

Standards will not be effective, auditable or enforceable with a CIP-013 standard dueling with CIP-002 through -011 on scope and obligations.

 

CIP-002 through -011 are the appropriate place to address these operational security controls. These standards establish the least ambiguity in scope of obligations. These standards make granular distinctions based on risk when assigning what BES Cyber Assets are subject to each requirement. The risk distinctions go beyond just low, medium or high impact and incorporate Control Center, External Routable Connectivity and Interactive Remote Access in assigning obligations for requirements.

 

NERC’s Compliance Registry Summary of Unique Entities and Functions as of March 3, 2017, identifies 1,398 unique NERC entities. These entities range from entities with a couple breakers for low impact Facilities (lines), to entities operating gigawatts of low impact generation units to entities operating high-impact Control Centers for thousands of miles of medium impact Transmission Facilities, for example. All have BES Cyber Assets and all have very different risks to the grid and different obligations under CIP-002 through CIP-011.

 

“Plans” cannot achieve an effective, auditable and enforceable standard for 1,398 NERC entities that address the complicated issues identified in LaFleur’s dissent … and certainly not to meet the September 2017 directed deadline.

 

Industry can at a minimum advance cyber security by revisions to operational security controls in CIP-002 through -011. Other commenters, including EEI, are submitting examples of language as starting points.

 

We recommend the CIP-013 SDT request NERC to assign the CIP revisions SDT to assist the CIP-013 team to draft the technical revisions for each of the four directives in CIP-002 through CIP-013.  The CIP revisions SDT has met their Order 822 directive that had a deadline. To get the best standards for reliability and meet the FERC Order 829 directives’ deadlines, NERC and industry should reprioritize SDT teams’ work and resources.

Darnez Gresham, Berkshire Hathaway Energy - MidAmerican Energy Co., 3, 3/6/2017

- 2 - 0

With Vectren's commitment to safety, reliability, and compliance excellence, we appreciate the opportunity to provide comments.  Vectren supports attention to the threat of inadequate supply chain risk management procedures and offer these comments to that end.  We propose the SDT modify standard language based on Vectren's proposed language below:  

 

R1.       Each Responsible Entity shall implement one or more documented supply chain risk management plan(s) that address controls for mitigating cyber security risks to industrial control systems project planning that include processes to identify and evaluate risks during the procurement process.  For control system procurement activities related to industrial control systems covered by NERC CIP Standards CIP-002 through CIP-012 and CIP-014 that shall include: 

1.1  Planning, including the implementation of controls to identify, evaluate, and assess risks during the procurement and deployment of products and services.

1.2  Criteria for products and services that address:

     1.2.1.  Disclosing known product vulnerabilities;

     1.2.2.  Verifying product integrity and authenticity of software patches; and

     1.2.3.  Controlling vendor-initiated interactive remote access and

                 machine‑to‑machine remote access.

 

In the event the SDT does not accept the above changes, Vectren asks the following comments be considered:

 

R1

1.2 - How do we address these requirements with large companies (Microsoft, Oracle, etc.)?  How do we document the decision to stay with a preferred source that refuses to comply or cannot comply?  Is there a threshold or risk level? 
1.2.1 - "Vendor security events" is too broad of a statement.  Does this include physical security events as well?  Vectren recommends placing some type of a boundary around this statement. How do we document the decision to stay with the vendor if they refuse to comply?  Is this identifying for 1.2.4 coordination?  How does vendor security event relate to vendor-related cyber security incidents – is it the same?

1.2.3 – Technical Guidance & Examples states that for the duration of the relationship with the vendor cooperation in access to documentation regarding identified security breaches.  Standard states R1 and R2 are for the procurement of products, not operation/maintenance.
1.2.4 - "vendor-related cyber security incidents" is too broad of a statement.  Place some type of a boundary around this statement.  Coordinate with vendor, internally, what is our responsibility?  If Microsoft has a phishing attempt, what does that mean to the utility?  Is that an event for the utility?  What is the trigger for the utility to implement their plan?
1.2.6 - Would an Entity-owned anti-virus server that provides signature updates to assets be considered "vendor initiated" system-to-system remote access?
Add the forward-looking language to the standard, itself.

Propose to remove security events.  Would this require contract language that requires vendor to notify utility within 24 hours of a security event? 

Steve Rawlinson, 3/6/2017

- 0 - 0

  • Dominion supports the work that the drafting team has performed to-date and understands that the current draft of CIP-013-1 is continuing to evolve.  Dominion has developed extensive comments to allow the drafting team to focus efforts on areas of particular concern with the current draft.  Dominion supports the team’s continued efforts to bring stakeholder knowledge and expertise together to develop an objective based reliability standard that realistically addresses reliability gaps in the cyber supply chain process.

  • Dominion has a concern that the specific risks identified in P57 of FERC Order No. 829 are not included Requirement R1.  The term used in the current draft of CIP-013-1, “cyber security risks”, is overly broad and should be constrained by the enumerated risks in the FERC order. 

    Constraining language for the term ‘cyber security risks’ could include” risks associated with the of procurement and installation of unsecure equipment or software, the risks associated with unintentionally failing to anticipate security issues that may arise due to network architecture or during technology and vendor transitions, and the risks associated with purchasing software that is counterfeit or that has been modified by an unauthorized party.”

    Dominion recommends the development team consider the following language change for R1:

 “Each Responsible Entity shall implement one or more documented supply chain risk management plan(s) that include security considerations related to cyber security risks related to procuring and installing unsecure equipment or software, the risk of unintentionally failing to anticipate security issues that may arise due to network architecture, unintentionally arise during technology and vendor transitions, and purchasing software that is counterfeit or that has been modified by an unauthorized party for BES Cyber Systems and, if applicable, associated Electronic Access Control or Monitoring Systems, Physical Access Control Systems, and Protected Cyber Assets."

  • In addition, Dominion recommends that system applicability should be clearly identified in the Rationale section of the requirement.  Specifically, it is recommended that the “to the extent applicable” language should be removed from part 1. 2 and from the Rationale for R1. 

  • Dominion recommends the following for Parts 1.1.1 and 1.1.2:

    1. Identify and assess cyber security risk(s) to the BES, if any, during the procurement and deployment of vendor products and services; and
    2. Evaluate methods to address identified risk(s).

  • The term “services” in Part 1.2 is very broad and could be interpreted differently by different parties.  To ensure consistent understanding of this term, Dominion recommends that the development team place context around the term ‘service’ as used in requirement R1.2 in a compliance guidance document.

  • Dominion recommends that Part 1.2.7 be removed from CIP-013-1.  The comprehensive list of risks in Parts 1.2.1 through 1.2.6 appropriately addresses the risk.

  • As an alternative to the above recommendations, the development team could consider the following new proposed requirements in lieu of requirement R1 and R2:

    R1: Each Responsible Entity shall implement one or more documented supply chain risk management plan(s) that include security considerations related to cyber security risks of 1) procuring and installing un-secure equipment or 2) procuring and installing un-secure software, including purchasing counterfeit software, or software that has been modified by an un-authorized party 3) unintentionally failing to anticipate security issues that may arise due to network architecture,  4) unintentionally failing to anticipate security issues that may arise during technology and vendor transitions for BES Cyber Systems and associated Electronic Access Control or Monitoring Systems, Physical Access Control Systems, and Protected Cyber Assets.  The supply chain plan(s) shall address:
     

1. 1. Process(es) for notification of vendor security events;

1.2. Process(es) for notification when vendor employee remote or onsite access should no longer be granted;

1.3. Process(es) for disclosure by the vendor of known vulnerabilities;

1.4. Coordination of response to vendor-related cyber security incidents;

1.5. Process(es) for verifying software integrity and authenticity of all software and patches that are intended for use; and,

1.6. Coordination of remote access controls for (i) vendor-initiated Interactive Remote Access and (ii) system-to-system remote access with a vendor(s);

R2: The supply chain plan(s) shall include a process whereby any risk identified by the vendor during the purchasing process is assessed, reviewed, mitigating activities evaluated, and actions based on the selected mitigating activities implemented prior to placing the item(s) in service.

R3: The supply chain plan(s) shall be reviewed, updated as necessary, and approved by CIP SM or delegate at least once every fifteen (15) months.

The Rationale should explain that risks 1 and2 are addressed by R1.3 and R1.5, risk 3 by R1.1-R1.4 and R1.6, and risk 4 by R1.2, 1.3, and R1.6.  And that the planning and system lifecycle processes are addressed in the order are expected to encapsulate the purchasing process and are covered by R2.

2. The SDT developed CIP-013-1 Requirement R2 to address the Order No. 829 directive for entities to periodically reassess selected controls and keep plans up to date with emerging cyber security supply chain risk management concerns and vulnerabilities (P 46). Do you agree with the proposed requirement? If you do not agree, or if you agree but have comments or suggestions for the proposed requirement provide your recommendation and explanation.

Sean Bodkin, Dominion - Dominion Resources, Inc., 6, 3/6/2017

- 0 - 0

NRG recommends that the overall structure of the proposed CIP-013 standard be changed to be consistent with CIP-004 through CIP-011 standards (Specifically by applying similar formatting and use of applicability tables to identify the in-scope systems.)  NRG recommends that the CIP-013 standard should focus only on R1 and R2. This would allow the operational controls to remain or be placed in the existing CIP standards.

NRG suggests that the drafting team consider the risk impact classification for Requirement R1 as they would with the other Requirements through the Standard. Additionally, we suggest the drafting team remove the phrase “if applicable, associated Electronic Access Control or Monitoring Systems, Physical Access Control Systems, and Protected Cyber Assets” from the language of R1 and section 1.2 because, we think that this language is inconsistent with FERC Order 829 Directive language. Also, we suggest that the drafting team adds some clarity to the sub-parts of Section 1.2 on what are the SDT intentions for the industry in reference to these sub-parts.

In reference to R1 and contracts, NRG suggests that the term “future contracts” be addressed in the requirement language such as: “new or modified contracts” on or after the date of Enforcement. NRG recommends that these terms should be vetted in an implementation plan to include a conversation of initial compliance versus implemented/ongoing compliance (for example, Registered Entities need clear understanding of the scope as it pertains to plan reviews, new contracts, modified contracts, current contracts).

The Measurement and Requirement language is inconsistent with the sub-part language. In the second sentence of R1’s Measures section, the term “mitigating” is used and we suggest replacing the term with “addressing”.  NRG recommends that the term “addressing” includes that Registered Entities have the flexibility to exercise all risk management options within a Risk Management Plan (to include an acceptance of risk).

Each requirement should have a provision that allows an entity to accept the risk of selection a vendor that will not or cannot supply a control. The requirement intent appears to be about control of a process of disclosure and communication (how a vendor notifies us).  Whether a vendor fixes a vulnerability does not appear to be the direct scope or intent of the requirement.  Therefore, obtaining specific controls in the negotiated contract may not be feasible.  In these cases, NRG suggests that a failure to obtain and implement these controls is not considered a failure to implement an entity's plan.  NRG recommends that an entity be able to use a formalized risk management process to evaluate or accept the risk [Risk Management Plan].  In the event that a vendor cannot supply a control, that a Registered Entity may be able to present a mitigating control or that the Registered Entity be allowed to decide to accept the risk (for example a process to vet through a Registered Entity risk management, supply chain, and/or senior management departments and a process to accept risk based on a risk matrix).  This may be implied by R1.2.7; however NRG recommends that the standard explicitly communicate that a level of risk acceptance can be part of an entities’ Risk Management Plan. The Risk Management Plan could include steps to keep track of failures and steps to take in the event that vendor controls are found to be insufficient (for example, lessons learned feedback and correction process) - in the Measures section. An example of demonstration of compliance could be a periodic (i.e. 15 month) survey to the vendor during plan review (i.e. 15 month) validation of the notification processes between the two parties or dependent on the level or risk. NRG recommends that R1 should have a description of elements of a good Risk Management Plan (Measures) to include how deficiencies will be addressed, regular feedback to the vendor, and potential implications of non-conformance. NRG requests clarity on how revisions to the Risk Management Plan would need to be addressed for contracts that are in the process of being negotiated since this negotiation process may take months.

For R.1.2.7, NRG recommends using “or” vs “and” after R1.2.6

In R1.2, NRG recommends rewording the requirement to “implement processes that describe controls to address risks identified in R1.1.”  NRG recommends that the intent of R1 to be to provide processes (for disclosure and responding controls).  Therefore, NRG recommends that the Measure be limited to the sufficiency of the Entities’ vendor controls and evaluation process.  The Measures should state that the evaluation would be on an entities process for evaluation and if a vendor does not uphold a negotiated communication process, this does not reflect a compliance violation on the Registered Entity. 

Kara White, On Behalf of: NRG - NRG Energy, Inc., FRCC, MRO, WECC, Texas RE, NPCC, SERC, SPP RE, RF, Segments 3, 4, 5, 6

- 0 - 0

  1. The Rational for Requirement R1 includes a definition of the term “vendors”.  This definition is also included in the Guidelines and Examples document.  This term should be officially defined.

  2. It is not clear if R1 applies to high, medium and low since R3, R4 and R5 specify the impact level.  The high, medium, low impact level applicability would be much easier to understand if this standard were written to be consistent with CIP-004 through CIP-011 through the use of Applicability Tables.

  3. R1.1 is vague in the language used with terms like “assess risk” and “evaluate”.  The need to revise CIP-002 shows the difficulties that have occurred when entities are required to assess risk.  Request that the SDT encourage NERC to include in the CIP-013 RSAW, language similar to that used in the CIP-003-7(i) RSAW, Attachment 1 Section 4, possible Notes to Auditor:

    “The entity must document its determination as to what are the supply chain risks. Once this determination has been made and documented, the audit team’s professional judgement cannot override the determination made by the Responsible Entity. “

  4. For R1: This requirement requires both the development and the implementation of a plan.    Recommend breaking this into three steps, which follows CIP-014 – Entity to a) identify risk, b) develop a plan, c) implement plan in future contracts.

  5. For R1: We recommend stating the responsible entity is not required to renegotiate or abrogate existing contracts. The rationale from R1 states that “Obtaining specific controls in the negotiated contract may not be feasible and is not considered failure to implement an entity's plan.” This should be incorporated into the Requirement itself.

  6. For R1.1 and the R1 Rationale:  The R1 Rationale and the Guidance document list “planning, acquisition and deployment” and versions of these terms in the diagram.  R1.1 uses “planning and development”.  The meaning of “development” has not been clarified and is not part of the process addressed by this standard.  Suggest that “development” be clarified or removed.

  7. For R1.1.2: We seek further clarification of the intent. As, written the requirement is ambiguous:

    1. Is the intent to have the entity evaluate potential methods to mitigate risk? or;
    2. To evaluate the effectiveness of mitigating that risk? or;
    3. Is it meant to identify the controls in place to mitigate the identified risks?
  8. For R1.2.1:  The words “Security Event” are in quotes the first time that they are used in the Guidelines and Examples document (page 6).  If the Guidelines and Examples document is providing a definition to be applied here, then” Security Event” should be replaced or clarified in the Requirement.  This clarification could include “any identified, threatened, attempted or successful breach of the vendor’s components, software or systems used in the support of the Entity’s BES Cyber System.” This new language differentiates R1.2.1 from the vulnerabilities in R1.2.3
  9. For R1.2.1: Page 6 of the Guidance and Examples document list both notification from the vendor and notifications from the entity.  The R1.2.1 language is unclear in requiring both notifications. Request an update to the Guidance and Examples or the Requirement, for consistency.
  10. For R1.2.2: The requirement for the” process for notification” is very different than the “request vendor cooperation” guidance given on page 6, line 22 of the guidance document the requirement as written would require that a process be defined and implemented.  The failure of a vendor to notify the entity would, at a minimum be a violation of the entities process or maybe even a compliance violation as a failure to implement the process.  Would like to see an additional statement in the requirement language that “A failure of a vendor to follow a defined process is not a violation of this Requirement.”
  11. Request clarification - May a responsible entity's procurement plan identify and mitigate risks without requiring vendor involvement for each identified risk
  12. Requirements overlap with existing CIP standards and create double jeopardy situations. Change 1.2.7 from pointing to 1.1.2 to 1.1.1
  13. The following statements from the R1 Rationale box are important caveats for compliance and should be included in the Requirement text:

“Implementation of the cyber security risk management plan(s) does not require the Responsible Entity to renegotiate or abrogate existing contracts.”

“Obtaining specific controls in the negotiated contract may not be feasible and is not considered failure to implement an entity's plan.”

David Rivera, New York Power Authority, 3, 3/6/2017

- 0 - 0

Same as RoLynda Shumpert's comments from SCE&G:

In addition to high and medium impact BES Cyber Systems, the applicability of R1 should be clear to include low impact BES Cyber Systems.

SCE&G agrees with the concerns and question raised by the Security Practices Working Group of North American Generator Forum (NAGF) regarding “if applicable”:

“The phrase “if applicable” is ambiguous in the language of the main requirement. One reading is that “if applicable” means that the requirement only applies should the device types of associated EACMS, PACS or PCAs actually exist. Another reading is that “if applicable” is based on the risk that an entity places on a particular vendor as part of its documented risk management plan(s). If an entity performs a risk assessment of its vendors and finds that a vendor is a low or potentially zero risk (coupling a vendor’s reputation with their particular usage within an entity), does this mean that an entity could determine that the protections in R1 are therefore “not applicable” and not place any additional expectations on them?”

SCE&G believes the current language of R1 places unacceptable burden on the Regional Entities because the obligations of R1 occur at the end of the supply chain between Regional Entity and its vendor(s). Cyber security risks can occur at any phase of the supply chain(s) and R1 does not clearly demarcate the supply chain(s) where the risk management plan(s) apply. It is not clear how far in the supply chain(s) of a BES Cyber Asset do Responsible Entities need to identify and assess procurement risks.  SCE&G is concerned that Regional Entities will be held responsible for assessment and mitigation of risks outside of the Entities’ realm of influence over vendor internal processes and vendor’s supply chain(s).

Alyssa Hubbard, 3/6/2017

- 0 - 0

With Vectren's commitment to safety, reliability, and compliance excellence, we appreciate the opportunity to provide comments.  Vectren supports attention to the threat of inadequate supply chain risk management procedures and offer these comments to that end.  We propose the SDT modify standard language based on Vectren's proposed language below:  

 

R1.       Each Responsible Entity shall implement one or more documented supply chain risk management plan(s) that address controls for mitigating cyber security risks to industrial control systems project planning that include processes to identify and evaluate risks during the procurement process.  For control system procurement activities related to industrial control systems covered by NERC CIP Standards CIP-002 through CIP-012 and CIP-014 that shall include: 

1.1  Planning, including the implementation of controls to identify, evaluate, and assess risks during the procurement and deployment of products and services.

1.2  Criteria for products and services that address:

     1.2.1.  Disclosing known product vulnerabilities;

     1.2.2.  Verifying product integrity and authenticity of software patches; and

     1.2.3.  Controlling vendor-initiated interactive remote access and

                 machine‑to‑machine remote access.

 

In the event the SDT does not accept the above changes, Vectren asks the following comments be considered:

 

R1

1.2 - How do we address these requirements with large companies (Microsoft, Oracle, etc.)?  How do we document the decision to stay with a preferred source that refuses to comply or cannot comply?  Is there a threshold or risk level? 
1.2.1 - "Vendor security events" is too broad of a statement.  Does this include physical security events as well?  Vectren recommends placing some type of a boundary around this statement. How do we document the decision to stay with the vendor if they refuse to comply?  Is this identifying for 1.2.4 coordination?  How does vendor security event relate to vendor-related cyber security incidents – is it the same?

1.2.3 – Technical Guidance & Examples states that for the duration of the relationship with the vendor cooperation in access to documentation regarding identified security breaches.  Standard states R1 and R2 are for the procurement of products, not operation/maintenance.
1.2.4 - "vendor-related cyber security incidents" is too broad of a statement.  Place some type of a boundary around this statement.  Coordinate with vendor, internally, what is our responsibility?  If Microsoft has a phishing attempt, what does that mean to the utility?  Is that an event for the utility?  What is the trigger for the utility to implement their plan?
1.2.6 - Would an Entity-owned anti-virus server that provides signature updates to assets be considered "vendor initiated" system-to-system remote access?
Add the forward-looking language to the standard, itself.

Propose to remove security events.  Would this require contract language that requires vendor to notify utility within 24 hours of a security event? 

Brad Lisembee, 3/6/2017

- 0 - 0

The California ISO supports the comments submitted by the ISO/RTO Council (IRC) and the Security Working Group (SWG)

Richard Vine, 3/6/2017

- 0 - 0

Entergy/NERC Compliance, Segment(s) 1, 5, 3/1/2017

- 0 - 0

1)      The Rational for Requirement R1 includes a definition of the term “vendors”.  This definition is also included in the Guidelines and Examples document.  This term should be officially defined.

 

2)      It is not clear if R1 applies to high, medium and low since R3, R4 and R5 specify the impact level.  The high, medium, low impact level applicability would be much easier to understand if this standard were written to be consistent with CIP-004 through CIP-011 through the use of Applicability Tables.

 

3)      R1.1 is vague in the language used with terms like “assess risk” and “evaluate”.  The need to revise CIP-002 shows the difficulties that have occurred when entities are required to assess risk.  Request that the SDT encourage NERC to include in the CIP-013 RSAW, language similar to that used in the CIP-003-7(i) RSAW, Attachment 1 Section 4, possible Notes to Auditor:

 

“The entity must document its determination as to what are the supply chain risks. Once this determination has been made and documented, the audit team’s professional judgement cannot override the determination made by the Responsible Entity. “

 

4)      For R1: This requirement requires both the development and the implementation of a plan.    Recommend breaking this into three steps, which follows CIP-014 – Entity to a) identify risk, b) develop a plan, c) implement plan in future contracts.

 

5)      For R1: We recommend stating the responsible entity is not required to renegotiate or abrogate existing contracts. The rationale from R1 states that “Obtaining specific controls in the negotiated contract may not be feasible and is not considered failure to implement an entity's plan.” This should be incorporated into the Requirement itself.

 

6)      For R1.1 and the R1 Rationale:  The R1 Rationale and the Guidance document list “planning, acquisition and deployment” and versions of these terms in the diagram.  R1.1 uses “planning and development”.  The meaning of “development” has not been clarified and is not part of the process addressed by this standard.  Suggest that “development” be clarified or removed.

 

7)      For R1.1.2: We seek further clarification of the intent. As, written the requirement is ambiguous:

{C}a.      Is the intent to have the entity evaluate potential methods to mitigate risk? or;

{C}b.      To evaluate the effectiveness of mitigating that risk? or;

{C}c.       Is it meant to identify the controls in place to mitigate the identified risks?

 

8)      For R1.2.1:  The words “Security Event” are in quotes the first time that they are used in the Guidelines and Examples document (page 6).  If the Guidelines and Examples document is providing a definition to be applied here, then ”Security Event” should be replaced or clarified  in the Requirement.  This clarification could include “any identified, threatened, attempted or successful breach of the vendor’s components, software or systems used in the support of the Entity’s BES Cyber System.” This new language differentiates R1.2.1 from the vulnerabilities in R1.2.3

 

9)      For R1.2.1: Page 6 of the Guidance and Examples document list both notification from the vendor and notifications from the entity.  The R1.2.1 language is unclear in requiring both notifications. Request an update to the Guidance and Examples or the Requirement, for consistency.

 

10)  For R1.2.2: The requirement for the ”process for notification” is very different than the “request vendor cooperation” guidance given on page 6, line 22 of the guidance document  The requirement as written would require that a process be defined and implemented.  The failure of a vendor to notify the entity would, at a minimum be a violation of the entities process or maybe even a compliance violation as a failure to implement the process.  Would like to see an additional statement in the requirement language that “A failure of a vendor to follow a defined process is not a violation of this Requirement.”

 

11)  Request clarification - May a responsible entity's procurement plan identify and mitigate risks without requiring vendor involvement for each identified risk?

Quintin Lee, Eversource Energy, 1, 3/6/2017

- 0 - 0

CenterPoint Energy believes requirement R1 should only be applicable to BES Cyber Systems and recommends removing the portion of the requirement in R1 and R1.2 that states “and, if applicable, associated Electronic Access Control or Monitoring Systems, Physical Access Control Systems, and Protected Cyber Assets”. The FERC order is focused on “industrial control system hardware, software, and services associated with bulk electric system operations” and does not mention Electronic Access Control and Monitoring System (EACMS), Physical Access Control System (PACS), or Protected Cyber Assets (PCA). These additional systems are low risk and not considered industrial control systems. CenterPoint Energy recommends taking a risk-based approach as stated in the FERC order, so entities can focus their efforts on the supply chain risk management of BES Cyber Systems, which pose a higher risk to the Bulk Electric System. Additionally, this requirement is applicable to High, Medium, and Low Impact BES Cyber Systems, but Low Impact BES Cyber Systems do not have EACMS, PACS, and PCA.

If the intent of R1 is address the procurement controls, CenterPoint Energy recommends stating that in the main R1 requirement; otherwise, the sub-requirements in R1 can appear to be duplicative of the technical operational controls in R3 and R4.  Furthermore, the expectation for R1 is not clear for open source products with no vendor or products bought off the shelf with no purchase contract.

CenterPoint Energy recommends deleting R1.1.2 as the items in R1.2 appear to be the mitigation for the risks identified in R1.1. There is no need for a separate statement about mitigation in R1.1.2.

R1.2.1 uses the term “security events” which is not defined and the meaning could vary for each vendor.  CenterPoint Energy recommends defining the term for consistency.

R1.2.2 appears to be redundant to CIP-004 R5.1 and R5.2 and extends to PACS and PCA requirements formerly required only for BES Cyber Systems (BCS) and Electronic Access Control and Monitoring Systems (EACMS).

R1.2.4 should capitalize the term “cyber security incident” because it is a NERC defined term.

R1.2.5 includes “all software and patches” which conflicts with the existing CIP Standards.

R1.2.6 is either redundant with or in conflict with CIP-005 requirements to identify inbound and outbound access permissions with reason for access and control remote access with 2 factor authentication and an identified access control system. It is unclear what additional evidence would be expected to satisfy this requirement.

R1.2.7 is far too broad, requiring and exposing to audit a potentially infinite number of new processes. The requirement wording is not appropriate for a Reliability Standard.

Amelia Sawyer Anderson, On Behalf of: CenterPoint Energy Houston Electric, LLC, Texas RE, Segments 1

- 0 - 0

Nicolas Turcotte, Hydro-Qu?bec TransEnergie, 1, 3/6/2017

- 0 - 0

  No additional comments.

DTE Energy - DTE Electric, Segment(s) 5, 4, 3, 2/27/2017

- 0 - 0

In addition to high and medium impact BES Cyber Systems, the applicability of R1 should be clear to include low impact BES Cyber Systems.

 SCE&G agrees with the concerns and question raised by the Security Practices Working Group of North American Generator Forum (NAGF) regarding “if applicable”:

 “The phrase “if applicable” is ambiguous in the language of the main requirement. One reading is that “if applicable” means that the requirement only applies should the device types of associated EACMS, PACS or PCAs actually exist. Another reading is that “if applicable” is based on the risk that an entity places on a particular vendor as part of its documented risk management plan(s). If an entity performs a risk assessment of its vendors and finds that a vendor is a low or potentially zero risk (coupling a vendor’s reputation with their particular usage within an entity), does this mean that an entity could determine that the protections in R1 are therefore “not applicable” and not place any additional expectations on them?”

 

SCE&G believes the current language of R1 places unacceptable burden on the Regional Entities because the obligations of R1 occur at the end of the supply chain between Regional Entity and its vendor(s). Cyber security risks can occur at any phase of the supply chain(s) and R1 does not clearly demarcate the supply chain(s) where the risk management plan(s) apply. It is not clear how far in the supply chain(s) of a BES Cyber Asset do Responsible Entities need to identify and assess procurement risks.  SCE&G is concerned that Regional Entities will be held responsible for assessment and mitigation of risks outside of the Entities’ realm of influence over vendor internal processes and vendor’s supply chain(s).

RoLynda Shumpert, On Behalf of: SCANA - South Carolina Electric and Gas Co., SERC, Segments 1, 3, 5, 6

- 0 - 0

I support the comments submitted by Brian Evans-Mongeon, Utility Services, Inc, and Marty Hostler, Northern California Power Agency.

Dennis Sismaet, Northern California Power Agency, 6, 3/6/2017

- 0 - 0

OUC has been engaging in dialogue with peers of trade associations such as Large Public Power Council to address the CIP-013 standard development activities.  We continue to be a strong supporter of efforts that ensure the security of the bulk electric system.  We appreciate the great strides that the SDT has made in the development of this standard to address the elements of the FERC Order while balancing reasonable responsibilities as required by the electric industry in support of the security objectives.        

OUC does not agree with including all BES Cyber Systems in Requirement R1.  Using a risk-based approach, OUC requests limiting this requirement to high and medium only.  As the current low impact requirements do not require entities to conduct an inventory of equipment and software or identify systems, OUC believes this requirement will place substantial additional administrative burden on entities with low impact assets.  If a risk management plan is to be required low, with a reduced set of requirements to address their lower risk, OUC requests that those requirements be included as an element of R5 so all the low impact requirements are together or, ideally, included in CIP-003 along with the content of R5.

OUC requests that the SDT add the following language from the rationale to the language of the standard: “Implementation of the cyber security risk management plan(s) does not require the Responsible Entity to renegotiate or abrogate existing contracts.”  

OUC is concerned about compliance obligations for procurement activities associated with multi-party wide-area contracts such as state & city negotiated contracts.  An exception, comparable to a CIP Exceptional Circumstance, should be included in the standard for these kinds of procurement activities (see OUC’s response to Question #9 for additional information on exceptions).

OUC notes that the Rationale for R1 includes a definition of the term “vendors”.  This definition is also included in the Technical Guidance and Examples document.  This term should be officially added to the NERC Glossary of Terms and capitalized when used.

For R1.1.2 OUC requests changing the word evaluate to determine.

For R1.2.1 OUC requests that the words Security Event and the definition from the Technical Guidance and Examples document be placed in the NERC Glossary of Terms and capitalized when used.

For R1.2.1 OUC requests that the SDT provide clarification on the language in the guidance document related to 1.2.1.  The document references the “process for notification” which is very different than the “request vendor cooperation” language.  The requirement as written would require that a process be defined and implemented.  OUC requests additional language in the requirement that addresses “entities are not required to validate a vendor is adhering to its processes and a failure of a vendor to follow a defined process is not a violation of this Requirement.”

Ballard Mutters, Orlando Utilities Commission, 3, 3/6/2017

- 0 - 0

At the main Requirement level, while the rationale for Requirement R1 clearly states,

Implementation of the cyber security risk management plan(s) does not require the Responsible Entity to renegotiate or abrogate existing contracts, consistent with Order No. 829 (P. 36) as specified in the Implementation Plan”,

the requirement language is silent to this stipulation and therefore could lead to future confusion if left absent from the requirement language.

For ultimate clarity, ATC recommends the SDT consider the inclusion of language within the Requirement R1 itself that provides this specificity of scope. Proposed language for consideration could include phrasing like, but not limited to:

 “Each Responsible Entity shall implement one or more documented supply chain risk management plan(s) for new/future vendor/supply chain contracts, agreements, and/or relationships that address controls for mitigating…”

 Additionally, it is not uncommon for operational technology to be proprietary, and as such to limit the supplier base and/or the industry’s options/bargaining power over supplier practices. While the Rationale provided by the SDT carries the message that the intent is for this requirement to be forward-thinking and exclude existing contracts, even if the above proposed language were incorporated for clarity, it does not address the gap incurred after initial enforcement and implementation is achieved.  Once the Standard would be enforceable, inevitably existing contracts will continue to age and will need to be renewed or renegotiated. This requirement language does not address that condition, the feasibility of the imposed obligations upon the future expiration of existing contracts, nor the potential unintended consequences that may be incurred at the time that renewal or renegotiation process are initiated as those existing contracts reach maturity and ultimately expiration.  Consequently, the industry must assure that any future regulations regarding supply chain are constructed in a manner that 1.) supports successful and ongoing accomplishment of safe, secure, resilient, and reliable operation of the Bulk Electric System as existing contracts reach maturity and inevitably age to the level of expiration, 2.) prevents the unintended consequences that are at variance with the intent to maintain safe, secure, resilient, and reliable operation of the Bulk Electric System.

As an example, some unintended consequences could include, and may not be limited to:

  • Rendering previously contracted and necessary suppliers inviable upon the renewal or renegotiation of expiring/expired contracts creating a gap in the ability to procure necessary limited or proprietary supply that supports reliable operations,

  • The industry being subject to the operationally risky, unnecessarily time-constrained, and cost prohibitive need to perform wholesale replacements of infrastructure with a new supplier to achieve compliance,  

  • The industry being held hostage by its suppliers through cost prohibitive supplier capitalization via unreasonable increase to the cost of supplier services containing contractual language that meet the CIP-013-1 requirements for their products/services.

The absence of a provision to accommodate for these potential conditions could lead to an impossibility of compliance and/or could compromise reliability if the Registered Entity 1.) cannot procure necessary products without being subject to a compliance violation, or 2.) is forced to abandon current solutions and perform wholesale upgrades or replacements of BES Cyber System infrastructure in order to comply, 3.) is forced to pay exorbitant fees to renegotiate/renew contracts with limited suppliers of necessary limited or proprietary products.  Proposed language for consideration could include phrasing like, but not limited to:

 “Each supply chain risk management plan(s) shall contain provisions to address instances where expired/expiring vendor/supply chain contracts, agreements, and/or relationships cannot be reasonably renewed in a compliant mode without posing significant risk to safe, secure, resilient, and reliable operation of the Bulk Electric System and its BES Cyber Assets.

Requirement R1:

The scope of R1 is too broad in its reference to BES Cyber Systems without consideration of impact-rating. Consequently, some of the proposed requirements are duplicative of existing requirements for high and/or medium impact BES Cyber Systems, and others exceed the controls required for approved and future enforceable CIP Cyber Security Reliability Standards for low impact BES Cyber Systems. 

  1. This approach is at odds with the overall intent for the CIP Cyber Security Standards to be constructed in a manner that applies graduated controls commensurate with the risk associated to the impact rating of the BES Cyber System.

  2. This approach creates double jeopardy in certain instances, and is at variance with the approach to the body of documentation that comprises the CIP Cyber Security Standards wherein significant effort was invested to eliminate cross references and duplicative content.

  3. Through it redundancy, this approach is at odds with the efforts associated to the FERC filing of proposed retired standards for Project 2013-02 Paragraph 81, and the intent to eliminate requirements are administrative in nature only and therefore that do not provide security or reliability value.    

  4. This approach is at odds with the directive in FERC Order No. 829 (P.2), which directed NERC to draft a new or modified Reliability Standard wherein “…In making this directive, the Commission does not require NERC to impose any specific controls, nor does the Commission require NERC to propose “one-size-fits-all” requirements. 

Requirement R1 Sub Requirement 1.1.2:

At the sub requirement level, R1 sub requirement 1.1.2 is broad and unclear. ATC recommends the SDT consider providing clarification if anything actionable is expected beyond just an evaluation, such as creating a plan to address the risk and then mitigating risk where possible. 

Requirement R1 Sub Requirement 1.2.2:

R1.2.2 is simultaneously duplicative and additive to the language and/or intent of existing approved and effective CIP Cyber Security Reliability Standards as consequence of the broad reference to BES Cyber Systems without consideration of impact-rating in Requirement R1.

  1. CIP-004-6 R4 and R5 address access management and revocation for individuals having cyber or unescorted access to specified high and/or medium impact-rated BES Cyber Systems and associated Cyber Assets.  The existing enforceable CIP-004-6 standard is silent to the capacity with which a given individual is engaged with a Registered Entity, and therefore in its silence addresses employees, contractors, interns, apprentices, and even vendors or suppliers etc. The existing implemented access requirements within CIP-004-6 are more prescriptive than what is proposed for CIP-013-1 rendering CIP-013-1 R1.2.2 superfluous. Consequently, CIP-013-1 R1.2.2 adds no value and rather creates a condition of potential double jeopardy for existing approved and enforceable Standard CIP-004-6 R5.  Through it redundancy, this approach is also at odds with the efforts associated to the FERC filing of proposed retired standards for Project 2013-02 Paragraph 81, and the intent to eliminate requirements are administrative in nature only and therefore that do not provide security or reliability value.   

  2. CIP-003-6 R1.2 prescribes policy level controls, and CIP-003-6 R2 Attachment 1 Sections 2-3 necessitate plans for the implementation of physical and electronic controls for low impact BES Cyber Systems.  CIP-013-1 R1.2.2 effectively expands the scope and requirements for access of vendor employees beyond what is mandated as access requirements of low impact BES Cyber Systems to all other types of employees and Registered Entity engagements wit personnel.  Any expansion in scope to access requirements or controls for low impact BES Cyber Systems as defined in the currently approved and enforceable Standard should be subject to the Standards Authorization Request, Development, Commenting, and Balloting Processes so as not to be effectively revising an existing approved and enforceable Reliability Standard through the creation of a separate one.

  3. Additionally, the inclusion of “onsite access” within the proposed language in 1.2.2 is an expansion in scope from the second directive in FERC Order No. 829 (P.2), which directed NERC to draft a new or modified Reliability Standard that “…should address the following security objectives, discussed in detail below: (1) software integrity and authenticity; (2) vendor remote access; (3) information system planning; and (4) vendor risk management and procurement controls.”

Requirement R1 Sub Requirement 1.2.4 and 1.2.6:

For consistency with other 1.2.x sub requirements, ATC recommends the SDT consider replacing ‘Coordination’ with ‘Process’ by revising the language in both R1.2.4 and R1.2.6 to “Process to respond to vendor-related….”, and “Process to implement remote access controls…”, respectively.

Requirement R1 Sub Requirement 1.2.5:

CIP-013-1 R1.2.5 is heavily dependent on supplier capabilities and their willingness to provide tools and/or mechanism to enable Registered Entities to perform integrity or authenticity verification.  ATC recommends the SDT consider incorporating language that provides flexibility where it is not technically possible.

Lauren Price, 3/6/2017

- 0 - 0

CPS Energy supports the comments provided by ERCOT and APPA

Brian Bartos, On Behalf of: Brian Bartos, , Segments 1, 3, 5

- 0 - 0

Xcel Energy supports the comments filed by the Edison Electric Institute (EEI).

- 0 - 0

1.       We are concerned about the risks associated with BES Cyber Asset products and services that may contain potentially malicious functionality, are counterfeit, or are otherwise vulnerable due to poor manufacturing and development practices within the industrial control system supply chain. However, the proposed draft standard extends well beyond software authenticity and beyond the ability for entities to manage.

 

2.       New requirements for notification of changes in supplier workforce and incident reporting are impossible to implement and audit due to a lack of a consistent approach and application amongst entities. Industry and industrial supply chain vendors would serve more time sending out notification agreements and attestations than working on making a better and more secure product. Would the supply chain vendor be required to send out a notification every time an employee leaves or finds a virus in the office? If so, then the requirement will be too burdensome for vendors and entities to manage.

 

3.      We believe NERC language in the in the draft standard would have a significant negative impact on the industrial control system community over the long term. As seen in the nuclear industry, specific standards that are outside of other critical sectors will only drive cost up and a willing supply of vendors, down.

 

4.      The need for such a broad set of requirements are unnecessary due to the existing requirement for the entity to have an incident response plan, anti-virus protection and patch management.

 

5.      The additions of “and, if applicable, 4 associated Electronic Access Control or Monitoring Systems, Physical Access Control Systems, and 5 Protected Cyber Assets” in requirement 1 greatly expands the scope of cyber assets. ACES recommends limiting the cyber assets in scope to BES Cyber Assets.

Warren Cross, On Behalf of: ACES Power Marketing, MRO, WECC, Texas RE, SERC, SPP RE, Segments 1, 3, 4, 5

- 0 - 0

Though each of the objectives in Order 829 is addressed, Reclamation recommends a more simplified format for the requirements as the SDT originally suggested in the Cyber Security Supply Chain Management Technical Conference on November 10, 2016.

 

As part of Supply Chain Risk Management, Reclamation understands that the risks associated with interaction with vendors, their products, and/or their services are to be considered and mitigated with controls such as contract clauses, physical controls, and/or electronic controls (including vendor remote access).  Reclamation recommends that Requirement R1 should instead address the development of one or more supply chain risk management plans that identify risks and controls for mitigating cyber security risks throughout the life cycle(s) of BES Cyber Systems and, if applicable, associated Electronic Access Control or Monitoring Systems, Physical Access Control Systems, and Protected Cyber Assets.

 

Within Requirement R1, the life cycle steps to consider in identifying risks and the respective controls should include but not be limited to: evaluation of design, procurement, acquisition, testing, deployment, operation, and maintenance.

 

Within each Requirement, the sub-requirements should distinguish between high, medium, and low impact BES Cyber Systems and other supporting systems. Reclamation recommends the implementation plan enforcement dates be staggered based on high, medium, and low impact for auditing purposes and to allow the associated risks and severity levels to be spelled out more clearly.

Wendy Kalidass, U.S. Bureau of Reclamation, 5, 3/6/2017

- 0 - 0

Rationale for Requirement R1: 

The rationale language for R1 states, “The cyber security risk management plan(s) specified in Requirement R1 apply to BES Cyber Systems." If the intent of the “BES Cyber Systems” reference is to be applicable for all three impact classifications (High, Medium and Low), IPC recommends adding impact classification language.

The rationale language for R1 states, “Implementation of the cyber security risk management plan(s) does not require the Responsible Entity to renegotiate or abrogate existing contracts.” How does the SDT expect Responsible Entities to demonstrate compliance if existing contracts are acceptable?

The rationale language for R1 states, “The objective of verifying software integrity and authenticity (Part 1.2.5) is to ensure that the software being installed in the applicable cyber system was not modified without the awareness of the software supplier and is not counterfeit.” How does the SDT expect Responsible Entities/vendors to demonstrate compliance with this?

The rationale language for R1 states, “Implementation of the cyber security risk management plan(s) does not require the Responsible Entity to renegotiate or abrogate existing contracts, consistent with Order No. 829 (P. 36) as specified in the Implementation Plan." IPC suggests including the verbiage “with vendors, suppliers or other entities executed as of the effective date of CIP-013-1” to the third paragraph of the “Rationale for Requirement R1.”

 R1

The requirement language for R1 states, “Each Responsible Entity shall implement one or more documented supply chain risk management plan(s) that address controls for mitigating cyber security risks to BES Cyber Systems and, if applicable, associated EACMS, PACS and PCAs.” If the intent of the “BES Cyber Systems” reference is to be applicable for all three impact classifications (High, Medium and Low), IPC recommends adding impact classification language. In addition, if the intent of the “if applicable” reference is to imply “EACMS, PACS and PCAs associated with BES Cyber Systems,” IPC recommends replacing the “if applicable” language with “and their associated” language to remain consistent with current enforceable standard language.

R1.2 – IPC has concerns about the ability of a Responsible Entity to comply with, as written, R1.2, specifically R1.2.1 – R1.2.7. IPC believes there will be instances when vendors (e.g., larger IT vendors, smaller vendors, open source software, etc.) will not agree to provide all of the information necessary to meet the R1.2.1 – R1.2.7 requirements, potentially forcing Responsible Entities to look at other, lower quality options to ensure compliance, or vendors will use the required compliance control(s) as leverage during contract negotiations. The rationale for R1 states, “Obtaining specific controls in the negotiated contract may not be feasible and is not considered failure to implement an entity’s plan.” However, the rational language does not translate to a release from the R1.2 requirements. How does the SDT foresee Responsible Entities demonstrating compliance when an entity is unable to obtain a specified control(s)? Further, how does the SDT foresee these requirements being measured by auditors?    

R1 and R1.2 require the development and implementation of “processes” and/or “plans.” If vendors refuse to agree to terms, what implementation evidence does the SDT expect Responsible Entities to provide? Additionally, if the vendor agrees to the terms stated but fails to deliver according to the documented process, does the SDT foresee this being viewed as non-compliance?

IPC would like to know what additional security measures R1.2.1, R1.2.3, and R1.2.4 provide that aren’t already covered by CIP-007-6, for example CIP-007-6 R2?

IPC recommends adding mitigation plan verbiage to R1.2 requirement language.

M1

The measure language for R1 states, “Evidence shall include (ii) documentation to demonstrate implementation of the supply chain cyber security risk management plan(s), which could include, but is not limited to, written agreements in electronic or hard copy format, correspondence, policy documents, or working documents that demonstrate implementation of the cyber security risk management plan(s).” How will this measure apply to Responsible Entities who do not renegotiate or abrogate existing contracts or are unable to obtain specific controls?

Laura Nelson, 3/6/2017

- 0 - 0

Santee Cooper has been engaging in dialogue with peers of trade associations such as Large Public Power Corporation to address the CIP-013 standard development activities.  We continue to be a strong supporter of efforts that ensure the security of the bulk electric system.  We appreciate the great strides that the SDT has made in the development of this standard to address the elements of the FERC Order while balancing reasonable responsibilities as required by the electric industry in support of the security objectives.

Santee Cooper does not agree with including all BES Cyber Systems in Requirement R1 and suggest using a risk-based approach, to limit this requirement to high and medium only.  As the current low impact requirements do not require entities to conduct an inventory of equipment and software or identify systems, Santee Cooper believes this requirement will place substantial additional administrative burden on entities with low impact assets.  If a risk management plan is to be required low, with a reduced set of requirements to address their lower risk, Santee Cooper requests that those requirements be included as an element of R5 so all the low impact requirements are together or, ideally, included in CIP-003 along with the content of R5.

Santee Cooper requests that the SDT add the following language from the rationale to the language of the standard: “Implementation of the cyber security risk management plan(s) does not require the Responsible Entity to renegotiate or abrogate existing contracts.”  

Santee Cooper is concerned about compliance obligations for procurement activities associated with system integrators.  An exception, comparable to a CIP Exceptional Circumstance, should be included in the standard for these kinds of procurement activities because they provide important negotiating strength, flexibility, and effectiveness in contracting (see Santee Cooper’s response to Question #9 for additional information on exceptions).

Santee Cooper notes that the Rationale for R1 includes a definition of the term “vendors”.  This definition is also included in the Technical Guidance and Examples document.  This term should be officially added to the NERC Glossary of Terms and capitalized when used.  Additionally, Santee Cooper requests that the term be used consistently throughout the standard and not switch between vendor and supplier.

For R1.1.2 requests changing the word evaluate to determine.

For R1.2.1 Santee Cooper requests that the SDT provide clarification on the language in the guidance document related to 1.2.1.  The document references the “process for notification” which is very different than the “request vendor cooperation” language.  The requirement as written would require that a process be defined and implemented.  Santee Cooper requests additional language in the requirement that addresses “entities are not required to validate a vendor is adhering to its processes and a failure of a vendor to follow a defined process is not a violation of this Requirement.”

In Measure M1, Santee Cooper requests that the language be changed to be consistent with the Requirement. Specifically, change “Evidence shall include (i) one or more documented supply chain cyber security risk management plan(s) that address controls for MITIGATING cyber security risks as specified in the Requirement…” to “Evidence shall include (i) one or more documented supply chain cyber security risk management plan(s) that address controls for ADDRESSING cyber security risks as specified in the Requirement…” (BOLD emphasis added).  The construction “address risk” conforms to the text of the Requirement and acknowledges that risk might be avoided or transferred, for example, as opposed to mitigated. 

Santee Cooper requests that the title of the standard be changed to “Vendor Risk Management” to clarify that the scope of the required activities relate to the relationships among a utility and its vendors. In common usage, the term “supply chain risk management” encompasses a much broader scope of concerns, including quality control and verification of third-party suppliers as well as addressing sole-source and international dependencies. Although the FERC Order and SDT white paper cite concerns about both vendor risk and supply chain risk, the requirements actually proposed in CIP-013 address vendor risk. A change of title is a simple means to clarify what is intended in R1.1, in particular, and helps identify auditable actions throughout R1. 

Santee Cooper , Segment(s) 1, 5, 3/6/2017

- 0 - 0

LCRA does not agree with including all BES Cyber Systems in Requirement R1.  Using a risk-based approach, LCRA requests limiting this requirement to high and medium only.  As the current low impact requirements do not require entities to conduct an inventory of equipment and software or identify systems, LCRA believes this requirement will place substantial additional administrative burden on entities with low impact assets.  If a risk management plan is to be required low, with a reduced set of requirements to address their lower risk, LCRA requests that those requirements be included as an element of R5 so all the low impact requirements are together or, ideally, included in CIP-003 along with the content of R5.

Teresa Krabe, Lower Colorado River Authority, 5, 3/6/2017

- 0 - 0

BPA believes CIP-013-1 R1 should only apply to High and Medium cyber systems. Applicability to Low systems would potentially place a large burden as current Low Impact requirements do not require entities to conduct an inventory of equipment and software or identify systems.

 

BPA requests that the SDT provide clarification as to how R1 would apply to TCAs.

 

1.2.1 - Is notification under 1.2.1 for what is known at the time of procurement or does it persist after the procurement is fulfilled? What is the time limit? BPA proposes that the language be made consistent with the R1 rationale: “obtaining specific controls in the negotiated contract may not be feasible and is not considered failure to implement an entity's plan.”

 

1.2.2 through 1.2.6 – BPA believes this expands the scope of CIP-004 R5. BPA requests clarification on what this applies to: does it apply to the vendor or to the hardware/software?

 

The SDT should address gaps that apply to other standards within that standard and not group them into CIP-013-1. For the sub-parts of CIP-013 R1, the scope might be more appropriate in the following locations:

  • The topic of access control CIP-013 R1, P1.2.2 is addressed in CIP-004 R5, P5.1

  • Vulnerability assessments CIP-013 R1, P1.2.3 is addressed in CIP-010 R3, P3.1

  • Cyber security response CIP-013 R1, P1.2.4 is addressed in CIP-008 R1, P1.1

  • Software security patches CIP-013 R1, P1.2.5 is addressed in CIP-007 R2, P2.1-2.4; BPA suggests revision to address all patches.

  • Interactive Remote Access CIP-013 R1, P1.2.6 is addressed in CIP-005 R2, P2.1.

Aaron Cavanaugh, On Behalf of: Bonneville Power Administration, WECC, Segments 1, 3, 5, 6

- 0 - 0

Requirement R1 requires a documented ‘supply chain risk management plan’, AZPS requests clarification and renaming of the plan to ‘vendor risk management plan’ throughout the Standard as this term more appropriately describes the content that is required to be included in the plan.  Also, the statement …’the plan(s) shall address:’ seems redundant and potentially creates a distinction that is not intended.  AZPS recommends striking the last sentence and appending …’including’ to the first sentence of Requirement R1.  Finally, AZPS recommends revising the language of Requirement R1 to focus on BES Cyber Systems and to allow the plan content to address when the associated “Electronic Access Control or Monitoring Systems, Physical Access Control Systems, and Protected Cyber Assets” are brought into the scope of such plans as follows:

R1. Each Responsible Entity shall implement one or more documented Vendor risk management plan(s) that address controls for mitigating cyber security risks to BES Cyber Systems, including: [Violation Risk Factor: Medium] [Time Horizon: Operations Planning]

1.1. The use of controls in BES Cyber System planning and development to:

1.1.1. Identify and assess risk(s) during the procurement and deployment of vendor products and services; and

1.1.2. Evaluate methods to address identified risk(s).

1.2. The use of controls in procuring vendor product(s) or service(s) that address the following items, to the extent each item applies to the Responsible Entity's BES Cyber Systems:

1.2.1. Process(es) for notification of vendor security events;

1.2.2. Process(es) for notification when vendor employee remote or onsite access should no longer be granted;

1.2.3. Process(es) for disclosure of known vulnerabilities;

1.2.4. Coordination of response to vendor-related cyber security incidents;

1.2.5. Process(es) for verifying software integrity and authenticity of all software and patches that are intended for use;

1.2.6. Coordination of remote access controls for (i) vendor-initiated Interactive Remote Access and (ii) system-to-system remote access with a vendor(s); and

1.2.7. Other process(es) to address risk(s) as determined in Part 1.1.2, if applicable.

1.3. The applicability of controls to associated Electronic Access Control or Monitoring Systems, Physical Access Control Systems, and Protected Cyber Assets.

AZPS also requests that two (2) definitions utilized in the Technical Guidance and Examples be proposed for inclusion as defined terms in the standard, “Security Events” and “Vendor.”  Specifically, AZPS notes that Requirement R1.2.1 uses the term “security events” as an undefined term in the Standard, but that the Technical Guidance and Examples, Page 6, uses “Security Events” as a defined term.  AZPS requests consistency between the two documents and the addition of the defined term “Security Events” to the Standard.  Additionally, AZPS requests the removal of ‘identified, threatened, attempted’ from the defined term and require only notification of ‘successful breach of vendor’s components, software or systems that have potential adverse impacts to the availability or reliability of BES Cyber Systems’.  Further, the Rationale for Requirement R1 defines the term “vendors” as ‘(i) developers or manufacturers of information systems, system components, or information system services; (ii) product resellers; or (iii) system integrators’,   AZPS requests incorporating this definition in the Standard for specificity of scope.

AZPS requests clarification regarding the term “processes” as used in Requirement R1.2.  In particular, AZPS requests clarification that these items or “processes” are to be included in the overall plan and do not require a separate process or process documentation.    Finally, the Rationale for Requirement R1 states that “obtaining specific controls in the negotiated contract may not be feasible and is not considered failure to implement the Entity’s plan;” however the Requirement does not make clear that the failure of contract negotiations to result in specific controls would not be considered a failure to implement.  

Stephanie Little, 3/6/2017

- 0 - 0

1)      The Rational for Requirement R1 includes a definition of the term “vendors”.  This definition is also included in the Guidelines and Examples document.  This term should be officially defined in the standard or added to the NERC Glossary of Terms and capitalized when used.

2)      For R1: This requirement requires both the development and the implementation of a plan.    We recommend modifying this requirement into three steps which follows the CIP-014 structure – Entity to 1) identify risk, 2) develop a plan, 3) develop an implementation timeline. The timeline should use fixed dates or intervals and not dates that are linked to the completion of other compliance activities  

3)      The standard as written addresses Vendor Risk Management and no other supply chain risks such as sole source and international dependencies.  Suggest changing the name, purpose, and other areas of the standard from supply chain” to “vendor”.

4)      For R1.1.2:

a.      We recommend changing evaluate to Determine. We also seek further clarification of the intent. As, written the requirement is ambiguous:

                                                              i.      Is the intent to have the entity evaluate potential methods to mitigate risk? or;

                                                             ii.      to evaluate the effectiveness of mitigating that risk? or;

                                                           iii.      is it meant to identify what controls you have to mitigate the risks you have?

b.      The evaluation of methods is a administrative task and similar to other tasks removed from the NERC standards as part of the Paragraph 81 project.

5)      For R1.2.1:  The words “Security Event” are in quotes the first time that they are used in the Guidelines and Examples document (page 6).  If the Guidelines and Examples document is providing a definition to be applied here, then this should be an officially defined term either in the standard or in the NERC glossary.  The s definition provided in the glossary is “any identified, threatened, attempted or successful breach of vendor’s components, software or systems” and “that have potential adverse impacts to the availability or reliability of BES Cyber Systems” It is unclear if the second portion is meant to be part of the definition.  Many cyber systems, like firewalls, are under constant threat and attempts to breach the systems security.  Suggest replacing “vendor security event” with “identification of a new security vulnerability”.  Vendors may not be able to determine if a vulnerability “could have potential adverse impact to the availability or reliability of BES Cyber System”.  This clause would only be applicable in determining when an entity would notify a vendor.

6)      For R1.2.1: Page 6, line 12 of the Guidance and Examples document list both notification of security events from the vendor and notifications from the entity.  The R1.2.1 language is unclear in requiring both types of notifications. 

7)      For R1.2.1: The requirement for the” process for notification” is very different than the “request vendor cooperation” guidance given on page 6, line 22 of the guidance document. 

8)      Page 6, line 12 of the guidance details the notification of the vendor by the entity. It is unclear that the R1.2.1 requires notification by the entity to the vendor as detail in the guidance document. 

9)      Recommend that “Security Event” be changed to require the reporting of only newly identified security vulnerabilities.

10)  Change 1.2.7 from pointing to 1.1.2 to 1.1.1.  Remove 1.2 since 1.2.7 covers 1.2.

11)  Do not agree with the current draft language that includes all High, Medium and Low BES Cyber Systems in Requirement R1. Suggests limiting this requirement to High and Medium only as the current Low Impact requirements do not require entities to conduct an inventory of equipment and software or identify systems. As written, this requirement will place additional administrative burden on entities and the impacts are not fully understood. If controls are needed for low impact, suggest moving these to R5 to consolidate all low impact into a single requirement.

12)  The Standard drafting team needs to verify that the SDT needs to make sure that there is no duplication in the standards.  Provide guidance on how areas that seem to overlap like Interactive Remote Access and CIP-005.

13)  Request the SDT to consider adding the following language from the rationale to the language of the standard “Implementation of the cyber security risk management plan(s) does not require the Responsible Entity to renegotiate or abrogate existing contracts.” 

14)  The Rationale for R1, it states that R1, P1.1 addresses P 56 of Order No. 829.  P 56 calls for a risk assessment of the entities internal systems with this language “how a responsible entity will include security considerations as part of its information system planning and system development lifecycle processes”. R1, P1.1.1 calls for a risk assessment of the vendors systems with this language “procurement and deployment of vendor products and services.”  The language in the order does not match the language in the standard and therefore suggest that the language be consistent to provide clarity.

15)  There could be an impact of contract requirements on the ability of public utilities to piggyback on wide-area contracts such as those of National Association of State Procurement Officials (NASPO) Cooperative, Western States Contracting Alliance (WSCA), Washington State Department of Enterprise Service, and others. Recommend that an exclusion be permitted in the case of such contracts, which are important to provide flexibility, effectiveness, and negotiating strength for public utilities throughout the country.  In some cases such contracts are required; also include language that provides an exclusion for contracts that are covered by other laws or regulations.

16)  The measure should not reference the word mitigation, which to an auditor may limit the actions an entity might take to address risk (such as avoid or transfer).  Suggest that “mitigate” be replace with “address” as listed in R1.2.

Nathan Mitchell, On Behalf of: Nathan Mitchell, , Segments 3, 4

- 1 - 0

CPS Energy supports the comments provided by ERCOT and APPA

Glenn Pressler, CPS Energy, 3, 3/6/2017

- 0 - 0

The FERC order applied to industrial control systems.  The SDT is applying the standard to all BES Cyber Assets or systems.  It is our belief that all BES Cyber systems are not industrial control systems.  The SDT should apply the requirements to industrial control systems such as DCS or EMS systems located in power plants and control rooms.

Louis Guidry, 3/6/2017

- 0 - 0

PSEG agrees with the intent of this requirement, but has the following questions/recommendations below:

  • The term vendors as used in the standards is defined in the Rationale for Requirement R1 box. This term should be officially defined in the Glossary of Terms used in NERC Reliability Standards.

     

  • Is requirement R1 applicable to new additions and/or modifications to existing BES Cyber Systems?  There is not sufficient information to determine if this requirement is applicable only to new BES Cyber Systems or if it also includes changes to existing BES Cyber Systems.

 

  • The applicability of Requirement R1 to High/Medium/Low BES Cyber systems and EACMs, PACs and PCAs is not clear the way it is written. Recommend using the applicability tables as in CIP-004 through CIP-011 for the requirements in this standard, especially R1.

 

  • Requirements 1.2.1 through 1.2.6 discuss processes for vendor controls but some of the controls are unclear as to who is expected to perform the “notification”. For each sub-requirement, PSEG recommends adding clarity in the requirement language indicating who is expected to perform the notification, the vendor or the registered entity.

     

  • Requirement 1.2.1 discusses a vendor security event. This is a vague term. The standard should include more clarification on what a vendor security event is or define the term.

PSEG REs, Segment(s) 5, 6, 3, 1, 3/6/2017

- 1 - 0

Colorado Springs Utilities (CSU) has been engaging in dialogue with peers of trade associations such as Large Public Power Corporation to address the CIP-013 standard development activities.  We continue to be a strong supporter of efforts that ensure the security of the bulk electric system.  We appreciate the great strides that the SDT has made in the development of this standard to address the elements of the FERC Order while balancing reasonable responsibilities as required by the electric industry in support of the security objectives.        

 

CSU does not agree with including all BES Cyber Systems in Requirement R1.  Using a risk-based approach, CSU requests limiting this requirement to high and medium only.  As the current low impact requirements do not require entities to conduct an inventory of equipment and software or identify systems, CSU believes this requirement will place substantial additional administrative burden on entities with low impact assets.  If a risk management plan is to be required low, with a reduced set of requirements to address their lower risk, CSU requests that those requirements be included as an element of R5 so all the low impact requirements are together or, ideally, included in CIP-003 along with the content of R5.

 

CSU requests that the SDT add the following language from the rationale to the language of the standard: “Implementation of the cyber security risk management plan(s) does not require the Responsible Entity to renegotiate or abrogate existing contracts.”  

 

CSU is concerned about compliance obligations for procurement activities associated with multi-party wide-area contracts such as national, regional, state & city negotiated contracts.  Examples include contracts from the National Association of State Procurement Officials (NASPO) Cooperative and the Western States Contracting Alliance. An exception, comparable to a CIP Exceptional Circumstance, should be included in the standard for these kinds of procurement activities because they provide important negotiating strength, flexibility, and effectiveness in contracting (see CS's Uresponse to Question #9 for additional information on exceptions).

 

CSU notes that the Rationale for R1 includes a definition of the term “vendors”.  This definition is also included in the Technical Guidance and Examples document.  This term should be officially added to the NERC Glossary of Terms and capitalized when used.

 

For R1.1.2 CSU requests changing the word evaluate to determine.

 

For R1.2.1 CSU requests that the words Security Event and the definition from the Technical Guidance and Examples document be placed in the NERC Glossary of Terms and capitalized when used.

 

For R1.2.1 CSU requests that the SDT provide clarification on the language in the guidance document related to 1.2.1.  The document references the “process for notification” which is very different than the “request vendor cooperation” language.  The requirement as written would require that a process be defined and implemented.  CSU requests additional language in the requirement that addresses “entities are not required to validate a vendor is adhering to its processes and a failure of a vendor to follow a defined process is not a violation of this Requirement.”

 

In Measure M1, CSU requests that the language be changed to be consistent with the Requirement. Specifically, change “Evidence shall include (i) one or more documented supply chain cyber security risk management plan(s) that address controls for MITIGATING cyber security risks as specified in the Requirement…” to “Evidence shall include (i) one or more documented supply chain cyber security risk management plan(s) that address controls for ADDRESSING cyber security risks as specified in the Requirement…” (BOLD emphasis added). The construction “address risk” conforms with the text of the Requirement and acknowledges that risk might be avoided or transferred, for example, as opposed to mitigated. 

 

CSU requests that the title of the standard be changed to “Vendor Risk Management” to clarify that the scope of the required activities relate to the relationships among a utility and its vendors. In common usage, the term “supply chain risk management” encompasses a much broader scope of concerns, including quality control and verification of third-party suppliers as well as addressing sole-source and international dependencies. Although the FERC Order and SDT white paper cite concerns about both vendor risk and supply chain risk, the requirements actually proposed in CIP-013 address vendor risk. A change of title is a simple means to clarify what is intended in R1.1, in particular, and helps identify auditable actions throughout R1. 

 

Colorado Springs Utilities, Segment(s) 5, 3, 1, 6, 5/6/2015

- 0 - 0

The Rationale for R1 states, “Implementation of elements contained in the entity’s plan related to Party 1.2 is accomplished through the entities procurement and negotiation process.” The SDT need to define the process for determining the minimum level deemed to be sufficient. Additionally, the SDT needs to identify the course of action an entity must take and document where a vendor is unwilling or unable to meet the obligations set forth for Responsible Entities.

 

R1. In FERC Order No. 829, paragraph 59 states, “The new or modified Reliability Standard must address the provision and verification of relevant security concepts in future contracts for industrial control system hardware, software, and computing and networking services associated with bulk electric system operations.” The Order does not address requirements for EACMS, PACS, or PCA as identified in R1. The SDT should limit the requirement to the context of the Order. 

 

R1.1.1. The obligation to “identify and assess risks” is extremely open-ended and ambiguous.  In contrast, the draft Technical Guidance and Examples document enumerates a list of 11 factors that should be considered in an entity’s plan.  NERC standards should be clear on their face, and it is inappropriate to require and entity to refer to draft Technical Guidance and Examples document for fundamental questions concerning whether an entity is compliant with a given requirement.   If the Drafting Team believes that this list of 11 factors within the draft Technical Guidance and Examples document is a comprehensive list of factors that should be considered when “identifying and assessing risks,” these factors should be listed in the standard as the exhaustive set of factors to be assessed.  If the Drafting Team does not believe this list is complete or appropriate, an alternate list of factors should be provided.  Without clear requirements on the factors to be considered, there is substantial risk in inconsistency of implementation by entities.

 

R1.1.1. The use of the term “deployment” can be read to require an ongoing obligation even after the software or hardware is in production. To avoid confusion, the term “deployment” should be removed.

Leonard Kula, Independent Electricity System Operator, 2, 3/6/2017

- 0 - 0

The attached document has comments compiled for all the questions.  Please note that the BOLD paragraphs below  (YELLOW highlighted in attachment) are uniquely Seattle City Lights.  The un-highlighted comments were developed in collaboration with other entities and trade organizations such as LPPC.  These comments may be like those submitted by other entities but not necessarily.  City Light recognizes the challenges facing the SDT and appreciates the efforts the SDT is placing into working towards developing a solid standard. 

Seattle City Light has been engaging in dialogue with peers of trade associations such as Large Public Power Corporation to address the CIP-013 standard development activities.  We continue to be a strong supporter of efforts that ensure the security of the bulk electric system.  We appreciate the great strides that the SDT has made in the development of this standard to address the elements of the FERC Order while balancing reasonable responsibilities as required by the electric industry in support of the security objectives.        

Seattle City Light does not agree with including all BES Cyber Systems in Requirement R1.  Using a risk-based approach, Seattle City Light requests limiting this requirement to high and medium only.  As the current low impact requirements do not require entities to conduct an inventory of equipment and software or identify systems, Seattle City Light believes this requirement will place substantial additional administrative burden on entities with low impact assets.  If a risk management plan is to be required low, with a reduced set of requirements to address their lower risk, Seattle City Light requests that those requirements be included as an element of R5 so all the low impact requirements are together or, ideally, included in CIP-003 along with the content of R5.

Seattle City Light requests that the SDT add the following language from the rationale to the language of the standard: “Implementation of the cyber security risk management plan(s) does not require the Responsible Entity to renegotiate or abrogate existing contracts.”  

Seattle City Light is concerned about compliance obligations for procurement activities associated with multi-party wide-area contracts such as national, regional, state & city negotiated contracts.  Examples include contracts from the National Association of State Procurement Officials (NASPO) Cooperative and the Western States Contracting Alliance. In some cases use of these contracts in procurement is mandated by other laws or regulations. An exception, comparable to a CIP Exceptional Circumstance, should be included in the standard for these kinds of procurement activities because they provide important negotiating strength, flexibility, and effectiveness in contracting (see Seattle City Light’s response to Question #9 for additional information on exceptions).

Seattle City Light notes that the Rationale for R1 includes a definition of the term “vendors”.  This definition is also included in the Technical Guidance and Examples document.  This term should be officially added to the NERC Glossary of Terms and capitalized when used.

For R1.1.2 Seattle City Light requests changing the word evaluate to determine.

For R1.2.1 Seattle City Light requests that the words Security Event and the definition from the Technical Guidance and Examples document be placed in the NERC Glossary of Terms and capitalized when used.

For R1.2.1 Seattle City Light requests that the SDT provide clarification on the language in the guidance document related to 1.2.1.  The document references the “process for notification” which is very different than the “request vendor cooperation” language.  The requirement as written would require that a process be defined and implemented.  Seattle City Light requests additional language in the requirement that addresses “entities are not required to validate a vendor is adhering to its processes and a failure of a vendor to follow a defined process is not a violation of this Requirement.”

In Measure M1, Seattle City Light requests that the language be changed to be consistent with the Requirement. Specifically, change “Evidence shall include (i) one or more documented supply chain cyber security risk management plan(s) that address controls for MITIGATING cyber security risks as specified in the Requirement…” to “Evidence shall include (i) one or more documented supply chain cyber security risk management plan(s) that address controls for ADDRESSING cyber security risks as specified in the Requirement…” (BOLD emphasis added). The construction “address risk” conforms with the text of the Requirement and acknowledges that risk might be avoided or transferred, for example, as alternatives to being mitigated. 

Seattle City Light requests that the title of the standard be changed to “Vendor Risk Management” to clarify that the scope of the required activities relate to the relationships among a utility and its vendors. In common usage, the term “supply chain risk management” encompasses a much broader scope of concerns, including quality control and verification of third-party suppliers as well as addressing sole-source and international dependencies. Although the FERC Order and SDT white paper cite concerns about both vendor risk and supply chain risk, the requirements actually proposed in CIP-013 address vendor risk. A change of title is a simple means to clarify what is intended in R1.1, in particular, and helps identify auditable actions throughout R1. 

Seattle City Light Ballot Body, Segment(s) 1, 4, 6, 5, 3, 12/2/2016

CIP-013 Comment Mar 2 revision SCL 2017-3-6.docx

- 0 - 0

FEUS supports the comments submitted by APPA

Linda Jacobson-Quinn, City of Farmington, 3, 3/6/2017

- 0 - 0

FMPA agrees with comments submitted by American Public Power Association.

FMPA, Segment(s) , 12/5/2016

- 0 - 0

It is unclear how the risk and requirements in R5 for Low Impact BES Cyber Systems are differentiated from the other requirements and how the requirements will be measured considering a list of Low Impact systems are not required. There seems to be some reduncancy between R1 and R5 for Low Impact. Suggest removing Low Impact requirements from CIP-013 and incorporating into CIP-003 for consitency.

Jay Barnett, 3/6/2017

- 0 - 0

Ambiguity in R1 

FERC Order No. 829 asks for a plan to be developed and implemented by the entity that includes security controls for supply chain management for industrial control system hardware, software, and services associated with bulk electric system operations. It recognizes the diversity of BES Cyber System environments, technologies and risks among entities.  FERC states that the “Reliability Standard may allow a responsible entity to meet the security objectives discussed below by having a plan to apply different controls based on the criticality of different assets.”  

We find that the use of word “address” in R1 is creating ambiguity.

We suggest that requirement should be clear in stating that entities are to identify supply chain cyber security risks, evaluate controls and select controls, and implement controls based on their acceptable risk levels for future procurement contracts.

In doing so, entities should consider, at minimum, the controls that are itemized in the FERC Order and evaluate whether implementation of those controls are appropriate based on risk.

The four objectives that R1 should address are not clear 

FERC Order states the “following four specific security objectives in the context of addressing supply chain management risks: (1) software integrity and authenticity; (2) vendor remote access; (3) information system planning; and (4) vendor risk management and procurement controls. Responsible entities should be required to achieve these four objectives but have the flexibility as to how to reach the objective (i.e., the Reliability Standard should set goals (the “what”), while allowing flexibility in how a responsible entity subject to the Reliability Standard achieves that goal (the “how”)).”

The required plan is not tied to the objectives stated in the FERC Order.    

1.      For Information System Planning, FERC Order appears to ask that the responsible entity must include security considerations as part of its information system planning and system development lifecycle.  The information system planning and development lifecycle should be periodically reviewed and approved by CIP Senior Manager.

We believe that R1.1 is intended to address the Information System Planning objective in the FERC Order.  Consideration of security risks in Information System Planning is the objective of the overall plan.

R1.1 causes ambiguity.  It is not clear how controls can be used to identify and assess risk.  Controls are used to mitigate risk.   Evaluation of controls is performed prior to their selection depending on the acceptable level of risk and cost associated with the controls.   The verbiage of Part 1.1.2 requires controls for the evaluation of methods to address risks.  It does not require risks to actually be determined. 

2.      R1.2 lists a number of controls (some specifically stated in the FERC Order) and does not identify which objective these controls are to address.

                      a.      For Software Integrity and Authenticity objective, FERC Order appears to ask that at minimum, entities should consider                                implementing the following controls to mitigate risk by:

1.      Verifying the identity of the software publisher for all software and patches that are intended for use on BES Cyber Systems; and

2.      Verifying the integrity of the software and patches before they are installed in the BES Cyber System environment. (R1.2.5)

           The Standard appears to address this objective in Requirement 3.   There is overlap/redundancy between                  R1.2.5 and Requirement 3.

b.      For Vendor Remote Access to BES Cyber Systems, FERC Order appears to ask that at minimum, entities should consider implementing controls to mitigate risk by Logging and controlling all third-party (i.e., vendor) initiated remote access sessions including user-initiated and machine-to-machine vendor remote access.  (R1.2.6)

The Standard appears to address this objective in Requirement 4.   There is overlap/ redundancy between R1.2.6 and Requirement 4.

 

c.       For Vendor Risk Management and Procurement Controls, FERC Order appears to ask that at minimum, entities’ controls should consider implementing controls to mitigate by means of:

1.      Vendor security event notification processes;  (R1.2.1)

2.      Vendor personnel termination notification for employees with access to remote and onsite systems; (R1.2.2)

3.      Product/services vulnerability disclosures, such as accounts that are able to bypass authentication or the presence of hardcoded passwords; (R1.2.3)

4.      Coordinated incident response activities; and (R1.2.4)

5.      Other related aspects of procurement. (R1.2.7)

Related to R1.2.1, It is not clear what constitutes a “vendor security event”.   Every vendor may have a different consideration for what constitutes a “security event”.  It could include an instance of employee fraud, workplace assault, or even the announcement of a patch release.

Related to R1.2.4, Cyber Security Incident is a NERC defined term.  Is a cyber security incident a Cyber Security Incident? If not, what is the distinction? If it is, the term will need to be capitalized.  Also the term “vendor related cyber security incident” is not clear.  Is it a Cyber Security Incident that could happen during procurement and deployment stage? 

We also find R1.2.7 is unnecessary and creates ambiguity.

Applicability 

FERC Order suggests that entities can perform their own assessment of risks and determine applicability of controls based on that.

It is not clear how the described controls are applicable to BES Cyber Systems based on their risk level in the context of CIP Standards (Low, Medium, and High).  

The Standard extends applicability to the EACMS, PACS, and PCAs associated to BES Cyber Systems.  We argue that PACS, EACMS and PCAs, although are important for Physical and Electronic Security, are not necessarily “industrial control system hardware, software, and computing and networking services associated with bulk electric system operations” as stated in the FERC Order. 

This standard should not be applied to systems or assets not needed for BES operations.

Payam Farahbakhsh, Hydro One Networks, Inc., 1, 3/6/2017

- 0 - 0

The NYPA Comments

Erick Barrios, 3/6/2017

- 0 - 0

 

Sacramento Municipal Utility District (SMUD) has been engaging in dialogue with peers of trade associations such as Large Public Power Council to address the CIP-013 standard development activities.  We continue to be a strong supporter of efforts that ensure the security of the bulk electric system.  We appreciate the great strides that the SDT has made in the development of this standard to address the elements of the FERC Order while balancing reasonable responsibilities as required by the electric industry in support of the security objectives.        

 

 

 

SMUD does not agree with including all BES Cyber Systems in Requirement R1.  SMUD supports a risk-based approach, while limiting this requirement to high and medium only.  As the current low impact requirements do not require entities to conduct an inventory of equipment and software or identify systems, SMUD believes this requirement will place substantial additional administrative burden on entities with low impact assets.  If a risk management plan is to be required low, with a reduced set of requirements to address their lower risk, SMUD requests that those requirements be included as an element of R5 so all the low impact requirements are together or, ideally, included in CIP-003 along with the content of R5.

 

 

 

SMUD requests that the SDT add the following language from the rationale to the language of the standard: “Implementation of the cyber security risk management plan(s) does not require the Responsible Entity to renegotiate or abrogate existing contracts.”  

 

 

 

SMUD is concerned about compliance obligations for procurement activities associated with multi-party wide-area contracts such as state & city negotiated contracts.  An exception, comparable to a CIP Exceptional Circumstance, should be included in the standard for these kinds of procurement activities (see SMUD’s response to Question #9 for additional information on exceptions).

 

 

 

SMUD notes that the Rationale for R1 includes a definition of the term “vendors”.  This definition is also included in the Technical Guidance and Examples document.  This term should be officially added to the NERC Glossary of Terms and capitalized when used.

 

 

 

For R1.1.2 SMUD requests changing the word evaluate to determine.

 

 

 

For R1.2.1 SMUD requests that the words Security Event and the definition from the Technical Guidance and Examples document be placed in the NERC Glossary of Terms and capitalized when used.

 

 

 

For R1.2.1 SMUD requests that the SDT provide clarification on the language in the guidance document related to 1.2.1.  The document references the “process for notification” which is very different than the “request vendor cooperation” language.  The requirement as written would require that a process be defined and implemented.  SMUD requests additional language in the requirement that addresses “entities are not required to validate a vendor is adhering to its processes and a failure of a vendor to follow a defined process is not a violation of this Requirement.”

 

 

 

2. The SDT developed CIP-013-1 Requirement R2 to address the Order No. 829 directive for entities to periodically reassess selected controls and keep plans up to date with emerging cyber security supply chain risk management concerns and vulnerabilities (P 46). Do you agree with the proposed requirement? If you do not agree, or if you agree but have comments or suggestions for the proposed requirement provide your recommendation and explanation.

 

 

 

 

- 0 - 0

Requirement Placement (CIP-013 versus CIP-003)

R1 (and R2) includes low, medium, and high BES Cyber Systems; however, the current CIP Standards put the low impact BES Cyber Systems (LIBCS) requirements in CIP-003.  EEI recommends that the SDT consider whether to move the LIBCS requirements from CIP-013 into CIP-003. Moving the LIBCS to CIP-003 may make it easier for Responsible Entities with only LIBCS to implement the requirements.

However, Responsible Entities with high, medium, and low impact BES Cyber Systems (HIBCS, MIBCS, and LIBCS) may be concerned that moving the supply chain LIBCS requirements to CIP-003 may make it difficult for them to take a holistic approach to the CIP-013 requirements. For example, some entities may want to focus on their BES Cyber System vendors and apply a single vendor-based approach for HIBCS, MIBCS, and LIBCS. Also, CIP-013 is focused on the risk that vendors and suppliers may introduce into BES Cyber Systems, whereas the other CIP Standards are focused on more general cybersecurity risks that can be addressed by Responsible Entity operational controls, which are within the control of the Responsible Entity. Third-party risk is harder for Responsible Entities to control and the methods of control are more likely contractual than operational. For example, a Responsible Entity cannot control a vendor’s manufacturing process, but can ask questions during procurement as to how security risk is managed by the vendor to help evaluate the level of risk the vendor may pose to the Responsible Entity. As a result, there may be value in keeping these requirements out of the other CIP Standards, which focus on operational controls for cybersecurity risk.

Applicable Systems

Requirement R1 applies to LIBCS as well as HIBCS and MIBCS and their associated EACMS, PACS, and PCAs. We do not believe that EACMS, PACS, and PCAs should be included under the scope of Requirement R1. The diversity and sheer number of these systems make it difficult to document how Responsible Entities will address procurement for all of these systems in their risk management plans. Auditing these plans will also be difficult.

Some products and services may pose greater risk than others depending on many factors including risk introduced by the vendor, risk introduced by the vendor’s product/service, or how the Responsible Entity deploys the vendor product or service. As a result, the requirement’s objective should be to get Responsible Entities to evaluate vendor cybersecurity practices during procurement and develop methods to mitigate potential risks, whether that is choosing another vendor, implementing an operational control, or accepting the risk. CIP-013 cannot address all risk introduced by vendors and their products and services. Vendors have a responsibility to reduce risk in their manufacturing processes and Responsible Entities have a responsibility to reduce risk in their operations. The existing CIP standards already address Responsible Entity operational risk.

We are also concerned that by specifying the applicable systems in Requirement R1 that the requirement may be interpreted that every device in a system must be addressed by these plans. We recommend that the SDT consider either narrowing the scope of the requirement language or making it more flexible to allow Responsible Entities to define which systems need to be addressed by the plans based on the risk. For example, using “industrial control systems associated with BES Cyber Systems” may narrow the scope to more critical systems; however, industrial control systems would need to be defined by the SDT as interpretations may vary.

Security Objective

The security objective of Requirement R1 is unclear. Although it focuses on the Commission objectives 3 and 4, it would be helpful to make it clear in the requirement language so that Responsible Entities understand the purpose of the requirement.

Objective 3 is focused on making sure that Responsible Entities do not unintentionally plan to procure or fail to anticipate security issues during procurement or technology/vendor transitions. Objective 4 is focused on ensuring security concepts are addressed in future contracts. Both of these objectives are focused on evaluation of the risk that the vendor or vendor product/service may introduce to the BCS by the Responsible Entity during planning for and actual procurement of new systems. The controls that are required under Requirement R1 are also not operational controls, but process controls to assess and evaluate the risk.

Risk Acceptance

We understand that Order No. 706 ordered the ERO to remove acceptance of risk language from the CIP Reliability Standards. In this case, it was tied to a concern over uncontrolled compliance exceptions to addressing potential vulnerabilities and the Commission preferred the use of technical feasibility, which led to technical feasibility exceptions. (See Order No. 706, P 150-151) We are not recommending the use of “acceptance of risk” in CIP-013, but we want to make it clear that risk acceptance may be a good option in dealing with procurement controls (CIP-013, Requirement R1), which are different than the operational controls covered by the other CIP Standards.

The security objective for Requirement 1 is focused on Responsible Entity awareness of risk that may be introduced by the vendor or vendor product/service. The Responsible Entity’s ability to control this risk is limited. For example, the Responsible Entity may only have a few vendors to choose from for a particular procurement and the vendors may not have a well-defined process for vendor security event notification. The Responsible Entity can ask them to define a process and can even put language into a contract to require such a contract, but the vendors can say no. The Responsible Entity is left with the choice of either not procuring this device or system or accepting the risk. Documenting a compliance exception for every term the vendor does not agree to does not seem reasonable in light of the scope of Requirement R1 – the sheer numbers of systems covered (HIBCS, MIBCS, and LIBCS) and diversity of vendors for each of these systems and system components. Responsible Entities also cannot make the vendor develop or follow this process even if the vendor agrees to, which is also a consideration for the SDT – if the vendor does not comply with their contract terms is the Responsible Entity subject to a violation and penalty?

We recommend that the SDT consider, set, and articulate compliance expectations with Requirements R1 and R2 and recognize the difference between these procurement controls and the operational controls found in the rest of the CIP Standards.

Measure M1

We are concerned with the M1 language use of “written agreements” as a measure of plan implementation, even though it is introduced with “could include, but is not limited to.” Requirement R1 does not (and should not) require Responsible Entities to use contract terms to meet the security objective. However, contract terms may be one method of “how” to meet the security objective (“what”), but not all entities will choose this “how”. We are concerned that the inclusion of “written agreements” in the measure text suggests that this is a key piece of evidence for compliance with R1. Also, the use of “correspondence” in M1 could include “written agreements” if an entity chooses to use them for R1. We recommend removing “written agreements in electronic or hard copy format” from M1.

We recommend the following language for consideration by the SDT:

R1.  Each Responsible Entity shall implement one or more documented supply chain risk management plan(s) to minimize the cyber security risks from vendors and vendor products and services to BES Cyber Systems during planning and procurement of industrial control systems. The plan(s) should address one or more methods to:

1.1.       Raise awareness of risk the vendor and vendor product or service may introduce, including awareness of vendor process(es) to:

1.1.1.     Notify the Responsible Entity of vendor security events;

1.1.2.     Notify the Responsible Entity of when vendor employee remote or onsite access should no longer be granted;

1.1.3.     Disclose known vulnerabilities to the Responsible Entity;

1.1.4.     Coordinate the response to vendor-related cyber security incidents with the Responsible Entity;

1.1.5.     Verify the software integrity and authenticity of vendor software and patches; and

1.1.6.     Control remote access, including vendor-initiated interactive remote access and system-to-system remote access to the Responsible Entity

1.2.       Assess risk(s) introduced by the vendor and vendor product or service identified by Part 1.1; and

1.3.       Evaluate method(s) to address risk(s) identified by Part 1.2.

Melanie Seader, On Behalf of: Edison Electric Institute, NA - Not Applicable, Segments NA - Not Applicable

- 1 - 0

Tacoma concurs with the comments provided by the LPPC.

Marc Donaldson, Tacoma Public Utilities (Tacoma, WA), 3, 3/6/2017

- 0 - 0

- 0 - 0

   SDG&E agrees with EEI comments and proposed language.  Particularly R1 should only focus on supply chain risk management during the procurement phase rather than controls during operations.  Operational controls on BES systems should be covered in other CIP standards. Furthermore, if controls are to be required on a vendor’s manufacturing process, in addition to those identified during RFP negotiations, these controls should be consistent and verifiable by an industry standard (similar to ISO(?) 9001 certification).   

Jeff Johnson, On Behalf of: Sempra - San Diego Gas and Electric, WECC, Segments 1, 2, 3, 4, 5, 6, 7

- 0 - 0

LCRA does not agree with including all BES Cyber Systems in Requirement R1.  Using a risk-based approach, LCRA requests limiting this requirement to high and medium only.  As the current low impact requirements do not require entities to conduct an inventory of equipment and software or identify systems, LCRA believes this requirement will place substantial additional administrative burden on entities with low impact assets.  If a risk management plan is to be required low, with a reduced set of requirements to address their lower risk, LCRA requests that those requirements be included as an element of R5 so all the low impact requirements are together or, ideally, included in CIP-003 along with the content of R5.

- 0 - 0

Many of the aspects of CIP-013-1 R1 cannot be controlled by the entity, but instead need to have assurances from the vendor. In other CIP standards there are operational controls that the entity can make to meet the requirements of the standards; these controls are things the entity can control.

 

The scope of R1 includes BCAs, EACMS PACS and PCAs with no guidance concerning the risk associated with each of these types of assets. Some products and services may pose greater risk than others depending on many factors including risk introduced by the vendor, risk introduced by the vendor’s product/service, or how the Responsible Entity deploys the vendor product or service. As a result, the requirement’s objective should be to get Responsible Entities to evaluate vendor cybersecurity practices during procurement and develop methods to mitigate potential risks, whether that is choosing another vendor, implementing an operational control, or accepting the risk. CIP-013 cannot address all risk introduced by vendors and their products and services. Vendors have a responsibility to reduce risk in their manufacturing processes and Responsible Entities have a responsibility to reduce risk in their operations. The existing CIP standards already address Responsible Entity operational risk.

 

We are also concerned that by specifying the applicable systems in Requirement R1 that the requirement may be interpreted that every device in a system must be addressed by these plans. We recommend that the SDT consider either narrowing the scope of the requirement language or making it more flexible to allow Responsible Entities to define which systems need to be addressed by the plans based on the risk. For example, using “industrial control systems associated with BES Cyber Systems” may narrow the scope to more critical systems; however, industrial control systems would need to be defined by the SDT as interpretations may vary.

William Wenz, On Behalf of: AES - Dayton Power and Light Co., RF, Segments NA - Not Applicable

- 0 - 0

The IRC and SWG thanks the Drafting Team for their work and support the concepts in the security program enhancements addressing supply chain risks. 

The Rationale for R1 states, “Implementation of elements contained in the entity’s plan related to Party 1.2 is accomplished through the entities procurement and negotiation process.” The SDT need to define the process for determining the minimum level deemed to be sufficient. Additionally, the SDT needs to identify the course of action an entity must take and document where a vendor is unwilling or unable to meet the obligations set forth for Responsible Entities.

R1. In FERC Order No. 829, paragraph 59 states, “The new or modified Reliability Standard must address the provision and verification of relevant security concepts in future contracts for industrial control system hardware, software, and computing and networking services associated with bulk electric system operations.” The Order does not address requirements for EACMS, PACS, or PCA as identified in R1. The SDT should limit the requirement to the context of the Order. 

R1.1.1. The obligation to “identify and assess risks” is extremely open-ended and ambiguous.  In contrast, the draft Technical Guidance and Examples document enumerates a list of 11 factors that should be considered in an entity’s plan.  NERC standards should be clear on their face, and it is inappropriate to require and entity to refer to draft Technical Guidance and Examples document for fundamental questions concerning whether an entity is compliant with a given requirement.   If the Drafting Team believes that this list of 11 factors within the draft Technical Guidance and Examples document is a comprehensive list of factors that should be considered when “identifying and assessing risks,” these factors should be listed in the standard as the exhaustive set of factors to be assessed.  If the Drafting Team does not believe this list is complete or appropriate, an alternate list of factors should be provided.  Without clear requirements on the factors to be considered, there is substantial risk in inconsistency of implementation by entities.

R1.1.1. The use of the term “deployment” can be read to require an ongoing obligation even after the software or hardware is in production. To avoid confusion, the term “deployment” should be removed.

IRC-SRC, Segment(s) 2, 11/18/2016

- 0 - 0

Many of the aspects of CIP-013-1 R1 cannot be controlled by the entity, but instead need to have assurances from the vendor. In other CIP standards there are operational controls that the entity can make to meet the requirements of the standards; these controls are things the entity can control.

 

The scope of R1 includes BCAs, EACMS PACS and PCAs with no guidance concerning the risk associated with each of these types of assets. Some products and services may pose greater risk than others depending on many factors including risk introduced by the vendor, risk introduced by the vendor’s product/service, or how the Responsible Entity deploys the vendor product or service. As a result, the requirement’s objective should be to get Responsible Entities to evaluate vendor cybersecurity practices during procurement and develop methods to mitigate potential risks, whether that is choosing another vendor, implementing an operational control, or accepting the risk. CIP-013 cannot address all risk introduced by vendors and their products and services. Vendors have a responsibility to reduce risk in their manufacturing processes and Responsible Entities have a responsibility to reduce risk in their operations. The existing CIP standards already address Responsible Entity operational risk.

 

We are also concerned that by specifying the applicable systems in Requirement R1 that the requirement may be interpreted that every device in a system must be addressed by these plans. We recommend that the SDT consider either narrowing the scope of the requirement language or making it more flexible to allow Responsible Entities to define which systems need to be addressed by the plans based on the risk. For example, using “industrial control systems associated with BES Cyber Systems” may narrow the scope to more critical systems; however, industrial control systems would need to be defined by the SDT as interpretations may vary.

William Wenz, On Behalf of: AES - Dayton Power and Light Co., RF, Segments NA - Not Applicable

- 0 - 0

Q1-Issue1-Discussion

(1) In reviewing the measures M1, R1 is written in a manner to collect evidence to achieve two objectives; (i) documentation of the plan, and (ii) documentation to demonstrate implementation of the plan(s).  According to NERC’s Drafting Team Reference Manual which was recently revised and published October 19, 2016, on page 11 under section B – Requirements and Measures (http://www.nerc.com/pa/Stand/Resources/Documents/Drafting%20Team%20Reference%20Manual_Oct2016_final.pdf), each requirement should “achieve one objective.”  The Reference Manual goes on to state:  If a requirement achieves two objectives, such as developing a document and distributing that document, then each objective should be addressed in its own requirement.  Contrary to instructions delineated in the Reference Manual, R1 requires Entities meet two objectives, develop and implement the supply chain risk management plan.

 

Q1-Issue1-Recommendation

GTC recommends R1 be separated into two separate requirements where the first objective of the FERC directive identified in paragraph 2 is addressed to “develop a plan” (R1), and the second objective is addressed in its own requirement to “implement the plan” (new R2).  This method simplifies compliance documentation for the Responsible Entity and aligns with the principles documented in NERC’s Reference Manual.  Additionally, this method will simplify and provide clarity to achieve FERCs directive for the plan to be forward-looking as explained in further detail below.

 

Q1-Issue2-DISCUSSION

(2)  The SDT has clarified in the rationale for requirement R1 that the implementation of the cyber security risk management plans(s) does not require the Responsible Entity to renegotiate or abrogate existing contracts, consistent with Order No. 829 as specified in the Implementation Plan.  Additionally, Paragraph 59 stipulates to address security concepts in “future contracts”.  However, GTC does not see this forward looking language in the actual Requirement R1 that is specified by the FERC Order.  GTC believes this forward looking language can be better clarified and highlighted if the SDT accepts GTC’s first recommendation to separate R1 into two requirements and “implement the plan” is written as its own requirement. 

 

Q1-Issue2-Recommendation

GTC recommends the following:

Separate R# to implement plan(s), then update the new Requirement with the following language:  “Each Responsible Entity shall implement the documented supply chain risk management plan(s) specified in Requirement R1.   Implementation of the cyber security risk management plan(s) does not require the Responsible Entity to renegotiate or abrogate existing contracts.”

 

 

Q1-Issue3-DISCUSSION

(3) Paragraph 45 of Order No. 829, clearly specifies “The Plan” should address, at a minimum, four specific security objectives in the context of addressing supply chain management risks.  

 

(P. 45) The plan required by the new or modified Reliability Standard developed by NERC should address, at a minimum, the following four specific security objectives in the context of addressing supply chain management risks: (1) software integrity and authenticity; (2) vendor remote access; (3) information system planning; and (4) vendor risk management and procurement controls.

 

Although R1 technically covers the four specific security objectives, the presentation lends itself somewhat confusing.   R1.2.5 seems to align with security objective (1), R1.2.6 seems to align with security objective (2), and are both subsets to R1.2 which seems to align with security objective (4).   

 

Q1-Issue3-Recommendation

GTC believes R1 will be clearer to understand and that the drafting team could gain more support if the four specific security objectives required by Order 829 Paragraph 45 had their own individual sub-requirement of “The Plan”, in lieu of sub-requirements of one of the security objectives such as:

R1.1 aligns with security objective 3 (information system planning) where the specifics of the third objective identified in paragraph 56 is captured as a subset of R1.1;

 

R1.2 aligns with security objective 4 (vendor risk management and procurement controls) where the specifics of the fourth objective identified in paragraph 59 is captured as a subset of R1.2;

 

R1.3 to align with security objective 1 (software integrity and authenticity) where the specifics of the first objective identified in paragraph 48 is captured as a subset of R1.3; and

 

R1.4 to align with security objective 2 (vendor remote access) where the specifics of the second objective identified in paragraph 51 is captured as a subset of R1.4.

 

Q1-Issue4-DISCUSSION

 

(4) Order 829 Paragraph 58 refers to NIST Special Publication 800-53 for various supply chain development life cycle controls.  The definition of Supply Chain from NIST SP 800-53 r4 states that the “supply chain horizon" ends at the delivery of products/services to the acquirer.  FERC Order 829 acknowledges this definition in paragraph 32, footnote 61.

 

Supply Chain: “Linked set of resources and processes between multiple tiers of developers that begins with the sourcing of products and services and extends through the design, development, manufacturing, processing, handling, and delivery of products and services to the acquirer”

 

Accordingly, in the system lifecycle, the supply chain management process occurs prior to the identification of a Cyber Asset as a BES Cyber System pursuant to the implementation of CIP-002-5.1a.  This designation must only occur “upon commissioning” for planned system installations (and even later for unplanned changes).  Therefore, BES Cyber System identification, categorization as high, medium, or low impact; and also identifying associated EACMS, PACS, and PCAs does not exist during the supply chain context.  Therefore, R1 should be limited to a supply chain risk management plan which will address controls for mitigating Supply Chain risks to hardware, software, and computing and networking services of Cyber Assets which are intended to support Bulk Electric System operations as specified in Order 829 paragraph 43.

 

Q1-Issue4-Recommendation

 

GTC recommends the SDT adopt the aforementioned NIST SP 800-53 defined term Supply Chain for use with CIP-013-1 R1 in front of the term “risks” to contain the Time Horizon to supply chain risk management, and also edit to account for the fact that BES Cyber System identification and categorizations do not exist during the supply chain context.

 

An example of R1 is provided:

R1. Each Responsible Entity shall document a Supply Chain risk management plan(s) that address controls for mitigating Supply Chain risks to hardware, software, and computing and networking services which are intended to support Bulk Electric System operations.  The plan(s) shall address:

R1.1 The use of controls for mitigating Supply Chain risks associated with information system planning

R1.2 The use of controls for mitigating Supply Chain risks associated with vendor risk management and procurement controls

R1.3 The use of controls for mitigating Supply Chain risks associated with software integrity and authenticity

R1.4 The use of controls for mitigating Supply Chain risks associated with vendor remote access

 

Q1-Issue5-DISCUSSION

GTC disagrees with the inclusion of associated Electronic Access Control or Monitoring Systems, Physical Access Control Systems, and Protected Cyber Assets in requirement R1.  GTC finds no reference to the inclusion of these associated systems in FERC Order 829 and recommends their removal from this standard. 

 

Further, GTC questions whether the use of the term BES Cyber Systems is appropriate in a standard which is limited per FERC Order 829 to “the context of addressing supply chain management risks.”  In the system lifecycle, the supply chain management process occurs prior to the identification of a Cyber Asset as a BES Cyber System pursuant to the implementation of CIP-002-5.1a.  This designation must only occur “upon commissioning” for planned system installations (and even later for unplanned changes).  Therefore, BES Cyber System identification, categorization as high, medium, or low impact; and also identifying associated EACMS, PACS, and PCAs does not exist during the supply chain context.

 

Q1-Issue5-Recommendation

GTC recommends the removal of any reference to Electronic Access Control or Monitoring Systems, Physical Access Control Systems, and Protected Cyber Assets.  GTC recommends removal of references to BES Cyber Systems and replacing it with the phrase “hardware, software, and computing and networking services which are intended to support Bulk Electric System operations.”

Jason Snodgrass, 3/6/2017

- 0 - 0

R1.1 is acceptable in regard to requiring entities to have a plan to identify and assess risks with procured equipment.  R1.2 is unacceptable because Entity creation of Detective Controls for the four Objectives of P. 45 is considered out of the Entity's scope.  If only one Entity and one Vendor existed, the individual sub-parts of R1.2 may be feasible for control planning – but this approach is not viable for hundreds of entities and dozens of vendors.  The Entity is capable of identifying Preventative Controls, in concept, but they will only be effective if all the vendors in the supply chain make a diligent effort to implement the controls all the way back to the first-line suppliers.  Corrective Action Controls are critical, but would be able to be implemented only after a problem is identified.

Bob Case, On Behalf of: Black Hills Corporation, WECC, Segments 1, 3, 5, 6

- 0 - 0

Refer to CSU comments.

Devin Elverdi, 3/6/2017

- 0 - 0

See comments submitted by Black Hills Corporation

Maryanne Darling-Reich, 3/6/2017

- 0 - 0

The requirement should focus on the risk of the software or services being procured and not allow for the possibility of a Registered Entity taking a risk view based upon the impact categorization of the BES Cyber System or EACMS, PACS, or PCA that is affected by the procurement.  The requirement needs to clearly be focused on the vendor processes without regard to the Cyber Assets impacted by the vendor.  The controls need to include processes for granting vendor access in addition to the processes for notifying when removal of access is necessary.  The controls to grant access should include expectations for the conduct of training and personnel risk assessments, including review, modification as necessary, and acceptance of the vendor’s process by the Registered Entity, if applicable, along with expectations of what evidence of compliance will be provided to the Registered Entity by the vendor.  Part 1.2.4 should include an expectation of notification by the vendor in addition to coordination of the response.

Bob Reynolds, On Behalf of: Bob Reynolds, , Segments 10

- 0 - 0

Avista supports the comments filed by the Edison Electric Institute (EEI).

- 0 - 0

1)      The Rational for Requirement R1 includes a definition of the term “vendors”.  This definition is also included in the Guidelines and Examples document.  This term should be officially defined.

 

2)      It is not clear if R1 applies to high, medium and low since R3, R4 and R5 specify the impact level.  The high, medium, low impact level applicability would be much easier to understand if this standard were written to be consistent with CIP-004 through CIP-011 through the use of Applicability Tables.

 

3)      R1.1 is vague in the language used with terms like “assess risk” and “evaluate”.  The need to revise CIP-002 shows the difficulties that have occurred when entities are required to assess risk.  Request that the SDT encourage NERC to include in the CIP-013 RSAW, language similar to that used in the CIP-003-7(i) RSAW, Attachment 1 Section 4, possible Notes to Auditor:

 

“The entity must document its determination as to what are the supply chain risks. Once this determination has been made and documented, the audit team’s professional judgement cannot override the determination made by the Responsible Entity. “

 

For R1: With respect to the obligation to “identify and assess risks,” the standard is extremely open-ended.  In contrast, the Compliance Guidance enumerates a list of 11 factors that should be considered.  NERC standards should be clear on their face, and it should not be necessary to refer to Compliance Guidance for basic questions concerning whether an entity is in compliance with a given requirement.   If the Drafting Team believes that this list of 11 factors is a comprehensive list of factors that should be considered when “identifying and assessing risks,” these factors should be listed in the standard as the exhaustive set of factors to be assessed.  If the Drafting Team does not believe this list is complete or appropriate, a complete list of factors should be provided.  Without clear guidance, as to factors that should be considered, there is substantial compliance risk if a subjective auditor disagrees with the risk factors identified by an entity

 

R 1.1.1 – The use of the term “deployment” can be read to require an ongoing obligation even after the software or hardware is in production (i.e.  once deployed).  To avoid confusion, the term “deployment” should be removed or clarified.

 

4)      For R1: This requirement requires both the development and the implementation of a plan.    Recommend breaking this into three steps, which follows CIP-014 – Entity to a) identify risk, b) develop a plan, c) implement plan in future contracts.

 

5)      For R1: We recommend stating the responsible entity is not required to renegotiate or abrogate existing contracts. The rationale from R1 states that “Obtaining specific controls in the negotiated contract may not be feasible and is not considered failure to implement an entity's plan.” This should be incorporated into the Requirement itself.

 

6)      For R1.1 and the R1 Rationale:  The R1 Rationale and the Guidance document list “planning, acquisition and deployment” and versions of these terms in the diagram.  R1.1 uses “planning and development”.  The meaning of “development” has not been clarified and is not part of the process addressed by this standard.  Suggest that “development” be clarified or removed.

 

7)      For R1.1.2: We seek further clarification of the intent. As, written the requirement is ambiguous:

a.      Is the intent to have the entity evaluate potential methods to mitigate risk? or;

b.      To evaluate the effectiveness of mitigating that risk? or;

c.       Is it meant to identify the controls in place to mitigate the identified risks?

 

8)      For R1.2.1:  The words “Security Event” are in quotes the first time that they are used in the Guidelines and Examples document (page 6).  If the Guidelines and Examples document is providing a definition to be applied here, then” Security Event” should be replaced or clarified in the Requirement.  This clarification could include “any identified, threatened, attempted or successful breach of the vendor’s components, software or systems used in the support of the Entity’s BES Cyber System.” This new language differentiates R1.2.1 from the vulnerabilities in R1.2.3

 

9)      For R1.2.1: Page 6 of the Guidance and Examples document list both notification from the vendor and notifications from the entity.  The R1.2.1 language is unclear in requiring both notifications. Request an update to the Guidance and Examples or the Requirement, for consistency.

 

10)  For R1.2.2: The requirement for the” process for notification” is very different than the “request vendor cooperation” guidance given on page 6, line 22 of the guidance document the requirement as written would require that a process be defined and implemented.  The failure of a vendor to notify the entity would, at a minimum be a violation of the entities process or maybe even a compliance violation as a failure to implement the process.  Would like to see an additional statement in the requirement language that “A failure of a vendor to follow a defined process is not a violation of this Requirement.”

 

For R1.2: A newly added (in the 1/19/17 draft) sentence in the Rationale (R1) section states: “Implementation of elements contained in the entity’s plan related to Part 1.2 is accomplished through the entities procurement and negotiation process. Who determines whether it was a sufficient effort to “implement the elements” as part of the procurement and negotiation process? What if you take their first “no” for an answer – is that sufficient effort to implement? Who gets the final sign off?

 

11)  Request clarification - May a responsible entity's procurement plan identify and mitigate risks without requiring vendor involvement for each identified risk?

 

The Compliance Guidance states: “Implementation of the cyber security risk management plan(s) does not require the Responsible Entity to renegotiate or abrogate existing contracts, consistent with Order No. 829 (P 36) as specified in the Implementation Plan.”  What qualifies as an existing contract?  Is there an obligation to implement the risk management plan when: (1) negotiating and executing a new Statement of Work; (2) negotiating an amendment to a Master Agreement; or (3) renewing a contract under existing terms?  The answer to these questions should be clarified and directly addressed in the standard.

 

Requirements overlap with existing CIP standards and create double jeopardy situations. Change 1.2.7 from pointing to 1.1.2 to 1.1.1

The following statements from the R1 Rationale box are important caveats for compliance and should be included in the Requirement text:

“Implementation of the cyber security risk management plan(s) does not require the Responsible Entity to renegotiate or abrogate existing contracts.”

“Obtaining specific controls in the negotiated contract may not be feasible and is not considered failure to implement an entity's plan.”

RSC no Dominion and NextEra, Segment(s) 1, 0, 2, 4, 5, 6, 7, 3, 3/6/2017

- 0 - 0

  • What is meant by “if applicable” in the Requirement. If this means EACMS/PACS/PCAs for high and medium impact BES Cyber Systems, then state this.

  • Extending the applicability to all BES Cyber Systems and associated EACMS/PACS/PCAs results in an unfathomable expansion in scope. For example, in a small Medium Impact Control Center BES Cyber System, we have between 50 and 60 individual software and hardware contracts to manage. Most common industry practices would base the procurement policies for these contracts based on their financial risk, or contracts above a certain spending threshold. However, managing cyber risk does not relate to spending. A million-dollar EMS system could carry less cyber security risk than a $20 camera or a one thousand-dollar network switch. This implies a centralized procurement office for all purchases, since each potential purchase needs to be evaluated for the Cyber Security risk it presents. This would have tremendous costs for smaller entities. We suggest limiting the scope to high and medium impact BES Cyber Systems.

  • 1.2.3 should read “known [security] vulnerabilities”. Vulnerabilities include any weakness in the code.

  • What does coordination mean in 1.2.4 and 1.2.6?

  • Remove 1.2.7. This does not belong in a mandatory and enforceable Standard. As it stands, an entity is required to add other indeterminate processes.

Philip Huff, On Behalf of: Philip Huff, , Segments 3, 4, 5, 6

- 0 - 0

See Black Hills Corp comments

George Tatar, 3/6/2017

- 0 - 0

 R1.1 is acceptable in regard to entities having a plan to identify and assess risks with procured equipment.  R1.2 is unacceptable because the entity creation of Detective Controls for the four Objectives of P. 45 is considered out of the Entity's scope.  If only one Entity and one Vendor existed, the individual sub-parts of R1.2 would be feasible for a control plan – but this approach is not viable for hundreds of Entities and dozens of vendors.  The Entity is capable of identifying Preventative Controls, in concept, but they will only be effective if the vendors in the supply chain make a diligent effort to implement the controls to the first-line suppliers.  Corrective Action Controls are critical, but would be able to be implemented only after a problem is identified. Corrective Action Controls are critical, but would be able to be implemented only after a problem is identified.

Wes Wingen, 3/6/2017

- 0 - 0

We generally agree with EEI’s comments, except for the exclusion of EACMS, PACs and PCAs for Requirement 1.

Jamie Monette, Allete - Minnesota Power, Inc., 1, 3/6/2017

- 0 - 0

FERC didn’t specifically ask for Low Impact BES Cyber Systems to be included but didn’t explicitly exclude them either. SunPower does not believe Low Impact Cyber Systems should have to meet the same expectations of High and Medium Impact Cyber Systems. While we appreciate the efforts of the SDT to meet the expectations of the FERC Order, we believe the SDT may have gone beyond what FERC was asking them to do.

CIP-003-6 does not require Entities with Low Impact Cyber Systems to have to list the BES Cyber Systems, with this new requirement, do Entities lose their exception? If there is an expectation of that Low Impact Cyber System Entities must adhere to the same or lesser requirements as High and Medium Impact Cyber System Entities, then perhaps CIP-003 would be a better place for the exception. SunPower believes CIP-013, as written, is in direct conflict with the intent of CIP-003-6.

Bradley Collard, 3/6/2017

- 0 - 0

Kansas City Power and Light Company incorporates by reference Edison Electric Institute’s comments to Question 1. In addition, we offer the following comments:

Remove Identify, Assess, and Control Found at the Requirement Level

We suggest deletion of these words and terms.  The use of identify, assess, and control (IAC) is represented by the responsible entity’s governance and control structure.  This is an evaluation performed by the Regional Entity in evaluation of the responsible entity’s inherent risk and oversight model.

Douglas Webb, 3/6/2017

- 0 - 0

Oxy disagrees that R1 should be applicable to low impact BES Cyber Systems.  Although FERC is silent on whether low impact should be included, Paragraph 2 of Order No. 829 says “nor does the Commission require NERC to propose “one-size-fits-all” requirements.  The new or modified Reliability Standard should instead require responsible entities to develop a plan to meet the four objectives, or some equally efficient and effective means to meet these objectives, while providing flexibility to responsible entities as to how to meet those objectives.”  The language of R1 elevates low impact BES Cyber Systems to the level of medium and high impact BES Cyber Systems.  For example, R 1.2.2 requires a process for when vendor employee remote or onsite access should no longer be granted.  Under existing CIP Standards, Access Management Program requirements reside in CIP-004 and none are applicable to low impact BES Cyber Systems.  R 1.2.5 requires processes for verifying software integrity and authenticity of all software and patches that are intended for use.  Under existing CIP Standards, Security Patch Management requirements reside in CIP-007 and none are applicable to low impact BES Cyber Systems.  Additionally, software and patching typically occurs at the Cyber Asset level and low impact entities are only required to identify assets containing low impact BES Cyber Systems.  As currently written, R1 and its sub-requirements seem to require an inventory of Cyber Assets or BES Cyber Systems, neither of which are required of low impact entities, which is another element that elevates low’s to that of medium and high.  Using a risk based approach, it seems more appropriate that R1 be applicable to medium impact and high impact only.  The risk assessments are required and performed under CIP-002 and the determination made that low impact BES Cyber Systems pose a minimal threat to the BES.  Finally, under the existing CIP suite of standards, requirements applicable to low impact entities reside in CIP-003.  If a risk management plan is to be required, low impact with a reduced set of requirements to address their minimal BES risk, Oxy requests that those requirements be included as an element of R5 so all the low impact requirements are together or, ideally, included in CIP-003 along with the content of R5. Oxy also requests that CIP-013-1, R1 be rewritten to be applicable to medium and high impact BES Cyber Systems only.

Oxy, Segment(s) 7, 5, 9/6/2016

- 0 - 0

  • Regarding R1.2.1, vendors will unlikely to share security events. Registered Entities should not be held accountable for compliance obligations in which they have no control of.

  • Regarding R1.2.1, the Standard Drafting Team should clarify what is intended by, “vendor security event.” This is an ambiguous term which can have different meanings.

  • Regarding R1.2.3, the Standard Drafting Team should clarify what is intended by, “known vulnerabilities.” This is an ambiguous term which can have different meanings.

  • Regarding R1.2.4, the Standard Drafting Team should clarify what is intended by, “cyber security incidents.” This is an ambiguous term which can have different meanings.

  • Regarding R1.2.4, vendors will be unlikely to share cyber security incidents. Registered Entities should not be held accountable for compliance obligations in which they have no control of.

  • Regarding R1.2.5, this requirement is duplicative of CIP-007-6. The Standard Drafting Team should clarify how proposed requirement would be completed within the Procurement phase.

  • Regarding R1.2.6, this Requirement is duplicative of CIP-005-5.

.

Heather Morgan, EDP Renewables North America LLC, 5, 3/6/2017

- 0 - 0

The scope of the requirement is not clear due to the phrase "if applicable." Please clarify how an entity would determine if their Electronic Access Control or Monitoring Systems, Physical Access Control Systems, and Protected Cyber Assets are applicable.

Due to some vendors offering many of their products and services outside of the electric utility industry (Microsoft, Cisco, Symantec, GE…) there is a concern that entities will lack leverage when negotiating these new terms and will likely find it difficult to come to an agreement. There are also instances where there are very few options available to industry for a particular product, device, or service. Does the SDT envision that registered entities would be forced to find alternative vendors or products if they are unable to come to an agreement?

It is not clear if the requirements are only applicable to new software purchases or also apply to upgrades of existing software (including adding additional licenses for existing software) or renewals of software maintenance contracts that provide software upgrades of existing software.  If the existing software is already in place, there is concern that there will be the lack of leverage to require vendors of existing software to negotiate new terms.

Sergio Banuelos, On Behalf of: Tri-State G and T Association, Inc., MRO, WECC, Segments 1, 3, 5

- 0 - 0

Concur with EEI’s Position

Linsey Ray , 3/6/2017

- 0 - 0

SVP agrees with other entity comments to limit this requirement to High and Medium only, as current low impact requirements does not require entities to conduct an inventory of equipment and software or identify systems.  Pleas also see APPA's comments, with which SVP is in agreement.

Val Ridad, On Behalf of: Silicon Valley Power, WECC, Segments 1

- 0 - 0

The need for such a broad set of requirements is unnecessary due to the existing CIP requirements for the entity to have an incident response plan, anti-virus protection and patch management.  To the extent the following items remain in R1, NRECA proposes the following actions:

 

R1.2 – Recommend deleting text after “BES Cyber Systems” as the text is unnecessary.

R1.1.1 – Clarify what is meant by “vendor security events.”

R1.2.3 – What is the basis for determining what are “known vulnerabilities?”

R1.2.4 – Clarify the scope of this language as it seems unnecessarily open-ended.

R1.2.5 – Clarify that this item is for BES Cyber Systems only.

R1.2.7 – Delete as it is unclear and unnecessarily open-ended.

Barry Lawson, 3/6/2017

- 0 - 0

Scott Downey, 3/6/2017

- 0 - 0

EPE shares the comments and concerns voiced by the Edison Electric Institute (EEI) in this Ballot #1.  Please refer to the EEI ballot for detailed comments on each of the proposed requirements; however, EPE would like to emphasis one issue that is at the forefront of its concerns:

The proposed language of the requirements (especially Requirement 1.2) speaks in terms of using controls that “address process(es),” and yet, the contents of the requirements include “verifying software integrity.”  Responsible Entities are familiar with various existing CIP requirements that mandate the development of “processes,” but in CIP-013-1, the inclusion of responsibility for verifying software integrity places a Responsible Entity in a conundrum not present in the other Reliability Standards.  Must a Responsible Entity start hiring employees with software capabilities equal or better than the software developers on the staff of the vendors who have historically supplied software products to the industry?  If so, how long will that take and at what cost to ratepayers, and can a third party effectively or efficiently create a pool of talent superior to the actual developers of the vendor’s software itself? 

Perhaps there is room in the standard for a Responsible Entity to simply require in its processes that any vendor will provide an attestation to the Responsible Entity that the vendor’s software product is authentic and has integrity for the intended use, making this type of attestation a means of complying with the verification requirements found throughout CIP-013-1 in its proposed form.  If so, the current wording of the draft standard does not plainly or clearly say so. 

EPE understands the objective of the standard, and the Commission’s desire to tackle the risks that stem from third party vendors whose work may impact the BES.  Our participation in the balloting process for this standard is with the goal of arriving at language that is clear and that enables a Responsible Entity to comply.

Luis Rodriguez, El Paso Electric Company, 6, 3/6/2017

- 0 - 0

EPE shares the comments and concerns voiced by the Edison Electric Institute (EEI) in this Ballot #1.  Please refer to the EEI ballot for detailed comments on each of the proposed requirements; however, EPE would like to emphasis one issue that is at the forefront of its concerns:

The proposed language of the requirements (especially Requirement 1.2) speaks in terms of using controls that “address process(es),” and yet, the contents of the requirements include “verifying software integrity.”  Responsible Entities are familiar with various existing CIP requirements that mandate the development of “processes,” but in CIP-013-1, the inclusion of responsibility for verifying software integrity places a Responsible Entity in a conundrum not present in the other Reliability Standards.  Must a Responsible Entity start hiring employees with software capabilities equal or better than the software developers on the staff of the vendors who have historically supplied software products to the industry?  If so, how long will that take and at what cost to ratepayers, and can a third party effectively or efficiently create a pool of talent superior to the actual developers of the vendor’s software itself? 

Perhaps there is room in the standard for a Responsible Entity to simply require in its processes that any vendor will provide an attestation to the Responsible Entity that the vendor’s software product is authentic and has integrity for the intended use, making this type of attestation a means of complying with the verification requirements found throughout CIP-013-1 in its proposed form.  If so, the current wording of the draft standard does not plainly or clearly say so. 

EPE understands the objective of the standard, and the Commission’s desire to tackle the risks that stem from third party vendors whose work may impact the BES.  Our participation in the balloting process for this standard is with the goal of arriving at language that is clear and that enables a Responsible Entity to comply.

Pablo Onate, El Paso Electric Company, 1, 3/6/2017

- 0 - 0

The applicability of this requirement should be limited to high and medium impact BES Cyber Systems.  Low impact Cyber Systems are categorized as low impact because they inherently have a low ability to negatively impact the Bulk Electric System. We should focus our resources on those systems that have the potential for significant adverse impact on the BES.  We can re-evaluate at a later date whether additional requirements should be established for low impact BES Cyber Systems.

Using “if applicable” adds confusion to the language.  If it is not always applicable to associated Electronic Access Control or Monitoring Systems, Physical Access Control Systems, and Protected Cyber Assets, define where it is applicable and where it is not. 

We’re concerned that the word “Evaluate” in requirement 1.1.2 might imply that all possible methods for addressing the risks will need to be evaluated.  We prefer replacing the term “Evaluate” with “Identify”.  Additionally, there may be occasion where a risk is identified but is judged to be at an acceptable level given the ability or inability to address it.  This standard, in its entirety, should be about minimizing the risks and/or providing reasonable assurance which may result in some instances where the entity will accept a certain level of risk as reasonable.  Therefore, we propose the following language: 1.1.2. Identify methods to address the above risk(s), as needed.

Requirement 1.2.1 requires “Process(es) for notification of vendor security events”. CIP-007-6 R4 Security Event Monitoring includes a requirement for generating alerts for security events.  Assuming that Requirement R1.2.1. is intended to mean the entity will have a process to encourage and direct vendor notification to the client, we suggest this be included in the language of CIP-007.   

Requirement 1.2.2 requires “Process(es) for notification when vendor employee remote or onsite access should no longer be granted” The revocation of access, including Interactive Remote Access is currently addressed in CIP-004-6 R5. If this is attempting to require something above and beyond those requirements, it should be made clear what that is and consideration given to housing all of these requirements in CIP-004.

Requirement 1.2.3 requires “Process(es) for disclosure of known vulnerabilities”.  Is this asking for entities to have a process for the entity to disclose vulnerabilities?  Who would we be disclosing to?  If it’s directed at vendors, the entity can discuss this with the vendor, but the vendor is under no obligation to disclose vulnerabilities and neither the entity, nor FERC, has the authority to require this.  Vendors MAY disclose vulnerabilities, but that will likely occur concurrent with providing a fix/patch.

Requirement 1.2.4 requires a “Coordination of response to vendor-related cyber security incidents”. From our understanding of what this requires, we believe this is already covered in the entities cyber security incident response plan (CIP-008).

Requirement 1.2.7 requires “Other process(es) to address risk(s) as determined in Part 1.1.2, if applicable”. While we understand what this requirement is intending to do, we believe it is may lead to second-guessing by auditors and/or unrealistic auditor expectations.

Luminant, Segment(s) 6, 7, 5, 1/24/2017

- 1 - 0

EPE shares the comments and concerns voiced by the Edison Electric Institute (EEI) in this Ballot #1.  Please refer to the EEI ballot for detailed comments on each of the proposed requirements; however, EPE would like to emphasis one issue that is at the forefront of its concerns:

The proposed language of the requirements (especially Requirement 1.2) speaks in terms of using controls that “address process(es),” and yet, the contents of the requirements include “verifying software integrity.”  Responsible Entities are familiar with various existing CIP requirements that mandate the development of “processes,” but in CIP-013-1, the inclusion of responsibility for verifying software integrity places a Responsible Entity in a conundrum not present in the other Reliability Standards.  Must a Responsible Entity start hiring employees with software capabilities equal or better than the software developers on the staff of the vendors who have historically supplied software products to the industry?  If so, how long will that take and at what cost to ratepayers, and can a third party effectively or efficiently create a pool of talent superior to the actual developers of the vendor’s software itself? 

Perhaps there is room in the standard for a Responsible Entity to simply require in its processes that any vendor will provide an attestation to the Responsible Entity that the vendor’s software product is authentic and has integrity for the intended use, making this type of attestation a means of complying with the verification requirements found throughout CIP-013-1 in its proposed form.  If so, the current wording of the draft standard does not plainly or clearly say so. 

EPE understands the objective of the standard, and the Commission’s desire to tackle the risks that stem from third party vendors whose work may impact the BES.  Our participation in the balloting process for this standard is with the goal of arriving at language that is clear and that enables a Responsible Entity to comply.

Victor Garzon, 3/6/2017

- 0 - 0

Scott Kinney, Avista - Avista Corporation, 3, 3/6/2017

- 0 - 0

ERCOT supports the IRC comments and offers the following supplemental comments.

 

FERC Order 829, Paragraph 59, states that NERC’s new or modified standard “must address the provision and verification of relevant security concepts in future contracts for industrial control system hardware, software, and computing and networking services associated with bulk electric system operations.”  This does not include the Electronic Access Control or Monitoring Systems (EACMS), Physical Access Control Systems (PACS), and Protected Cyber Assets (PCAs) listed in R1.  These systems do not perform or provide bulk electric system operations.  ERCOT believes the inclusion of these systems in the draft standard goes beyond the scope of the standard intended by FERC and recommends the SDT remove them from the applicable systems of the standard language.

 

Requirement R1 requires Responsible Entities to have a plan that addresses processes for notification of a vendor’s cyber security events (R1.2.1) and vulnerabilities (R1.2.3), as well as coordination of cyber security incident response activities (R1.2.4). As this information is highly sensitive, it is unlikely that all vendors will agree in all cases to provide this information unless they are already required to do so under other regulatory obligations. Responsible Entities cannot force a vendor to agree to these terms, and in cases where the vendor deems the risk of this disclosure too great compared to the value of the contract, the vendor will decline to enter into the agreement.  This will force the Responsible Entity to seek another vendor that is willing to accept these terms, and such a vendor may or may not exist.  Because it is possible that a Responsible Entity may be unable to identify a vendor that is willing to accept a contract with the terms required by R1, the proposed standard could seriously hamper the essential functions of Responsible Entities.  To address the concern, the drafting team should include a limited exemption from compliance, such as a Technical Feasibility Exception (TFE), which would protect Responsible Entities in the event a vendor is unwilling to agree to the terms otherwise required by R1.  NERC’s Appendix 4D to the Rules of Procedure provides for a basis of approval of a TFE beyond strict technical limitations of a system.  (See Section 3.0 of the appendix.)   

 

Requirement R1.2.2 requires “notification when vendor employee remote or onsite access should no longer be granted.” The revocation of access, including Interactive Remote Access, is currently addressed in CIP-004, R5. Since the background checks, training, access authorization, and access revocation for employees and vendors is already addressed in CIP-004, the drafting team should ensure any new requirements related to access revocation of vendors be placed in CIP-004. In developing the CIP Version 5 standards, extensive work was undertaken to ensure that all requirements related to the subject were included in one standard instead of being spread across multiple standards. The proposed language will disrupt that framework.

 

Requirement R1.2.5, which requires a Responsible Entity’s plan to include “Process(es) for verifying software integrity and authenticity of all software and patches that are intended for use,” is duplicative of Requirements R3 and R5 within this standard, which also require documentation of processes. ERCOT recommends removing R1.2.5.

 

Requirement R1.2.6 requires an entity’s plan to include “Coordination of remote access controls for (i) vendor-initiated Interactive Remote Access and (ii) system-to-system remote access with a vendor(s).”  This requirement is duplicative of Requirement 4 within this standard. ERCOT recommends removing Requirement R1.2.6, which also requires documentation of processes.

Elizabeth Axson, 3/6/2017

Final_Unofficial_Comment_Form_2016-03_03162017_ERCOT comments.docx

- 0 - 0

Hot Answers

- 0 - 0

Southern Company strongly encourages the SDT to consider the below edits to R2 to make it clear that assessment of risks and revisions to the plan are required on a “once every 15 months” interval, and not at the time of each and every notification of any new potential risks/vulnerability.  The below proposed modifications also clarify that revisions to the plan(s) are predicated on the existence of “new supply chain cyber security risks” by moving the phrase “if any.”  Subsequently, R2.2 has been modified to require CIP Senior Manager or delegate approval only when, following a required review every 15 months, it is determined revisions to the plan(s) are warranted to address “new supply chain cyber security risks” or “mitigation measures.”  As written in the draft Standard, an annual review and approval by the CIP Senior Manager or delegate where no revisions were warranted or made is a documentation exercise that provides no benefit to reliability or reduction of supply chain risk.  The SDT should also consider strengthening the language in the Rationale and/or Guidelines directing Entities to adequate and/or designated sources (NERC/DHS/E-ISAC/ICS-CERT) providing Supply Chain guidance for those higher level issues that warrant a change to your plan(s).  Also of note and for SDT consideration is the structure of the Implementation Plan for this Standard that does not require the CIP Senior Manager or delegate to review and approve the initial plan(s) on or before the effective date the plan(s) is required to be in place; therefore, review and approval of the plan(s) would be 15 months after the plan(s) was already in effect.

 

Modify R2 language as follows:

 

R2. Each Responsible Entity shall review its supply chain cyber security risk management plan(s) specified in Requirement R1 and update them, as necessary, at least once every 15 calendar months, which shall include:

2.1. Evaluation of revisions to address new supply chain cyber security risks and mitigation measures, if any, related to industrial control system vendor products and services applicable to the Responsible Entity’s BES Cyber Cyber Systems; and

2.2. Obtaining CIP Senior Manager or delegate approval for any revisions to the plan(s).

Southern Company, Segment(s) 1, 3, 5, 6, 8/3/2016

- 0 - 0

Other Answers

Dennis Minton, 1/19/2017

- 0 - 0

Dennis Minton, 1/19/2017

- 0 - 0

Dennis Minton, 1/19/2017

- 0 - 0

Dennis Minton, 1/19/2017

- 0 - 0

Tom Anthony, On Behalf of: Tom Anthony, , Segments 1, 3

- 0 - 0

Tom Anthony, On Behalf of: Tom Anthony, , Segments 1, 3

- 0 - 0

Glen Farmer, Avista - Avista Corporation, 5, 2/6/2017

- 0 - 0

Russel Mountjoy, 2/24/2017

- 0 - 0

The use of 15 calendar months allows entities to review and update (as required) on a systematic basis, the same time every year, Thank you.

MRO NSRF, Segment(s) 1, 2, 3, 4, 5, 6, 2/24/2017

- 1 - 0

The standard as written doesn’t clearly address the objectives as listed in its Requirements. It also creates confusion and possible double jeopardy with other CIP Standards.

faranak sarbaz, Los Angeles Department of Water and Power, 1, 2/27/2017

- 0 - 0

Richard Kinas, 2/28/2017

- 0 - 0

Donald Lock, 2/28/2017

- 0 - 0

See APPA's, TAP's, and USI's comments.

Marty Hostler, Northern California Power Agency, 4, 2/28/2017

- 1 - 0

R2 is applicable to all BES Cyber Systems and, as applicable, EACMS PACS and PCA.  The philosophy used by preceding CIP standard drafting teams has been to write any requirements for low impact BES Cyber Systems in Attachment 1 of CIP-003 R2.  AEP believes this is a practice that results in a greater potential for compliance of all Responsible Entities.  AEP recommends that the essence of R2 be rewritten to address the lower risk associated with low impact BES Cyber Systems and moved to CIP-003 R2 Attachment 1.  In addition, CIP-013-1 R2 should be be rewritten to be only applicable to high and medium impact BES Cyber Systems.

Thomas Foltz, AEP, 5, 3/2/2017

- 0 - 0

Proposed CIP-013-1, R2 properly implements Order No. 829’s directive to develop a Standard requiring entities to periodically review and approve the controls adopted to address specific security objectives associated with supply chain risk management. 

Rachel Coyne, Texas Reliability Entity, Inc., 10, 3/2/2017

- 0 - 0

Mike Smith, Manitoba Hydro , 3, 3/2/2017

- 0 - 0

Strike R2.1 because the R2 language includes “review and update as necessary” covers the FERC Order. Additional evaluation of the revisions is an administrative task that does not enhanced BES security.  Make corresponding changes to section M2.

Jesus Sammy Alcaraz, Imperial Irrigation District, 1, 3/2/2017

- 0 - 0

What is the target of the word “revisions” at the beginning of R2.1? Does revisions refer to modifications of the “supply chain cyber security risk management plan(s)” document itself? If so, then requirement is redundant in that R2, and consequently R2.1 could be interpreted to require entities to evaluate the revisions that were just completed.

Or is the intent of “revisions” to direct REs to consult document(s) external to the standard when executing revisions?

Tennessee Valley Authority, Segment(s) 1, 3, 5, 6, 9/1/2016

- 0 - 0

Eric Ruskamp, Lincoln Electric System, 6, 3/2/2017

- 0 - 0

Deborah VanDeventer, On Behalf of: Edison International - Southern California Edison Company, WECC, Segments 1, 3, 5, 6

- 0 - 0

Please refer to comments submitted by Deborah VanDeventer on behalf of Southern California Edison.

Romel Aquino, Edison International - Southern California Edison Company, 3, 3/2/2017

- 0 - 0

Duke Energy suggests the drafting team consider collapsing 2.1 and 2.2 into one sub-requirement. We do not see the need in having these as two sub-requirements, and this would mirror the language used in CIP-003-6.

Also, the use of the term “applicable” in R2.1, appears vague and could lead to potential disagreement on what supply chain security issues actually pose a substantial risk.

Duke Energy , Segment(s) 1, 5, 6, 4/10/2014

- 0 - 0

Anthony Jablonski, ReliabilityFirst , 10, 3/3/2017

- 0 - 0

R2 has no stated applicability and it is unclear whether the CIP Senior Manager approval required here is any different from the required approval under R5.  It would be clearer if R2 were made into R1.3, with the clarification suggested in our comments above to clearly exclude Low BES Cyber Assets from this requirement and consolidate requirements for those assets under R5.

PPL NERC Registered Affiliates, Segment(s) 3, 1, 5, 6, 2/9/2017

- 1 - 0

See NPCC comments.

ALAN ADAMSON, New York State Reliability Council, 10, 3/3/2017

- 0 - 0

Please refer to comments submitted by Deborah VanDeventer on behalf of Southern California Edison

Thomas Rafferty, 3/3/2017

- 0 - 0

AECI supports the following comment from AEP:

“R2 is applicable to all BES Cyber Systems and, as applicable, EACMS PACS and PCA.  The philosophy used by preceding CIP standard drafting teams has been to write any requirements for low impact BES Cyber Systems in Attachment 1 of CIP-003 R2.  AEP believes this is a practice that results in a greater potential for compliance of all Responsible Entities.  AEP recommends that the essence of R2 be rewritten to address the lower risk associated with low impact BES Cyber Systems and moved to CIP-003 R2 Attachment 1.  In addition, CIP-013-1 R2 should be rewritten to be only applicable to high and medium impact BES Cyber Systems.”

Mark Riley, Associated Electric Cooperative, Inc., 1, 3/3/2017

- 0 - 0

CHPD agrees that the plans in Requirement R1 need to be updated and a 15-month review period is appropriate.  However, CHPD  requests the removal of R2.1 and 2.2 and updating R2 to read:  Each Responsible Entity shall review its supply chain cyber security risk management plan(s) specified in R1 at least once every 15 calendar months, to include reviewing new risks and mitigation measures and identifying related changes, if any, and obtain CIP Senior Manager or delegate(s) approval.

Mick Neshem, 3/3/2017

- 0 - 0

PRPA agrees that the plans in Requirement R1 need to be updated and a 15-month review period is appropriate.  However, PRPA requests the removal of R2.1 and 2.2 and updating R2 to read:  Each Responsible Entity shall review its supply chain cyber security risk management plan(s) specified in R1 at least once every 15 calendar months, to include reviewing new risks and mitigation measures and identifying related changes, if any, and obtain CIP Senior Manager or delegate(s) approval.

Tyson Archie, Platte River Power Authority, 5, 3/3/2017

- 1 - 0

Please refer to comments submitted by Deborah VanDeventer on behalf of Southern California Edison.

Steven Mavis, 3/3/2017

- 0 - 0

AE agrees that the plans in Requirement R1 need to be updated and a 15-month review period is appropriate.  However, AE requests the removal of R2.1 and 2.2 and updating R2 to read:  Each Responsible Entity shall review its supply chain cyber security risk management plan(s) specified in R1 at least once every 15 calendar months, to include reviewing new risks and mitigation measures and identifying related changes, if any, and obtain CIP Senior Manager or delegate(s) approval.

Andrew Gallo, 3/3/2017

- 1 - 0

  1. Suggest deleting R2.1. The R2 language includes “review and update as necessary”. Additional evaluation of the revisions is an administrative task that does not enhanced BES security.  Make corresponding changes to section M2.

  2. For R2.2: Page 9 of the Guidance and Examples document states “Requirement R2 allows responsible entities to incorporate the review of CIP-013-1 into their annual CIP-003 review.”  CIP-003-6 R1 does not allow delegates to review and approve.  In addition, CIP-003 requires the review of Policies and not plans.

  3. Request clarity on how revisions to the plan would need to be addressed for contracts that are in the process of being negotiated since this negotiation process may take months.

Brian Evans-Mongeon, Utility Services, Inc., 4, 3/3/2017

- 0 - 0

CHPD agrees that the plans in Requirement R1 need to be updated and a 15-month review period is appropriate.  However, CHPD  requests the removal of R2.1 and 2.2 and updating R2 to read:  Each Responsible Entity shall review its supply chain cyber security risk management plan(s) specified in R1 at least once every 15 calendar months, to include reviewing new risks and mitigation measures and identifying related changes, if any, and obtain CIP Senior Manager or delegate(s) approval.

Janis Weddle, 3/3/2017

- 0 - 0

CHPD agrees that the plans in Requirement R1 need to be updated and a 15-month review period is appropriate.  However, CHPD  requests the removal of R2.1 and 2.2 and updating R2 to read:  Each Responsible Entity shall review its supply chain cyber security risk management plan(s) specified in R1 at least once every 15 calendar months, to include reviewing new risks and mitigation measures and identifying related changes, if any, and obtain CIP Senior Manager or delegate(s) approval.

Haley Sousa, 3/3/2017

- 0 - 0

Jeanie Doty, 3/3/2017

- 0 - 0

I support the comments of Andrew Gallo at Austin Energy.

W. Dwayne Preston, 3/3/2017

- 0 - 0

We agree with the LPPC/APPA comments.

JEA Voters, Segment(s) , 3/3/2017

- 0 - 0

While supporting this requirement, ACEC recommends that the requirement be modified to state it only applies to high and medium impact, consistent with requirements R3 and R4.     

Alan Farmer, On Behalf of: ACEC/Burns & McDonnell, NA - Not Applicable, Segments NA - Not Applicable

- 0 - 0

R2 contains the language “As necessary… at least once every 15 months…”  Is it an “as necessary” requirement or is it once per 15 months?  Recommend removing the “as necessary” language as it is too subjective and open to interpretation.

Michael Haff, On Behalf of: Seminole Electric Cooperative, Inc., FRCC, Segments 1, 3, 4, 5, 6

- 0 - 0

CHPD agrees that the plans in Requirement R1 need to be updated and a 15-month review period is appropriate.  However, CHPD  requests the removal of R2.1 and 2.2 and updating R2 to read:  Each Responsible Entity shall review its supply chain cyber security risk management plan(s) specified in R1 at least once every 15 calendar months, to include reviewing new risks and mitigation measures and identifying related changes, if any, and obtain CIP Senior Manager or delegate(s) approval.

 

3. The SDT developed CIP-013-1 Requirement R3 to address the Order No. 829 directive for entities to address verification of software integrity and authenticity in the BES Cyber System environment (P 48) as it applies to high and medium impact BES Cyber Systems. Do you agree with the proposed requirement? If you do not agree, or if you agree but have comments or suggestions for the proposed requirement provide your recommendation and explanation.

Chad Bowman, 3/3/2017

- 0 - 0

SRP agrees that the plans in Requirement R1 need to be updated and a 15-month review period is appropriate.  However, SRP requests the removal of R2.1 and 2.2 and updating R2 to read:  Each Responsible Entity shall review its supply chain cyber security risk management plan(s) specified in R1 at least once every 15 calendar months, to include reviewing new risks and mitigation measures and identifying related changes, if any, and obtain CIP Senior Manager or delegate(s) approval.

Lona Calderon, On Behalf of: Salt River Project, WECC, Segments 1, 3, 5, 6

- 0 - 0

Please refer to comments submitted by Deborah VanDeventer on behalf of Southern California Edison

Kenya Streeter, Edison International - Southern California Edison Company, 6, 3/3/2017

- 0 - 0

R2 is pretty straightforward, however unless modified by a subsequent implementation plan, WECC would expect an entity to have a reviewed and approved SCRM plan on or before the effective date, then complete R2 on intervals of no more than 15 calendar months. If an entity exceeds the 15 calendar month time frame, an R2 PNC would be indicated.

Steven Rueckert, Western Electricity Coordinating Council, 10, 3/3/2017

- 0 - 0

John Hagen, 3/3/2017

- 0 - 0

  • As previously stated, for consistency with other CIP Standards (e.g. Physical Security plans, Incident Response Plan, Recovery Plans, Information Protection program, etc..) , CIP-003 R1.1 should be expanded to include the Supply Chain Risk Management plan as part of the collective cyber security policies reviewed and approved by the CIP Sr. Manager at least every 15 months.  And, applicability of supply chain risk management controls to assets that contain Low Impact BCS should be consigned to CIP-003, R1.2 and R2. 

  • The NERC Glossary of Terms definition of CIP Senior Manager will require update to include CIP-013 

Aaron Ghodooshim, FirstEnergy - FirstEnergy Corporation, 3, 3/3/2017

- 0 - 0

Please refer to RSC- NPCC comments

Si Truc Phan, On Behalf of: Hydro-Qu?bec TransEnergie, NPCC, Segments 1

- 0 - 0

Support FirstEnergy Comments submitted by Aaron Ghodooshim – Segment 4). 

Aubrey Short, 3/3/2017

- 0 - 0

Basin Electric would prefer low impact requirements be included in CIP-003 rather than CIP-013.

 

The language of R2.1 appears redundant and not any different than what is already required in the language of the main requirement, R2.  Suggest deleting R2.1.

Mike Kraft, 3/3/2017

- 0 - 0

  1. Strike R2.1 because the R2 language includes “review and update as necessary” covers the FERC Order. Additional evaluation of the revisions is an administrative task that does not enhanced BES security.  Make corresponding changes to section M2.

 

  1. For R2.2: Page 9 of the Guidance and Examples document states “Requirement R2 allows responsible entities to incorporate the review of CIP-013-1 into their annual CIP-003 review.”  CIP-003-6 R1 does not allow delegates to review and approve.  In addition, CIP-003 requires the review of Policies and not plans.

     

Request clarity on how revisions to the plan would need to be addressed for contracts that are in the process of being negotiated since this negotiation process may take months.

SDT should clarify that existing contracts do not need to be renegotiated based on the 15 calendar month reassessment of the plan or other plan revisions.

An entity’s plan must be implemented at the commencement of negotiations. 

Will NERC, E-ISAC or other sources referenced in Rationale issue annual updates for supply chain risk? How will an entity prove that all risks have been incorporated? Seems to imply scope creep from elements on R1. Is necessity in R1 defined by entity, NERC, or outside source?

Con Edison, Segment(s) 1, 3, 5, 6, 0, 6/24/2016

- 0 - 0

Seminole Electric comments submitted by Michael Haff

Michael Ward, 3/3/2017

- 0 - 0

OSI Open Systems International, On Behalf of: OSI Open Systems International, NA - Not Applicable, Segments NA - Not Applicable

- 0 - 0

See comments on Requirement R2 in attached file.

William Harris, 3/4/2017

Resilient Societies CIP 013-1 Comments 03042017.docx

- 0 - 0

Approval of CIP Senior Manager or delegate should be required for both or neither of R1 and R2.

Nicholas Lauriat, Network and Security Technologies, 1, 3/4/2017

- 0 - 0

We suggest moving this Requirement language to the CIP-003 Standard. Our group feels that CIP-003 is the most appropriate Standard to handle this Requirement which is applicable to Low Impact BES Cyber Systems.

SPP Standards Review Group, Segment(s) , 3/5/2017

- 0 - 0

Preston Walker, On Behalf of: PJM Interconnection, L.L.C., SERC, RF, Segments 2

- 0 - 0

- 0 - 0

John Williams, 3/6/2017

- 1 - 0

Exelon feels that the R2.1 language is vague and has the potential to become administratively burdensome without a corresponding benefit to BES reliability.  While Exelon agrees with the rationale that examples of sources of information that an entity could consider include guidance or information issued by the E-ISAC, this language should be included in the Requirement itself because only that language forms the basis of a compliance assessment.  Exelon receives over 100 security-related messages regarding potential vulnerabilities per day from a myriad of sources.  Without creating bounds around the sources to be considered as well as the periodicity for updates to supply chain cyber security risk management plan(s), the question of whether any or all of the messages should have been considered will be difficult, if not impossible, to evidence.  Exelon points out that the E-ISAC already performs important filtering functions for the industry.  Perhaps future Alerts issued by the E-ISAC could be enhanced to point out vulnerabilities that would require new mitigating controls in supply chain cyber security risk management plan(s).  Without these limitations, each entity will need to develop processes and procedures to receive and filter information, define mitigating controls, update the plan(s) and obtain approvals which is inefficient at best and impossible to evidence at worst. 

Further, Exelon suggests that while multiple updates to the plan(s) may occur within a year as new E-ISAC Alerts are issued, CIP Senior Manager Review and Approval should only be required every 15 months. Intermediate reviews and approvals, or reviews for minor changes, should be outside the scope of the Requirement.

Daniel Gacek, Exelon, 1, 3/6/2017

- 0 - 0

Fred Frederick, 3/6/2017

- 0 - 0

Refer to our comments on R1.

 

We do not agree with the approach in R1 (and R2) of creating “plans” and the intent of the plans to “cover the procurement aspects of all four objectives.”

 

Order 829’s four objectives did not include creating “plans.” All four of the directives either direct or use examples of specific operational cyber security controls which are best addressed as revisions to CIP-002 through -011.

 

NERC’s Compliance Registry Summary of Unique Entities and Functions as of March 3, 2017, identifies 1,398 unique NERC entities. These entities range from entities with a couple breakers for low impact Facilities (lines), to entities operating gigawatts of low impact generation units to entities operating high-impact Control Centers for thousands of miles of medium impact Transmission Facilities, for example. All have BES Cyber Assets.

 

With respect to R2 as proposed, 1,398 entities would have to annually research information, including information which is readily available to be proactively provided by NERC to them.  This diverts and dilutes registered entities’ resources.

Darnez Gresham, Berkshire Hathaway Energy - MidAmerican Energy Co., 3, 3/6/2017

- 2 - 0

Steve Rawlinson, 3/6/2017

- 0 - 0

  • Dominion recommends that requirement R2 be replaced with the following:

“Each Responsible Entity shall review and update, as necessary, its supply chain cyber security risk management plan(s) specified in Requirement R1 related to procuring and installing unsecure equipment or software, the risk of unintentionally failing to anticipate security issues that may arise due to network architecture, unintentionally arise during technology and vendor transitions, and purchasing software that is counterfeit or that has been modified by an unauthorized party at least once every 15 calendar months, which shall include: [Violation Risk Factor: Medium] [Time Horizon: Operations Planning]”

Dominion is of the opinion that the activities specified in Part 2.1 are included in the language of R2.  Dominion recommends modifying Part 2.1 and 2.2 as follows:

  • 2.1  Revision(s), if any, to address applicable new supply chain security risks that include security considerations related to cyber security, and

  • 2.2 The supply chain plan(s) shall be reviewed, updated as necessary, and approved by CIP SM or delegate at least once every fifteen (15) months.

Also see the recommendation for replacing this requirement as described in the comments for R1.
 

Sean Bodkin, Dominion - Dominion Resources, Inc., 6, 3/6/2017

- 0 - 0

NRG recommends that each requirement should have a provision for allows an entity to accept the risk of selection a vendor that will not or cannot supply a control. NRG recommends removal of R2.1 language which is covered in R2.

For R2, will NERC, E-ISAC or other sources referenced in Rationale issue annual updates for supply chain risk? How will an entity prove that all risks have been incorporated? This seems to imply scope creep from elements on R1. Is “necessity” defined by entity, NERC, or outside source?

NRG requests clarity on how revisions to the plan would need to be addressed for contracts that are in the process of being negotiated since this negotiation process may take months.  

Kara White, On Behalf of: NRG - NRG Energy, Inc., FRCC, MRO, WECC, Texas RE, NPCC, SERC, SPP RE, RF, Segments 3, 4, 5, 6

- 0 - 0

  1. Strike R2.1 because the R2 language includes “review and update as necessary” covers the FERC Order. Additional evaluation of the revisions is an administrative task that does not enhanced BES security.  Make corresponding changes to section M2.

  2. For R2.2: Page 9 of the Guidance and Examples document states “Requirement R2 allows responsible entities to incorporate the review of CIP-013-1 into their annual CIP-003 review.”  CIP-003-6 R1 does not allow delegates to review and approve.  In addition, CIP-003 requires the review of Policies and not plans.

  3. Request clarity on how revisions to the plan would need to be addressed for contracts that are in the process of being negotiated since this negotiation process may take months.

  4. SDT should clarify that existing contracts do not need to be renegotiated based on the 15-calendar month reassessment of the plan or other plan revisions.

  5. Will NERC, E-ISAC or other sources referenced in Rationale issue annual updates for supply chain risk? How will an entity prove that all risks have been incorporated? Seems to imply scope creep from elements on R1. Is necessity in R1 defined by entity, NERC, or outside source?

David Rivera, New York Power Authority, 3, 3/6/2017

- 0 - 0

No comments.

Alyssa Hubbard, 3/6/2017

- 0 - 0

Brad Lisembee, 3/6/2017

- 0 - 0

The California ISO supports the comments submitted by the ISO/RTO Council (IRC) and the Security Working Group (SWG)

Richard Vine, 3/6/2017

- 0 - 0

Entergy/NERC Compliance, Segment(s) 1, 5, 3/1/2017

- 0 - 0

1)      Strike R2.1 because the R2 language includes “review and update as necessary” covers the FERC Order. Additional evaluation of the revisions is an administrative task that does not enhanced BES security.  Make corresponding changes to section M2.

 

2)      For R2.2: Page 9 of the Guidance and Examples document states “Requirement R2 allows responsible entities to incorporate the review of CIP-013-1 into their annual CIP-003 review.”  CIP-003-6 R1 does not allow delegates to review and approve.  In addition, CIP-003 requires the review of Policies and not plans.

 

3)      Request clarity on how revisions to the plan would need to be addressed for contracts that are in the process of being negotiated since this negotiation process may take months.

Quintin Lee, Eversource Energy, 1, 3/6/2017

- 0 - 0

The Rational for Requirement R2 lists several sources for supply chain vulnerabilities, but it is not clear what is considered a relevant source and whether the entity is required to review all sources of supply chain vulnerabilities which may be very burdensome.  CenterPoint Energy recommends adding the specific sources of vulnerability information, such as E-ISAC or ICS-CERT in the requirement.  

Amelia Sawyer Anderson, On Behalf of: CenterPoint Energy Houston Electric, LLC, Texas RE, Segments 1

- 0 - 0

Nicolas Turcotte, Hydro-Qu?bec TransEnergie, 1, 3/6/2017

- 0 - 0

  No additional comments.

DTE Energy - DTE Electric, Segment(s) 5, 4, 3, 2/27/2017

- 0 - 0

RoLynda Shumpert, On Behalf of: SCANA - South Carolina Electric and Gas Co., SERC, Segments 1, 3, 5, 6

- 0 - 0

I support the comments submitted by Brian Evans-Mongeon, Utility Services, Inc, and Marty Hostler, Northern California Power Agency.

Dennis Sismaet, Northern California Power Agency, 6, 3/6/2017

- 0 - 0

OUC agrees that the plans in Requirement R1 need to be updated and a 15-month review period is appropriate.  However, OUC requests the removal of R2.1 and 2.2 and updating R2 to read:  Each Responsible Entity shall review its supply chain cyber security risk management plan(s) specified in R1 at least once every 15 calendar months, to include reviewing new risks and mitigation measures and identifying related changes, if any, and obtain CIP Senior Manager or delegate(s) approval.

Ballard Mutters, Orlando Utilities Commission, 3, 3/6/2017

- 0 - 0

While it is not unreasonable to propose periodic review and reassessment to assure some minimum level of rigor, ultimately Registered Entities know that plans are living documents that must be supported by sound security practices implemented to stay apprised of emerging cybersecurity threats as they enter the landscape, and a 15-month reassessment is ill-equipped to support the pace of the ever-evolving threat landscape. The industry might be better served with language that supports a periodic review coupled with the need for ongoing and timely assessment and update of plans on an as needed basis when the impending threat warrants the action.

The SDT may want to reconsider the need and intended value for CIP Senior Manager approval for these reasons. 1.) While it is not unreasonable to propose an approval for plans of this nature, prescribing this as a CIP Senior Manager responsibility is inconsistent with other enforceable mandatory CIP Cyber Security Reliability Standards that limit these approvals to BES Cyber System populations, policy, and, exceptions (both CIP Exceptional Circumstances and Technical Feasibility Exceptions).  2.) The introduction of CIP Senior Manager or delegate approval may not provide the intended value for the complex range of jurisdictional, technical, economic, and business relationship issues. 3.) By NERC definition, as a technicality, please note that the scope of the CIP Senior Manager accountabilities is currently prescribed as CIP-002 – CIP-011 and would require amendment. 4.) Lastly, as a consideration, the SDT may want to revisit the need for this level of approval and to align the approach with the former efforts associated to the FERC filing of proposed retired standards for Project 2013-02 Paragraph 81, and the intent to eliminate requirements are administrative in nature only and therefore that do not provide security or reliability value.   

Lauren Price, 3/6/2017

- 0 - 0

CPS Energy supports the comments provided by ERCOT and APPA

Brian Bartos, On Behalf of: Brian Bartos, , Segments 1, 3, 5

- 0 - 0

Xcel Energy supports the comments filed by the Edison Electric Institute (EEI).

- 0 - 0

1.       Requiring a greater level of testing, documentation, or security features from system integrators, suppliers, and external service providers may increase the price of a product or service, and increase the compliance burden for the industry. We recommend language addressing key questions, such as: at what time frame does the risk reduce to acceptable: Daily, weekly, monthly or yearly? How is the standard addressing acceptance of risk?

Warren Cross, On Behalf of: ACES Power Marketing, MRO, WECC, Texas RE, SERC, SPP RE, Segments 1, 3, 4, 5

- 0 - 0

Though each of the objectives in Order 829 is addressed, Reclamation recommends a more simplified format for the requirements as the SDT originally suggested in the webinar on November 10, 2016.

 

Reclamation recommends Requirement R2 should instead require entities to implement their supply chain risk management plan(s) developed in Requirement R1.

Within each Requirement, the sub-requirements should distinguish between high, medium, and low impact BES Cyber Systems and other supporting systems. Reclamation recommends the implementation plan enforcement dates be staggered based on high, medium, and low impact for auditing purposes and to allow the associated risks and severity levels to be spelled out more clearly.

Wendy Kalidass, U.S. Bureau of Reclamation, 5, 3/6/2017

- 0 - 0

R2

IPC suggests the SDT consider re-structuring the proposed format for R2 to align with current enforceable standard format (see CIP-002-5.1 R2, R2.1, and R2.2):

The Responsible Entity shall: (1) Review and update, as necessary, its supply chain cyber security risk management plan(s) specified in Requirement R1 at least once every 15 calendar months, (2) Evaluate revisions, if any, to address applicable new supply chain security risks and mitigation measures; and (Question) How does the SDT foresee this evaluation being measured and accomplished? (3) Obtain its CIP Senior Manager or delegate approval (Question) Is the CIP Senior Manager or delegate intended to be an approval of the plan every 15 months? If so, IPC recommends specifying the timing and what is being approved in the wording of the requirement.

 

IPC does not believe R2.2 provides any security measures or controls and is simply an administrative exercise.  IPC recommends R2.2 be removed.

Laura Nelson, 3/6/2017

- 0 - 0

Santee Cooper agrees that the plans in Requirement R1 need to be updated and a 15-month review period is appropriate.  However, Santee Cooper requests the removal of R2.1 and 2.2 and updating R2 to read:  Each Responsible Entity shall review its supply chain cyber security risk management plan(s) specified in R1 at least once every 15 calendar months, to include reviewing new risks and mitigation measures and identifying related changes, if any, and obtain CIP Senior Manager or delegate(s) approval.

Santee Cooper , Segment(s) 1, 5, 3/6/2017

- 0 - 0

Teresa Krabe, Lower Colorado River Authority, 5, 3/6/2017

- 0 - 0

BPA believes if the scope and language for R1 is appropriate, the review process is necessary but should not require CIP Senior Manager Approval. BPA suggests maintaining consistency across standards: CIP Senior Manager approval is required for policies rather than plans.

Aaron Cavanaugh, On Behalf of: Bonneville Power Administration, WECC, Segments 1, 3, 5, 6

- 0 - 0

For consistency and to ensure that the requirement appropriately reflects the scope of risks being addressed, AZPS requests striking of ‘supply chain security risks’ in Requirement R2.1 and replacing with ‘Vendor security risks’.

Stephanie Little, 3/6/2017

- 0 - 0

1)      Suggest deleting R2.1. The R2 language includes “review and update as necessary”. Additional evaluation of the revisions is an administrative task that does not enhanced BES security.  Make corresponding changes to section M2.

Nathan Mitchell, On Behalf of: Nathan Mitchell, , Segments 3, 4

- 0 - 0

 CPS Energy supports the comments provided by APPA

Glenn Pressler, CPS Energy, 3, 3/6/2017

- 0 - 0

This should be removed and convered in CIP-003.

Louis Guidry, 3/6/2017

- 0 - 0

PSEG agrees with the intent of this requirement, but has the following questions/recommendations below:

  • Recommend changing Requirement 2.1 from “Evaluation of revisions, if any, to address applicable new supply chain security risks and mitigation measures; and” to “Evaluation of revisions, if any, to address applicable new supply chain security risks and mitigation measures as determined by the registered entity; and”.

     

  • The standard language does not address how a revision to the plan needs to be addressed by contracts already in process/negotiation at the time of review or revision. Please provide guidance.

PSEG REs, Segment(s) 5, 6, 3, 1, 3/6/2017

- 1 - 0

Colorado Springs Utilities (CSU) agrees that the plans in Requirement R1 need to be updated and a 15-month review period is appropriate.  However, CSU requests the removal of R2.1 and 2.2 and updating R2 to read:  Each Responsible Entity shall review its supply chain cyber security risk management plan(s) specified in R1 at least once every 15 calendar months, to include reviewing new risks and mitigation measures

Colorado Springs Utilities, Segment(s) 5, 3, 1, 6, 5/6/2015

- 0 - 0

With regards to the periodic reassessment of supply chain cyber security risk management controls, the IESO request the SDT provide objective criteria for the scope and content of the review to ensure consistent implementation against set criteria. Does this only require update of the plan document? Do needed ntract revisions have to be documented? What is required to demonstrate review and consideration of items that may not be incorporated into the updated plan?

Leonard Kula, Independent Electricity System Operator, 2, 3/6/2017

- 0 - 0

Seattle City Light agrees that the plans in Requirement R1 need to be updated and a 15-month review period is appropriate.  However, Seattle City Light requests the removal of R2.1 and 2.2 and updating R2 to read:  Each Responsible Entity shall review its supply chain cyber security risk management plan(s) specified in R1 at least once every 15 calendar months, to include reviewing new risks and mitigation measures and identifying related changes, if any, and obtain CIP Senior Manager or delegate(s) approval.

Seattle City Light Ballot Body, Segment(s) 1, 4, 6, 5, 3, 12/2/2016

- 0 - 0

FEUS supports the comments submitted by APPA

Linda Jacobson-Quinn, City of Farmington, 3, 3/6/2017

- 0 - 0

FMPA agrees with comments submitted by American Public Power Association.

FMPA, Segment(s) , 12/5/2016

- 0 - 0

Jay Barnett, 3/6/2017

- 0 - 0

We believe that sub requirements (2.1 and 2.2) in R2 are unnecessary.  Similar verbiage used in CIP-003-6 for review of cyber security policy can be used in this instance.  Also, can the CIP Senior Manager delegate this accountability?

Payam Farahbakhsh, Hydro One Networks, Inc., 1, 3/6/2017

- 0 - 0

The NYPA Comments

Erick Barrios, 3/6/2017

- 0 - 0

 

SMUD agrees that the plans in Requirement R1 need to be updated and a 15-month review period is appropriate.  However, SMUD requests the removal of R2.1 and 2.2 and updating R2 to read:  Each Responsible Entity shall review its supply chain cyber security risk management plan(s) specified in R1 at least once every 15 calendar months, to include reviewing new risks and mitigation measures and identifying related changes, if any, and obtain CIP Senior Manager or delegate(s) approval.

 

- 0 - 0

The rationale for Requirement R2 suggests that every Responsible Entity should assess all supply chain risks before updating the plan, which may be a very burdensome requirement that will be difficult to comply with and audit. Would a Responsible Entity be in violation if it didn’t document that they read a particular DHS report? Also, the Requirement R1 plan is focused on methods to review, assess, and evaluate vendor and vendor product/service risk before entering into a contract with a vendor, these methods are unlikely to change all that much based on guidance issued by NERC or DHS and would be naturally covered by a periodic review and approval of the plan(s).

Also, part 2.1 requires an evaluation of revisions to address new supply chain security risks and mitigation measures. It is unclear how a revision to address a new supply chain security risk is different than a mitigation measure. A mitigation measure addresses a risk.

We recommend the following language for consideration by the SDT:

R2.  Each Responsible Entity shall review and obtain CIP Senior Manager or delegate approval for its supply chain cyber security risk management plan(s) specified in Requirement R1 at least once every 15 calendar months.

Melanie Seader, On Behalf of: Edison Electric Institute, NA - Not Applicable, Segments NA - Not Applicable

- 1 - 0

Tacoma concurs with the comments provided by the LPPC.

Marc Donaldson, Tacoma Public Utilities (Tacoma, WA), 3, 3/6/2017

- 0 - 0

- 0 - 0

  SDG&E agrees with EEI comments and proposed language.  R2 needs a more clear description on when mitigation measures are required.  For example, would the selection of one vendor over another be considered a mitigation measure?  Would an entity be required to always choose the vendor with the best-in-class security posture despite cost?    

Jeff Johnson, On Behalf of: Sempra - San Diego Gas and Electric, WECC, Segments 1, 2, 3, 4, 5, 6, 7

- 0 - 0

- 0 - 0

The rationale for Requirement R2 suggests that every Responsible Entity should assess all supply chain risks before updating the plan, which may be a very burdensome requirement that will be difficult to comply with and audit. Would a Responsible Entity be in violation if it didn’t document that they read a particular DHS report? Also, the Requirement R1 plan is focused on methods to review, assess, and evaluate vendor and vendor product/service risk before entering into a contract with a vendor, these methods are unlikely to change all that much based on guidance issued by NERC or DHS and would be naturally covered by a periodic review and approval of the plan(s).

Also, part 2.1 requires an evaluation of revisions to address new supply chain security risks and mitigation measures. It is unclear how a revision to address a new supply chain security risk is different than a mitigation measure. A mitigation measure addresses a risk.

We recommend the following language for consideration by the SDT:

R2.  Each Responsible Entity shall review and obtain CIP Senior Manager or delegate approval for its supply chain cyber security risk management plan(s) specified in Requirement R1 at least once every 15 calendar months.

 

We feel that there should be some guidance on where to look for “emerging supply chain related concerns”. If our company is using a particular source and miss a notification on another site, will we be penalized?

 

3. The SDT developed CIP-013-1 Requirement R3 to address the Order No. 829 directive for entities to address verification of software integrity and authenticity in the BES Cyber System environment (P 48) as it applies to high and medium impact BES Cyber Systems. Do you agree with the proposed requirement? If you do not agree, or if you agree but have comments or suggestions for the proposed requirement provide your recommendation and explanation.

William Wenz, On Behalf of: AES - Dayton Power and Light Co., RF, Segments NA - Not Applicable

- 0 - 0

With regards to the periodic reassessment of supply chain cyber security risk management controls, the IRC and SWG request the SDT provide objective criteria for the scope and content of the review to ensure consistent implementation against set criteria. Does this only require update of the plan document? Do needed contract revisions have to be documented? What is required to demonstrate review and consideration of items that may not be incorporated into the updated plan?

IRC-SRC, Segment(s) 2, 11/18/2016

- 0 - 0

The rationale for Requirement R2 suggests that every Responsible Entity should assess all supply chain risks before updating the plan, which may be a very burdensome requirement that will be difficult to comply with and audit. Would a Responsible Entity be in violation if it didn’t document that they read a particular DHS report? Also, the Requirement R1 plan is focused on methods to review, assess, and evaluate vendor and vendor product/service risk before entering into a contract with a vendor, these methods are unlikely to change all that much based on guidance issued by NERC or DHS and would be naturally covered by a periodic review and approval of the plan(s).

Also, part 2.1 requires an evaluation of revisions to address new supply chain security risks and mitigation measures. It is unclear how a revision to address a new supply chain security risk is different than a mitigation measure. A mitigation measure addresses a risk.

We recommend the following language for consideration by the SDT:

R2.  Each Responsible Entity shall review and obtain CIP Senior Manager or delegate approval for its supply chain cyber security risk management plan(s) specified in Requirement R1 at least once every 15 calendar months.

 

We feel that there should be some guidance on where to look for “emerging supply chain related concerns”. If our company is using a particular source and miss a notification on another site, will we be penalized?

William Wenz, On Behalf of: AES - Dayton Power and Light Co., RF, Segments NA - Not Applicable

- 0 - 0

GTC knows of no definitive source to identify “new supply chain security risks and mitigation measures.”  Therefore, compliance with this requirement part becomes subjective thus is not auditable.  Reviewing and updating the plan as necessary under the core R2 along with CIP Senior Manager approval per R2.2 should be sufficient to maintaining a quality cyber security supply chain risk management program.  We recommend the removal of requirement part 2.1. 

Jason Snodgrass, 3/6/2017

- 0 - 0

Agree that it is appropriate to reassess the Entity plan associated with R1.1.  For the reasons already stated in the R1 response, updates to the R1.2 requirements would be unmanageable to point of being non-productive for entities and suppliers.

Bob Case, On Behalf of: Black Hills Corporation, WECC, Segments 1, 3, 5, 6

- 0 - 0

Refer to CSU comments.

Devin Elverdi, 3/6/2017

- 0 - 0

See comments submitted by Black Hills Corporation

Maryanne Darling-Reich, 3/6/2017

- 0 - 0

It is not clear if the approval by the CIP Senior Manager is required with the first version of the plans, or only for subsequent revisions.  It is not clear if the approval by the CIP Senior Manager or delegate is required with each review cycle or only if modifications are made to the document(s).

Bob Reynolds, On Behalf of: Bob Reynolds, , Segments 10

- 0 - 0

Avista supports the comments filed by the Edison Electric Institute (EEI).

- 0 - 0

1)      Strike R2.1 because the R2 language includes “review and update as necessary” covers the FERC Order. Additional evaluation of the revisions is an administrative task that does not enhanced BES security.  Make corresponding changes to section M2.

 

2)      For R2.2: Page 9 of the Guidance and Examples document states “Requirement R2 allows responsible entities to incorporate the review of CIP-013-1 into their annual CIP-003 review.”  CIP-003-6 R1 does not allow delegates to review and approve.  In addition, CIP-003 requires the review of Policies and not plans.

 

3)      Request clarity on how revisions to the plan would need to be addressed for contracts that are in the process of being negotiated since this negotiation process may take months.

 

SDT should clarify that existing contracts do not need to be renegotiated based on the 15-calendar month reassessment of the plan or other plan revisions.

 

Will NERC, E-ISAC or other sources referenced in Rationale issue annual updates for supply chain risk? How will an entity prove that all risks have been incorporated? Seems to imply scope creep from elements on R1. Is necessity in R1 defined by entity, NERC, or outside source?

RSC no Dominion and NextEra, Segment(s) 1, 0, 2, 4, 5, 6, 7, 3, 3/6/2017

- 0 - 0

The annual assessment of new risk is too open ended for a mandatory and enforceable Standard.

Philip Huff, On Behalf of: Philip Huff, , Segments 3, 4, 5, 6

- 0 - 0

See Black Hills Corp comments

George Tatar, 3/6/2017

- 0 - 0

Agree that it is appropriate to reassess the Entity plan associated with R1.1, but updates to the R1.2 portion would be unmanageable to point of being non-productive for entities and suppliers, for the reasons already stated in the R1 response above.

Wes Wingen, 3/6/2017

- 0 - 0

We generally agree with EEI’s comments, except for the exclusion of EACMS, PACs and PCAs for Requirement 1.

Jamie Monette, Allete - Minnesota Power, Inc., 1, 3/6/2017

- 0 - 0

The way the Requirement is written once again leaves the Requirement open to interpretation.

The current text reads:

“Each Responsible Entity shall review and update, as necessary, its supply chain cyber security risk management plan(s) specified in Requirement R1 at least once every 15 calendar months, which shall include:”

SunPower believes the correct statement of R2 should read:

“Each Responsible Entity shall review, as necessary, but at least once every 15 calendar months, its supply chain cyber security risk management plan(s) specified in Requirement R1 and update as necessary. The reviews and updates includes, but not limited to:”

SunPower also believes that the intent of R2.1 is not clear when the Requirement states, “to address applicable new . . . “ SunPower believes the term “applicable” needs to be left out of the Requirement unless the SDT is talking to the Applicability Section of the Standard, if that is the case, then state the Applicability Section. If that is not the case, SunPower believes the sub part should read:

“2.1 Evaluation of revisions, if any to address newly identified supply chain security risks and mitigation measures”

Bradley Collard, 3/6/2017

- 0 - 0

Kansas City Power and Light Company incorporates by reference Edison Electric Institute’s comments to Question 2.

Douglas Webb, 3/6/2017

- 0 - 0

For consistency with other CIP Standards, CIP-003 R1.1 should be expanded to include supply chain risk management as part of the collective cyber security policies to be reviewed and approved by the CIP Sr. Manager at least every 15 months and removed from CIP-013-1.

Oxy, Segment(s) 7, 5, 9/6/2016

- 0 - 0

Heather Morgan, EDP Renewables North America LLC, 5, 3/6/2017

- 0 - 0

Sergio Banuelos, On Behalf of: Tri-State G and T Association, Inc., MRO, WECC, Segments 1, 3, 5

- 0 - 0

Concur with EEI’s Position

Linsey Ray , 3/6/2017

- 0 - 0

SVP agrees with other entity comments that "additional evaluation of the revisions is an administrative task that does not enhance BES security."

Val Ridad, On Behalf of: Silicon Valley Power, WECC, Segments 1

- 0 - 0

R2 – first line – for clarity purposes NRECA recommends removing “and update, as necessary.”

R2.1 – strongly recommend deleting “to address applicable new supply chain security risks and mitigation measures” as it is unclear and unnecessarily open-ended.

Barry Lawson, 3/6/2017

- 0 - 0

Scott Downey, 3/6/2017

- 0 - 0

EPE shares the comments and concerns voiced by the Edison Electric Institute (EEI) in this Ballot #1.  Please refer to the EEI ballot for detailed comments on each of the proposed requirements.

Luis Rodriguez, El Paso Electric Company, 6, 3/6/2017

- 0 - 0

EPE shares the comments and concerns voiced by the Edison Electric Institute (EEI) in this Ballot #1.  Please refer to the EEI ballot for detailed comments on each of the proposed requirements.

Pablo Onate, El Paso Electric Company, 1, 3/6/2017

- 0 - 0

Generally, we agree with the requirement to have the CIP Senior Manager review and update, as necessary, its supply chain cyber security risk management plan(s) specified in Requirement R1 at least once every 15 calendar months.  However, R2.1 could be interpreted in many ways that might introduce uncertainty in the process.  In agreement with EEI, we suggest the following language:

R2.  Each Responsible Entity shall review and obtain CIP Senior Manager or delegate approval for its supply chain cyber security risk management plan(s) specified in Requirement R1 at least once every 15 calendar months.

Luminant, Segment(s) 6, 7, 5, 1/24/2017

- 1 - 0

EPE shares the comments and concerns voiced by the Edison Electric Institute (EEI) in this Ballot #1.  Please refer to the EEI ballot for detailed comments on each of the proposed requirements.

Victor Garzon, 3/6/2017

- 0 - 0

Scott Kinney, Avista - Avista Corporation, 3, 3/6/2017

- 0 - 0

ERCOT supports the IRC comments on this question. 

Elizabeth Axson, 3/6/2017

- 0 - 0

Hot Answers

- 0 - 0

Southern Company disagrees with the direction the proposed R3 requirement is taking.  Given our previous comments under R1 regarding the proper scoping of this new Standard to the “Supply Chain” time horizon, actions proposed to be required under R3 fall outside of that time horizon where the controls are applicable to BES Cyber Systems, which are not yet designated or commissioned as such.  Additionally, R3 requires the development of “one or more documented processes” that are in addition to “the plan(s)” required in R1; Southern recommends maintaining the proper scoping of this Standard by moving the components of R3 under R1 to be addressed by the Responsible Entity in “the plan(s).”   

If R3 is not consolidated under the R1 requirements for “the plan(s)” to be applicable within the Supply Chain time horizon, then Southern provides the following recommended edits to maintain vital consistency with existing requirements under CIP-010 R1.1.  There is firmware in every video card, mouse, hard drive, etc. that is NOT the objective of the requirements in this Standard, but could, without the qualification provided below, be included.  The addition under R3.2 also provides vital consistency with CIP-010 R1.1 so we aren’t maintaining different baseline configurations on all of our systems because of slightly different wording in the two Standards. 

In this situation where very similar requirements in two different standards create additional administrative burden on entities, the SDT needs to recognize and address the delays that the proposed R3 requirements will have on the existing requirements under CIP-007-6 R2 (Patch Management).  The burden of verification of integrity and authenticity of software and firmware in front of applicable requirements for determining availability, applicability, and conducting deployment of security patches within 35 day cycles will make those existing requirements under CIP-007-6 R2 unmanageable and will increase the administrative burden of creating patch mitigation plans as a result of competing Standards.

           

Modify R3 language as follows:

 

R3. Each Responsible Entity shall implement one or more documented process(es) that addresses the verification of the integrity and authenticity of the following software and firmware before being placed in operation on high and medium impact BES Cyber Systems:  [Violation Risk Factor: Medium] [Time Horizon: Operations Planning]

3.1  Operating System(s) or firmware where no independent operating system exists;

3.2  Commercially available or open-source application software intentionally installed; and

3.3  Patches, updates, and upgrades to 3.1 and 3.2.

Southern Company, Segment(s) 1, 3, 5, 6, 8/3/2016

- 0 - 0

Other Answers

Dennis Minton, 1/19/2017

- 0 - 0

Dennis Minton, 1/19/2017

- 0 - 0

Dennis Minton, 1/19/2017

- 0 - 0

Dennis Minton, 1/19/2017

- 0 - 0

Tom Anthony, On Behalf of: Tom Anthony, , Segments 1, 3

- 0 - 0

Tom Anthony, On Behalf of: Tom Anthony, , Segments 1, 3

- 0 - 0

Glen Farmer, Avista - Avista Corporation, 5, 2/6/2017

- 0 - 0

Russel Mountjoy, 2/24/2017

- 0 - 0

Suggest “software, firmware, and associated patches” Possible TFE language for R3? The

NSRF recommends the following:

Q 3.  Add language to address potential Technical Feasibility Exception (TFE).

 

R3. Each Responsible Entity shall implement one or more documented process(es) for verifying the integrity and authenticity of the following software and firmware, where technically feasible, before being placed in operation on high and medium impact BES Cyber Systems:

 

R3.2

“Firmware” is already included in R3 this redundant in R3.2 recommend R3 to be written as a general Requirement with specifics in the sub Requirements.

MRO NSRF, Segment(s) 1, 2, 3, 4, 5, 6, 2/24/2017

- 1 - 0

The standard as written doesn’t clearly address the objectives as listed in its Requirements. It also creates confusion and possible double jeopardy with other CIP Standards.

faranak sarbaz, Los Angeles Department of Water and Power, 1, 2/27/2017

- 0 - 0

Richard Kinas, 2/28/2017

- 0 - 0

TFE opportunity is again needed, especially to address vendor-proprietary (“black box”) vendor software and firmware, nor should there be any obligation to impose measures on vendors (see our “additional comments” responses).

R1.2.5 is largely duplicative of R3.  They should be made consistent, or one of them should be deleted.

R3 may better belong in CIP-007 and needs to be aligned with CIP-010.  Requirements for a single topic should be consolidated within a single standard.

Donald Lock, 2/28/2017

- 0 - 0

See APPA's, TAP's, and USI's comments.

Marty Hostler, Northern California Power Agency, 4, 2/28/2017

- 1 - 0

Thomas Foltz, AEP, 5, 3/2/2017

- 0 - 0

This appears to be a reasonable approach to meeting the FERC directive.

Rachel Coyne, Texas Reliability Entity, Inc., 10, 3/2/2017

- 0 - 0

Mike Smith, Manitoba Hydro , 3, 3/2/2017

- 0 - 0

Change/add language to emphasize that failure to obtain the cyber security controls from a vendor doesn’t translate to being out of compliance. Entity should have the ability to mitigate risks posed by vendors.  Furthermore, this risk should be evaluated during the procurement and deployment of vendor products and services (CIP-013-1 R1), and mitigated as part of the CIP-007 R2.

 

IID feels that there should be an exclusion or exception (similar to a CIP Exceptional Circumstance or Technical Feasibility Exception) added to this requirement for situations where the vendor does not cooperate or is otherwise unavailable.

 

Jesus Sammy Alcaraz, Imperial Irrigation District, 1, 3/2/2017

- 0 - 0

Would deployment tools that rely on digital signature enforcement (such as Microsoft Authenticode Security Verification or Red Hat signature verification) satisfy the intent of this requirement where such mechanisms provide technical checks for verification of authenticity and integrity?

The requirement measures should allow automated deployment tools such as Microsoft’s System Center Configuration Management to be trusted for the purpose of confirming the integrity and authenticity of software and firmware.
 

Tennessee Valley Authority, Segment(s) 1, 3, 5, 6, 9/1/2016

- 0 - 0

Eric Ruskamp, Lincoln Electric System, 6, 3/2/2017

- 0 - 0

Deborah VanDeventer, On Behalf of: Edison International - Southern California Edison Company, WECC, Segments 1, 3, 5, 6

- 0 - 0

Please refer to comments submitted by Deborah VanDeventer on behalf of Southern California Edison.

Romel Aquino, Edison International - Southern California Edison Company, 3, 3/2/2017

- 0 - 0

Duke Energy recommends the following language revision to R3.

“For BES Cyber Systems in production, each Responsible Entity shall implement one or more documented process(es) for verifying the integrity and authenticity of the following software and firmware prior to installation on high and medium impact BES Cyber Systems:”

We suggest the addition of the phrase “For BES Cyber Systems in production,” at the outset of the requirement.

We also recommend replacing the phrase “placed in operation” with “prior to installation” in R3. The phrase “placed in operation” is ambiguous, and could be open to debate as to what this actually means. The language “prior to installation” is less ambiguous, the language used in FERC Order 829, and is already used in the rationale section for this requirement.

Also, Duke Energy has some concern with the amount of involvement/cooperation that will be necessary from a vendor in order to achieve compliance with this requirement. Some issues may arise if/when a vendor is not able to verify the integrity or authenticity of a certain product. We suggest the drafting team consider this situation as appropriate for a Technical Feasibility Exception or in some instances be granted a CIP Exceptional Circumstance. For example, an issue could arise wherein an entity has a device that is failing, and a fix (update of software) is needed immediately. In the interest of system stability, there may not be enough time to wait on a vendor to send a certificate of authenticity on a patch or software upgrade. We feel that a Technical Feasibility Exception and CIP Exceptional Circumstance should be considered based on these issues.

Another aspect of R3 that we think requires some clarity is whether or not R3 should apply at the BES Cyber Asset level. Currently, the language explicitly states BES Cyber System, but we feel that the language may not represent the actual intent of the requirement. If the controls proposed in R3 are better suited at the Cyber Asset level, the language should be revised to reflect this.

Lastly, Duke Energy would like to suggest that the drafting team consider that this requirement be moved to current standard CIP-007-6. CIP-007-6 already addresses security controls for BES Cyber Systems, and we feel that this control oriented requirement may be better suited there.

Duke Energy , Segment(s) 1, 5, 6, 4/10/2014

- 0 - 0

Requirement R3 mentions high and medium BES Cyber Systems, but does not include their associated Electronic Access Control and Monitoring Systems (EACMs), Physical Access Controls(PACS), and Protected Cyber Assets (PCAs).  ReliabilityFirst offers the following modifications for consideration:

  1. R3. Each Responsible Entity shall implement one or more documented process(es) for verifying the integrity and authenticity of the following software and firmware before being placed in operation on high and medium impact BES Cyber Systems [and if applicable, associated Electronic Access Control or Monitoring Systems, Physical Access Control Systems, and Protected Cyber Assets]:

Anthony Jablonski, ReliabilityFirst , 10, 3/3/2017

- 0 - 0

CIP-007 R2 requires a mitigation plan for patches that cannot be applied within 35 days.  Please confirm that if a patch cannot be applied within 35 days due to the vendor’s inability to provide the integrity check, there is no other compliance risk if the RE provides a mitigation plan in accordance with CIP-007 R2. 

 

Additionally, if vendors refuse or can’t provide hashes or other verification methods, please provide confirmation that an internal process to test, scan and perform verification activities would be enough to satisfy this requirement.

PPL NERC Registered Affiliates, Segment(s) 3, 1, 5, 6, 2/9/2017

- 1 - 0

See NPCC comments.

ALAN ADAMSON, New York State Reliability Council, 10, 3/3/2017

- 0 - 0

Please refer to comments submitted by Deborah VanDeventer on behalf of Southern California Edison

Thomas Rafferty, 3/3/2017

- 0 - 0

AECI urges the SDT to remove R3 and address firmware and software integrity/authenticity in the supply chain risk management plan(s) as detailed in the requirement concepts proposed by AECI in Question 1.  This will allow Responsible Entities to address this issue contractually with applicable vendors in the supply chain/procurement process and not the operational time horizon.

Mark Riley, Associated Electric Cooperative, Inc., 1, 3/3/2017

- 0 - 0

CHPD requests that the scope of R3 be limited to high and medium BES Cyber Systems with ERC or Dial-up Connectivity in alignment with the approach in existing CIP-007 and CIP-010. 

Mick Neshem, 3/3/2017

- 0 - 0

PRPA requests that the scope of R3 be limited to high and medium BES Cyber Systems with ERC or Dial-up Connectivity in alignment with the approach in existing CIP-007 and CIP-010

Tyson Archie, Platte River Power Authority, 5, 3/3/2017

- 1 - 0

Please refer to comments submitted by Deborah VanDeventer on behalf of Southern California Edison.

Steven Mavis, 3/3/2017

- 0 - 0

AE requests that the scope of R3 be limited to high and medium BES Cyber Systems with ERC or Dial-up Connectivity in alignment with the approach in existing CIP-007 and CIP-010. 

Andrew Gallo, 3/3/2017

- 1 - 0

  1. R3 creates confusion and possible double jeopardy with CIP-007 R2 and CIP-010 R4 part 1.4.4.  Recommend moving R3 into these Standards/Requirements. This modification to CIP-007 and CIP-010 addresses FERC order No. 829.

     

  2. How does the SDT propose that the responsible entity handle R3 for existing equipment when the vendor is out-of-business or will not cooperate? This equipment may have been purchased prior to the implementation of CIP-013 but not put in services until after the effective date.

     

  3. The applicability of this requirement should be limited to high and medium impact BES Cyber Systems with external routable connectivity.  This would align the standard with the applicability of CIP-007 and CIP-010. 

     

  4. Suggest changing the format of the standard to use Applicability Tables like those used in CIP-004 through CIP-011.

     

  5. Suggest changing the format of the standard to use Applicability Tables like those used in CIP-004 through CIP-011.  

  6. Provide clarity for when a system is pre-loaded by a vendor and delivered to an entity. Is the entity required to verify software authenticity?  If a computer is purchased from Dell, can Dell provide authenticity for all of the firm ware that is part of the system but not directly manufactured by Dell;  i.e.  system bios, sound system, network adapter, video controller.

Brian Evans-Mongeon, Utility Services, Inc., 4, 3/3/2017

- 0 - 0

CHPD requests that the scope of R3 be limited to high and medium BES Cyber Systems with ERC or Dial-up Connectivity in alignment with the approach in existing CIP-007 and CIP-010. 

Janis Weddle, 3/3/2017

- 0 - 0

CHPD requests that the scope of R3 be limited to high and medium BES Cyber Systems with ERC or Dial-up Connectivity in alignment with the approach in existing CIP-007 and CIP-010. 

Haley Sousa, 3/3/2017

- 0 - 0

Jeanie Doty, 3/3/2017

- 0 - 0

I support the comments of Andrew Gallo at Austin Energy.

W. Dwayne Preston, 3/3/2017

- 0 - 0

We agree with the LPPC/APPA comments.

JEA Voters, Segment(s) , 3/3/2017

- 0 - 0

No Comments

Alan Farmer, On Behalf of: ACEC/Burns & McDonnell, NA - Not Applicable, Segments NA - Not Applicable

- 0 - 0

This requirement should be incorporated into CIP-007 R2 or CIP-010 R1.  This is a System Security Management requirement and belongs in the appropriate location.  CIP-013-1 R3.1-R3.4 are all components of the the CIP-010 baseline.  Placing this topic in a separate standard and requirement creates compliance confusion. As entities will have to follow different requirements in CIP-007, CIP-010, and CIP-013, there is an increased likelihood of a violation. 

As there is no consistency within the software industry on the use of hash functions, there must be guidelines on what is considered an acceptable approach to meet this requirement.  While guidelines are needed, it must be understood that many times the individual utility has little influence on software vendors due to the relatively small purchasing power of the electric sector relative to the vendor's overall market.

Michael Haff, On Behalf of: Seminole Electric Cooperative, Inc., FRCC, Segments 1, 3, 4, 5, 6

- 0 - 0

CHPD requests that the scope of R3 be limited to high and medium BES Cyber Systems with ERC or Dial-up Connectivity in alignment with the approach in existing CIP-007 and CIP-010. 

Chad Bowman, 3/3/2017

- 0 - 0

SRP requests that the scope of R3 be limited to high and medium BES Cyber Systems with ERC or Dial-up Connectivity in alignment with the approach in existing CIP-007 and CIP-010. 

Lona Calderon, On Behalf of: Salt River Project, WECC, Segments 1, 3, 5, 6

- 1 - 0

Please refer to comments submitted by Deborah VanDeventer on behalf of Southern California Edison

Kenya Streeter, Edison International - Southern California Edison Company, 6, 3/3/2017

- 0 - 0

What other measures or documented evidence should be expected by the Regional Entities when evaluating R3 at audit? An entity could leverage existing CIP-010-2 R1 (3.1-3.3) baseline controls and CIP-007-6 R2 patch management (3.4) controls to support the integrity and authenticity of software and firmware as specified in the CIP-013-1 R3 requirement.  However, since the baseline configurations are developed and managed at the BCS level, it is possible that a change to the baseline configuration(s) of a vendor supplied system may not trigger a change to the corresponding baseline configuration for the BCS to which the system(s) is assigned.  Therefore, relying on changes to the baseline configuration(s) may not (by itself) be a reliable control to determine if changes were made to a new vendor-supplied system.  In such cases, the addition of a simple control (an extra check for new vendor-supplied systems) integrated into an entity's existing CIP-010-2 program would suffice to address the issue.

Steven Rueckert, Western Electricity Coordinating Council, 10, 3/3/2017

- 0 - 0

John Hagen, 3/3/2017

- 0 - 0

  • The scope of CIP-013-1 R3 overlaps with parts of CIP-007-6 R2 and CIP-010-2 R1.1-1.5.  However, both CIP-007 R2 and CIP-010 R1 apply to High and Medium BCS and associated EACMS, PACs, and PCAs.  The potential collision of requirements that apply inconsistently (e.g. BCS vs EACMS) across three standards will be difficult to manage, monitor, and implement.  For example, timing of security patch implementation per CIP-007 R2.3 could be impeded by authenticity processes required in CIP-013.  Meeting compliance with CIP-013 could unintentionally cause not only potential compliance problems with CIP-007 R2, but also significant security, operational, and/or reliability impacts.

  • An exception process is required for R3.  This requirement will apply to the existing complement of High and Medium BCS, upon the enforcement date of the new Standard.  However, since entities are explicitly not required to renegotiate existing contracts, it may be difficult to meet compliance with this requirement upon enforcement, if existing vendors do not provide appropriate support.

  • Measures and Evidence – Since the R3 requires an entity to show that documented processes have been implemented, M1 does not adequately describe the evidence required to demonstrate implementation. 

Aaron Ghodooshim, FirstEnergy - FirstEnergy Corporation, 3, 3/3/2017

- 0 - 0

Please refer to RSC- NPCC comments

Si Truc Phan, On Behalf of: Hydro-Qu?bec TransEnergie, NPCC, Segments 1

- 0 - 0

Support FirstEnergy Comments submitted by Aaron Ghodooshim – Segment 4). 

Aubrey Short, 3/3/2017

- 0 - 0

Suggest striking the word “associated” from the phrase “software, firmware, and associated patches”.

 

Basin Electric recommends adding language to address potential Technical Feasibility Exception (TFE) such as: 

R3. Each Responsible Entity shall implement one or more documented process(es) for verifying the integrity and authenticity of the following software and firmware, where technically feasible, before being placed in operation on high and medium impact BES Cyber Systems:

 

In R3.2, “Firmware” is already included in R3 which is redundant in R3.2.  Basin Electric recommends R3 be written as a general Requirement with specifics in the sub Requirements.

 

There are a lot of parallels between these requirements and the requirements already required in CIP-007 R2 patch management controls.  Basin Electric would rather see these obligations integrated into CIP-007.

 

The rationale explains the obligation for this requirement starts in the operate/maintain phase of the life cycle, but the timing/life cycle language is not included in requirement.   Basin Electric suggests modifying the requirement to include clarification of when the obligation starts.  Perhaps add language to the front of R3 such as:  “For Cyber Assets in production…”

Mike Kraft, 3/3/2017

- 0 - 0

  1. R3 creates confusion and possible double jeopardy with CIP-007 R2 and CIP-010 R4 part 1.4.4.  Recommend moving R3 into these Standards/Requirements. This modification to CIP-007 and CIP-010 addresses FERC order No. 829.

  2. How does the SDT propose that the responsible entity handle R3 for existing equipment when the vendor is out-of-business, is unable to cooperate, or is unwilling to cooperate? This equipment may have been purchased prior to the implementation of CIP-013 but not put in services until after the effective date. Recommend rewording this Requirement to allow exceptions for these situations.

Does R3 allow the Entity to “accept the risk?”

We are concerned that this requirement requires vendor cooperation or else it may not be possible to verify the integrity or authenticity of software and firmware provided by the vendor. Vendors do not fall under the jurisdiction of NERC.

  • Request “per system capability” wording for R3. Not all vendors provide a “golden hash” or other mechanism to validate.

  • To be consistent with not requiring R1.2.5 we suggest adding the language “subject to procurement contract.”

     

    To be consistent with not requiring R1.2.5, we suggest adding the language “subject to procurement contract.” There should be provisions to allow an entity to accept the risk of selecting a vendor that will not or cannot supply authentication.

Additionally,  R3 may hinder an entity’s ability to meet the 35-day patch window in CIP-007-6 R2.2 and R2.3. In the case of a non-cooperative vendor, entities will be left in a position of choosing to violate CIP-013, R3 or CIP-007, R2.

Is R3 the implementation of R.1.2.5? Should there be more explicit tie-ins? Seems to be in conflict with provision in R1 where “obtaining specific controls in the negotiated contract may not be feasible and is not considered failure to implement an entity’s plan”

We request clarification on relationships with resellers. Is verification of integrity and authenticity adequate from the reseller? Or does validation have to reach back to the original manufacturer?

 

Con Edison, Segment(s) 1, 3, 5, 6, 0, 6/24/2016

- 0 - 0

Seminole Electric comments submitted by Michael Haff

Michael Ward, 3/3/2017

- 0 - 0

OSI Open Systems International, On Behalf of: OSI Open Systems International, NA - Not Applicable, Segments NA - Not Applicable

- 0 - 0

See comments n Requirement R3 in attached file.

William Harris, 3/4/2017

Resilient Societies CIP 013-1 Comments 03042017.docx

- 0 - 0

N&ST strongly supports the goal of verifying software integrity and authenticity and hopes vendors will be generally willing to provide Responsible Entities with checksums, cyber hash values, or other integrity checks for their software and firmware. However, as written the requirement creates the potential for a conflict with CIP-007-6 R2 Part 2.3 (installation of applicable security updates), and could leave a Responsible Entity with potentially no recourse other than to create a mitigation plan if a vendor is for some reason unable or unwilling to provide such integrity verification for a patch or other type of software or firmware update. N&ST recommends that the SDT consider allowing for exceptions that must be (a) fully documented and (b) approved by the Responsible Entity’s CIP Senior Manager

Nicholas Lauriat, Network and Security Technologies, 1, 3/4/2017

- 0 - 0

We agree with the drafting team that verification to the integrity and authenticity of the software needs to be validated. However, we would ask the question, “If the industry finds validations issues, how do we hold the vendor accountable?” We understand that contracts are in place to help this situation, but this doesn’t always resolve validation issues. We feel that FERC Order 829 language falls short of holding the vendors accountable in reference to addressing verification of software integrity and authenticity and as a result, the compliance burden is placed on the users. The CIP requirements focus on the Responsible Entity carrying the compliance risk even if the industry can identify vendor validation issues.   For example, entities could potentially pay for product upgrades to address compliance concerns when it’s been verified that the current product upgrades have not met the quality of service that was promised by the vendor. We suggest that the drafting team hold open discussions with FERC, potentially conducting a gap analysis in reference to this potential concern. If the analysis determines a gap, FERC should seek legislation to hold vendors more accountable.

Also, we suggest that Requirement R3 language should be moved to the CIP-010 Standard. Our group feels that the CIP-010 Standard adequately addresses software and firmware verification. Additionally, we propose some language revisions to the Requirement language.

SPP’s proposed language revision to R3:

“Each Responsible Entity shall implement one or more documented process for verifying the integrity and authenticity of the following software and firmware before being installed in operation on high and medium impact BES Cyber Systems”.

The term “installed” has been consistently used throughout the CIP-010 Standard and we feel this will give our proposed language validity and consistency. 

SPP Standards Review Group, Segment(s) , 3/5/2017

- 0 - 0

Preston Walker, On Behalf of: PJM Interconnection, L.L.C., SERC, RF, Segments 2

- 0 - 0

We propose the SDT modify standard language based on Vectren's proposed language below:

R3:

             Each Responsible Entity shall implement one or more documented process(es) for reviewing the vendor process for integrity and verifying authenticity of the following software and firmware, where a verification method is available from the vendor, before being placed in operation on high and medium impact BES Cyber Systems: 

3.1  Operating System(s);

3.2  Firmware;

3.3  Commercially available or open-source application software; and

3.4  Patches, updates, and upgrades to 3.1 through 3.3.

Additionally, Vectren understands that due to the deadline for this standard there is not time for this now, but suggest that future revisions to the Supply Chain Risk Management standard, consider moving R3 to CIP-007 patching or possibly to CIP-010 change control to avoid "spaghetti" requirement as had existed prior to CIP V5. 

Consider that future revisions format CIP-013 into a table format similar to CIP-008 & CIP-009 for clarity.  Expanded comments could then be moved to Technical Guidance and Examples.

                            

In the event the SDT does not accept the above changes, Vectren asks the following comments be considered:

 

R3 - Concerns that not all vendor products will provide a method to check authenticity.  Concerning patching, Vectren questions the ability of the utility industry to influence the vendor's contracting language.  Please consider If EACMS and PACS are truly the intent of this standard.  What steps will need to be taken to verify vendor is ensuring integrity of their business partners?  Consider formatting CIP-013 into a table format similar to CIP-008 & CIP-009 for clarity.  Expanded comments could then be moved to Technical Guidance and Examples.  Integrity is process internal to the vendor.  Cannot verify integrity for each individual patch.

What does the SDT consider a "secure central software repository"?

- 0 - 0

It may not be possible to verify the integrity and authenticity of software and firmware before being placed into operation if the Vendor is no longer in business or will not cooperate.  There should either be an exception or ‘out’ for possibility (e.g. … where possible.), leaving that determination up to an audit team, or a feasibility exception should be allowed.

John Williams, 3/6/2017

- 2 - 0

The draft Requirement R3 language creates compliance concerns due to the need for Responsible Entities to negotiate commercial contracts with vendors that commit the vendors to undertake the tasks necessary for R3 compliance, particularly in circumstances where only a single vendor has the capability of providing the necessary services for Cyber Assets covered by CIP-013-1.  For example, unless the vendor agrees to cooperate with any software integrity and authenticity verification process, the Responsible Entity will be unable to ensure the integrity and authenticity of software used in covered Cyber Assets.

 Responsible Entities could encounter scenarios where:

•    Vendors may refuse to comply with the Responsible Entity’s vendor controls;

•    Vendors may demand an unreasonably high payment for compliance with the Responsible Entity’s vendor controls;

•    Vendors may agree to Responsible Entity controls but fail to take the steps necessary to implement those controls in a compliant manner; or

  • Software/firmware made by a vendor no longer in business and unable to assist the Responsible Entity in the integrity and authenticity verification process.

To ensure that compliance with CIP-013-1 does not place Responsible Entities in an untenable negotiating position, a compliance “safety valve” is necessary to allow Responsible Entities to comply with the Standard even in the absence of vendor assent to the Responsible Entity’s required controls.  Such a “safety valve” would be consistent with the current draft guidance on CIP-013-1 R1.2, which states that “[o]btaining specific controls in the negotiated contract may not be feasible and is not considered failure to implement an entity’s plan.” 

Guidance language in the G&TB portion of a Standard is helpful, but the “safety valve” concept should be included within the language of the Requirement itself because only that language forms the basis of a compliance assessment. 

Exelon has sent ideas under separate cover to the Drafting Team Chair outlining three options for providing the necessary “safety valve” along with proposed text edits to the requirements.  In short, these options include a technical feasibility exception, a commercial feasibility exception or a simple exception documentation process.

Exelon does not support the draft language in R3 which requires an Entity to verify the integrity and authenticity before placing a BES Cyber System into operation.  Instead, Exelon prefers the suggested language from Order No. 829 that directs “the integrity of the software and patches before they are installed in the BES Cyber System environment” (P. 48).  Accordingly, Exelon suggests that R3 be edited to read as follows:

Each Responsible Entity shall implement one or more documented process(es) for verifying the integrity and authenticity of the following software and firmware prior to installation into high and medium impact BES Cyber Systems

Daniel Gacek, Exelon, 1, 3/6/2017

- 0 - 0

Vectren proposes that the SDT modify standard language based on Vectren's proposed language below:

R3:

             Each Responsible Entity shall implement one or more documented process(es) for reviewing the vendor process for integrity and verifying authenticity of the following software and firmware, where a verification method is available from the vendor, before being placed in operation on high and medium impact BES Cyber Systems: 

3.1  Operating System(s);

3.2  Firmware;

3.3  Commercially available or open-source application software; and

3.4  Patches, updates, and upgrades to 3.1 through 3.3.

 

Additionally, Vectren understands that due to the deadline for this standard there is not time for this now, but suggest that for future revisions to the Supply Chain Risk Management standard, consider moving R3 to CIP-007 patching or possibly to CIP-010 change control to avoid "spaghetti" requirement as had existed prior to CIP V5. 

Consider that future revisions format CIP-013 into a table format similar to CIP-008 & CIP-009 for clarity.  Expanded comments could then be moved to Technical Guidance and Examples.

In the event the SDT does not accept the above changes, Vectren asks the following comments be considered:

R3 - Concerns that not all vendor products will provide a method to check authenticity.  Concerning patching, Vectren questions the ability of the utility industry to influence the vendor's contracting language.  Please consider If EACMS and PACS are truly the intent of this standard.  What steps will need to be taken to verify vendor is ensuring integrity of their business partners?  Consider formatting CIP-013 into a table format similar to CIP-008 & CIP-009 for clarity.  Expanded comments could then be moved to Technical Guidance and Examples.  Integrity is process internal to the vendor.  Cannot verify integrity for each individual patch.

What does the SDT consider a "secure central software repository"? 

 

Fred Frederick, 3/6/2017

- 0 - 0

Specific operational cyber security controls are best addressed as revisions to CIP-002 through -011.

 

Prescribing verification of integrity and authenticity is a “how” not a “what.”

 

Refer to EEI comments on R3. We agree with the concept of the EEI comments to consider a revision in CIP-010 for a specific security objective (“what”), such as “method(s) to minimize the risk of installing compromised” CIP-010 R1 baseline configuration items.

 

We recommend the CIP-013 SDT request NERC to assign the CIP revisions SDT to assist the CIP-013 team to draft the technical revisions for each of the four directives in CIP-002 through CIP-013.  The CIP revisions SDT has met their Order 822 directive that had a deadline. To get the best standards for reliability and meet the FERC Order 829 directives’ deadlines, NERC and industry should reprioritize SDT teams’ work and resources.

Darnez Gresham, Berkshire Hathaway Energy - MidAmerican Energy Co., 3, 3/6/2017

- 2 - 0

We propose the SDT modify standard language based on Vectren's proposed language below:

 

R3:

             Each Responsible Entity shall implement one or more documented process(es) for reviewing the vendor process for integrity and verifying authenticity of the following software and firmware, where a verification method is available from the vendor, before being placed in operation on high and medium impact BES Cyber Systems: 

3.1  Operating System(s);

3.2  Firmware;

3.3  Commercially available or open-source application software; and

3.4  Patches, updates, and upgrades to 3.1 through 3.3.

 

Additionally, Vectren understands that due to the deadline for this standard there is not time for this now, but suggest that future revisions to the Supply Chain Risk Management standard, consider moving R3 to CIP-007 patching or possibly to CIP-010 change control to avoid "spaghetti" requirement as had existed prior to CIP V5. 

Consider that future revisions format CIP-013 into a table format similar to CIP-008 & CIP-009 for clarity.  Expanded comments could then be moved to Technical Guidance and Examples.

                               

In the event the SDT does not accept the above changes, Vectren asks the following comments be considered:

 

 

R3 - Concerns that not all vendor products will provide a method to check authenticity.  Concerning patching, Vectren questions the ability of the utility industry to influence the vendor's contracting language.  Please consider If EACMS and PACS are truly the intent of this standard.  What steps will need to be taken to verify vendor is ensuring integrity of their business partners?  Consider formatting CIP-013 into a table format similar to CIP-008 & CIP-009 for clarity.  Expanded comments could then be moved to Technical Guidance and Examples.  Integrity is process internal to the vendor.  Cannot verify integrity for each individual patch.

What does the SDT consider a "secure central software repository"? 

Steve Rawlinson, 3/6/2017

- 0 - 0

  • Patch Management obligations for cyber security related patches are already addressed in CIP-007.  Dominion is of the opinion that the obligations in this requirement would be better placed (once it’s determined what the obligations should be) in CIP-010 or CIP-007.

  • If R3 is kept in CIP-013 and not moved to an existing CIP Standard, we recommend the following:

R3:  Each Responsible Entity shall implement one or more documented process(es) for verifying the integrity and authenticity of the following, prior to authorized installation on high and medium impact BES Cyber Systems and associated EACMSs, PCAs, and PACs:  [Violation Risk Factor: Medium] [Time Horizon: Operations Planning]

Sean Bodkin, Dominion - Dominion Resources, Inc., 6, 3/6/2017

- 0 - 0

NRG recommends that the R3 and R4 technical/operation control requirements should be located in the associated standard to avoid misalignments or jeopardizing timeframes outline in the other standards such as patch management.  For Example: R3 creates confusion and possible double jeopardy with CIP-007 R2 and CIP-010 R4 part 1.4.4. 

NRG requests clarification from SDT regarding what could/should an entity do if there is no process to verify the authenticity of software?  In those cases, can an entity document their defense in depth strategies as a compensating measure?   NRG recommends that SDT communicate in Measures that verification of authenticity could include a way to present in our processes other methods that may not actually be verification.

NRG recommends that SDT list ways that a Registered Entity can authenticate a source in the Measures section.  NRG also recommends that SDT list that a Registered Entity should have a means to use putty, Debian, or things that don’t have as tight of controls, (i.e. provide a checksum, and/or set a policy that they don’t use open source code and requests clarification of how a Registered Entity would demonstrate that they had verified an authoritative source (i.e. open source) to the extent of what their capability would allow). For example, NRG recommends that SDT list examples in Measures section to include use of a layered approach of security and functional testing: For example start with a notification process, authenticity check of source, and use hash / checksum, then perform testing (but how does testing demonstrate authenticity? Answer – virus scan, etc (functional vs. security testing: A/V scan, logging, access, control).  Lastly perform a scan from a vulnerability assessment tool.  How does this prove integrity and authenticity of the software? NRG requests clarification in the standard requirement of when this requirement would become effective.  NRG recommends that the SDT allow the Registered Entities additional time for vendor re-negotiations relating to supply chain for the purposes of enabling validation of integrity and authenticity of software and firmware. 

NRG suggests that the R3 language should move to CIP-010. NRG requests clarification of whether testing is a valid form of verification.  Additionally, we suggest the Requirement language to read as follows “Each Responsible Entity shall implement one or more documented process(es) for verifying the integrity and authenticity of the following software and firmware before being installed in operation on high and medium impact BES Cyber Systems”. Each requirement should have a provision that allows an entity to accept the risk of selection a vendor that will not or cannot supply a control.

Kara White, On Behalf of: NRG - NRG Energy, Inc., FRCC, MRO, WECC, Texas RE, NPCC, SERC, SPP RE, RF, Segments 3, 4, 5, 6

- 0 - 0

  1. R3 creates confusion and possible double jeopardy with CIP-007 R2 and CIP-010 R4 part 1.4.4.  Recommend moving R3 into these Standards/Requirements. This modification to CIP-007 and CIP-010 addresses FERC order No. 829.

  2. How does the SDT propose that the responsible entity handle R3 for existing equipment when the vendor is out-of-business, is unable to cooperate, or is unwilling to cooperate? This equipment may have been purchased prior to the implementation of CIP-013 but not put in services until after the effective date. Recommend rewording this Requirement to allow exceptions for these situations

  3. Request clarification (in the Standard) on how the SDT expects current and past contract negotiations to impact R3

Does R3 allow the Entity to “accept the risk?”

We are concerned that this requirement requires vendor cooperation or else it may not be possible to verify the integrity or authenticity of software and firmware provided by the vendor. Vendors do not fall under the jurisdiction of NERC.

  • Request “per system capability” wording for R3. Not all vendors provide a “golden hash” or other mechanism to validate.
  • To be consistent with not requiring R1.2.5, we suggest adding the language “subject to procurement contract.” There should be provisions to allow an entity to accept the risk of selecting a vendor that will not or cannot supply authentication.

4. Additionally, R3 may hinder an entity’s ability to meet the 35-day patch window in CIP-007-6 R2.2 and R2.3. In the case of a non-cooperative vendor, entities will be left in a position of choosing to violate CIP-013, R3 or CIP-007, R2.

5. Is R3 the implementation of R.1.2.5? Should there be more explicit tie-ins? Seems to be in conflict with provision in R1 where “obtaining specific controls in the negotiated contract may not be feasible and is not considered failure to implement an entity’s plan”

6. We request clarification on relationships with resellers. Is verification of integrity and authenticity adequate from the reseller? Or does validation have to reach back to the original manufacturer?

 

David Rivera, New York Power Authority, 3, 3/6/2017

- 0 - 0

Same as RoLynda Shumpert's comments from SCE&G:

SCE&G agrees with the concerns and questions raised by the Edison Electric Institute (EEI), including the following:

“Requirement R3 and the associated guidance is not sufficient to explain the security objective this requirement is trying to address and the difference between integrity and authenticity controls. For example, the language could allow a Responsible Entity to use a vendor’s website for verifying both integrity and authenticity, which will not protect against a Watering Hole attack, where the vendor’s website has been compromised and both the software and the integrity check are likely to be compromised. However, we note that the majority of vendors use their websites for software downloads and include the hashes for integrity checks on those websites. Members have had difficulty in getting vendors to change their practices, which makes this requirement difficult if not impossible for Responsible Entities to comply with…Verifying integrity and authenticity may also not be possible. This requirement should be about minimizing risk and recognize that the Responsible Entity may not be able to be verify that all risk has been eliminated, especially since the risk is from a third part, a vendor.”

Alyssa Hubbard, 3/6/2017

- 0 - 0

We propose the SDT modify standard language based on Vectren's proposed language below:

 

R3:

             Each Responsible Entity shall implement one or more documented process(es) for reviewing the vendor process for integrity and verifying authenticity of the following software and firmware, where a verification method is available from the vendor, before being placed in operation on high and medium impact BES Cyber Systems: 

3.1  Operating System(s);

3.2  Firmware;

3.3  Commercially available or open-source application software; and

3.4  Patches, updates, and upgrades to 3.1 through 3.3.

 

Additionally, Vectren understands that due to the deadline for this standard there is not time for this now, but suggest that future revisions to the Supply Chain Risk Management standard, consider moving R3 to CIP-007 patching or possibly to CIP-010 change control to avoid "spaghetti" requirement as had existed prior to CIP V5. 

Consider that future revisions format CIP-013 into a table format similar to CIP-008 & CIP-009 for clarity.  Expanded comments could then be moved to Technical Guidance and Examples.

                             

In the event the SDT does not accept the above changes, Vectren asks the following comments be considered:

 

 

R3 - Concerns that not all vendor products will provide a method to check authenticity.  Concerning patching, Vectren questions the ability of the utility industry to influence the vendor's contracting language.  Please consider If EACMS and PACS are truly the intent of this standard.  What steps will need to be taken to verify vendor is ensuring integrity of their business partners?  Consider formatting CIP-013 into a table format similar to CIP-008 & CIP-009 for clarity.  Expanded comments could then be moved to Technical Guidance and Examples.  Integrity is process internal to the vendor.  Cannot verify integrity for each individual patch.

What does the SDT consider a "secure central software repository"? 

 

Brad Lisembee, 3/6/2017

- 0 - 0

The California ISO supports the comments submitted by the ISO/RTO Council (IRC) and the Security Working Group (SWG)

Richard Vine, 3/6/2017

- 0 - 0

Entergy/NERC Compliance, Segment(s) 1, 5, 3/1/2017

- 0 - 0

1)      R3 creates confusion and possible double jeopardy with CIP-007 R2 and CIP-010 R4 part 1.4.4.  Recommend moving R3 into these Standards/Requirements. This modification to CIP-007 and CIP-010 addresses FERC order No. 829.

 

2)      How does the SDT propose that the responsible entity handle R3 for existing equipment when the vendor is out-of-business, is unable to cooperate, or is unwilling to cooperate? This equipment may have been purchased prior to the implementation of CIP-013 but not put in services until after the effective date. Recommend rewording this Requirement to allow exceptions for these situations

 

3)      Request clarification (in the Standard) on how the SDT expects current and past contract negotiations to impact R3

Quintin Lee, Eversource Energy, 1, 3/6/2017

- 0 - 0

R3 applies whether revised contract terms and conditions exist or not, with no exception for vendor capability issues, technical feasibility, or situations where there is no vendor. It is also not clear whether changes that are not firmware or software versions or patches fall under the requirement. CenterPoint Energy requests that the phrase “where technically feasible” be added to Requirement 3.  

Furthermore, the Company believes verifying software integrity and authenticity as described in CIP-013 R3 belong in CIP-010 and recommends aligning the R3 sub-requirements to match the items in CIP-010 R1. 

It is not clear what an entity must do if the vendor will not or cannot assist by providing an authentication method. Having a verification requirement for R3.4, where not automatically supported by vendors, slows down the existing patch management process. This increases security risks by leaving systems unpatched against known vulnerabilities for longer periods and increases compliance risks for entities where dated mitigation plans must be used to document delays.

Additionally, it is not clear whether secure boot capability, default on many Cyber Asset operating systems, is adequate (or even required) to demonstrate compliance with software verification requirement.

CenterPoint Energy recommends that R3 be revised for flexibility and feasibility. It should also be moved to CIP-010 as these requirements would seem to fit as a part of existing configuration change management processes.

Amelia Sawyer Anderson, On Behalf of: CenterPoint Energy Houston Electric, LLC, Texas RE, Segments 1

- 0 - 0

Nicolas Turcotte, Hydro-Qu?bec TransEnergie, 1, 3/6/2017

- 0 - 0

We agree with this in principal, but this requirement will be extremely difficult to implement and ensure compliance. Currently, numerous vendors do not provide digitally signed patches (Microsoft is notorious for this) or other hashes to verify that a file was not modified. The ability to verify 100% of all software and files will be impossible until vendors are required to implement digital signatures. This can be done via contracts, but it will take time. We highly recommend that the requirement be changed to allow for the fact that software may not be able to be verified and that as long as an entities process checks for this that it is still valid to install with risks.

DTE Energy - DTE Electric, Segment(s) 5, 4, 3, 2/27/2017

- 0 - 0

SCE&G agrees with the concerns and questions raised by the Edison Electric Institute (EEI), including the following:

“Requirement R3 and the associated guidance is not sufficient to explain the security objective this requirement is trying to address and the difference between integrity and authenticity controls. For example, the language could allow a Responsible Entity to use a vendor’s website for verifying both integrity and authenticity, which will not protect against a Watering Hole attack, where the vendor’s website has been compromised and both the software and the integrity check are likely to be compromised. However, we note that the majority of vendors use their websites for software downloads and include the hashes for integrity checks on those websites. Members have had difficulty in getting vendors to change their practices, which makes this requirement difficult if not impossible for Responsible Entities to comply with…Verifying integrity and authenticity may also not be possible. This requirement should be about minimizing risk and recognize that the Responsible Entity may not be able to be verify that all risk has been eliminated, especially since the risk is from a third part, a vendor.”

RoLynda Shumpert, On Behalf of: SCANA - South Carolina Electric and Gas Co., SERC, Segments 1, 3, 5, 6

- 0 - 0

I support the comments submitted by Brian Evans-Mongeon, Utility Services, Inc, and Marty Hostler, Northern California Power Agency.

Dennis Sismaet, Northern California Power Agency, 6, 3/6/2017

- 0 - 0

OUC requests that the scope of R3 be limited to high and medium BES Cyber Systems with ERC or Dial-up Connectivity in alignment with the approach in existing CIP-007 and CIP-010. 

Ballard Mutters, Orlando Utilities Commission, 3, 3/6/2017

- 0 - 0

CIP-013-1 Requirement R3 is written with an assumption that the supplier provides a mechanism in which verification of integrity and authenticity can be performed on software and firmware.  These tools/mechanism may not always be available to the Registered Entity, and the Registered Entity may not have the power in which to force the supplier to provide a verification method.  Consistent with currently approved and enforceable CIP Cyber Security Reliability Standards, ATC recommends the SDT consider adding language to provision for conditions where it is not technically possible to perform a verification in order to provide the flexibility needed to preclude an impossibility of achieving compliance.

Additionally, the inclusion of “firmware” within the proposed language in CIP-013-1 R3 is an expansion in scope from the first directive in FERC Order No. 829 (P.2), which directed NERC to draft a new or modified Reliability Standard that “…should address the following security objectives, discussed in detail below: (1) software integrity and authenticity; (2) vendor remote access; (3) information system planning; and (4) vendor risk management and procurement controls.” 

Additionally, CIP-013-1 Requirement R3 is simultaneously duplicative and additive with currently approved and enforceable CIP-010-2 Requirement R1 and the Applicable Systems within CIP-010-2 Requirement R1 Parts 1.1 – 1.5 as consequence of the broad reference to “high and medium impact BES Cyber Systems” without consideration of the construct of the CIP-010-2 Standard.

  1. CIP-013-1 Requirement R3 Sub Requirements R3.1 –  R3.4 are duplicative of CIP-010-2 Requirement R1 Parts 1.1 – 1.2, which obligates Registered Entities to develop and maintain a baseline of ‘software’ information for both high and medium impact BES Cyber Systems, where the types of software are effectively the same as what is being proposed.  

    • CIP-010-2 Requirement R1 Part 1.5 addresses the testing of changes to this ‘software’ and ‘firmware’ for high impact BES Cyber Systems, rendering Sub Requirement R3.1 – R3.4 superfluous and unnecessary.  Consequently, Requirement R3.1 – R3.4 also creates a condition of potential double jeopardy for existing approved and enforceable Standard CIP-010-2 Requirement R1 Part 1.5. In its redundancy, it is at odds with the former efforts associated to the FERC filing of proposed retired standards for Project 2013-02 Paragraph 81, and the intent to eliminate duplicative or unnecessary requirements that do not provide security or reliability value.

    • CIP-010-2 Requirement R1 Part 1.5 has a provision to allow for the testing of this software and firmware in production where it is not technically feasible to perform testing in a test environment.  CIP-013-1 R3 is effectively an expansion in scope to CIP-010-2 Requirement R1 Part 1.5 in its obligation to perform testing “…before being placed in operation on a high … …impact BES Cyber System”.  Any expansion in scope to access requirements or controls for high impact BES Cyber Systems as defined in the currently approved and enforceable Standard should be subject to the Standards Authorization Request, Development, Commenting, and Balloting Processes for CIP-010-2 so as not to be effectively revising an existing approved and enforceable Reliability Standard through the creation of a separate one.

    • CIP-010-2 Requirement R1 Part 1.5 is not applicable to medium impact BES Cyber Systems.  CIP-013-1 R3 is effectively an expansion in scope to CIP-010-2 Requirement R1 Part 1.5 in its obligation to perform testing “…before being placed in operation on a… …medium impact BES Cyber System”.  Any expansion in scope to access requirements or controls for medium impact BES Cyber Systems as defined in the currently approved and enforceable Standard should be subject to the Standards Authorization Request, Development, Commenting, and Balloting Processes for CIP-010-2 so as not to be effectively revising an existing approved and enforceable Reliability Standard through the creation of a separate one.

Lauren Price, 3/6/2017

- 0 - 0

CPS Energy supports the comments provided by ERCOT and APPA

Brian Bartos, On Behalf of: Brian Bartos, , Segments 1, 3, 5

- 0 - 0

Xcel Energy supports the comments filed by the Edison Electric Institute (EEI).

- 0 - 0

1.      We favor industry accepted methods to address software authenticity such as digital signatures that are consistent with other critical sectors.

Warren Cross, On Behalf of: ACES Power Marketing, MRO, WECC, Texas RE, SERC, SPP RE, Segments 1, 3, 4, 5

- 0 - 0

Though each of the objectives in Order 829 is addressed, Reclamation recommends a more simplified format for the requirements as the SDT originally suggested in the webinar on November 10, 2016.

 

Reclamation recommends Requirement R3 should instead require entities to review and update as necessary their supply chain risk management plan(s) developed in Requirement R1 at least once every 15 months.

 

Within each Requirement, the sub-requirements should distinguish between high, medium, and low impact BES Cyber Systems and other supporting systems. Reclamation recommends the implementation plan enforcement dates be staggered based on high, medium, and low impact for auditing purposes and to allow the associated risks and severity levels to be spelled out more clearly.

Wendy Kalidass, U.S. Bureau of Reclamation, 5, 3/6/2017

- 0 - 0

Rationale for Requirement R3:

The rationale language for R3 states, “The objective of verifying software integrity and authenticity is to ensure that the software being installed in the BES Cyber System was not modified without the awareness of the software supplier and is not counterfeit.” R1, R2, and the Rationale for Requirement R3 do not specify the impact classification (High, Medium and Low) when referencing the BES Cyber System. R3 specifically states the impact classification of the BES Cyber System “applicable to High and Medium Impact BES Cyber Systems.” IPC would like know if the inconsistent impact classification references were intended or were an oversight by the SDT.

R3

The requirement language for R3 states, “before being placed in operation on high and medium impact BES Cyber Systems.” R1, R2, and the Rationale for Requirement R3 do not specify the impact classification (High, Medium and Low) when referencing the BES Cyber System. R3 specifically states the impact classification of the BES Cyber System “applicable to High and Medium Impact BES Cyber Systems.” IPC would like know if the inconsistent impact classification references were intended or were an oversight by the SDT.

The requirement language for R3 states, “Each Responsible Entity shall implement one or more documented process(es) for verifying the integrity and authenticity of the following software and firmware." IPC is concerned that the SDT developed a standard that requires Responsible Entities to “verify the integrity and authenticity” of software and firmware of which Responsible Entities have no oversight or control over what each vendor provides. 

IPC does not feel CIP-013-1 is an appropriate standard to address R3. IPC believes this requirement belongs in CIP-007-6 or CIP-010-2 as R3 is related to patching or configuration change management. IPC feels the intent of CIP-013-1 is to address supply chain controls, whereas CIP-007-6 and CIP-010-2 address testing and verification of changes controls, which are typically performed by technical staff as they test, implement, and update systems.

Laura Nelson, 3/6/2017

- 0 - 0

Santee Cooper requests that the scope of R3 be limited to high and medium BES Cyber Systems with ERC or Dial-up Connectivity in alignment with the risk-based approach in existing CIP-007 and CIP-010.

Santee Cooper , Segment(s) 1, 5, 3/6/2017

- 0 - 0

LCRA supports ERCOT’s comments.  CIP-013 R3 directly impacts baseline data and as such should be located within CIP-010.

Teresa Krabe, Lower Colorado River Authority, 5, 3/6/2017

- 0 - 0

BPA proposes that to truly isolate the production systems from compromised software or firmware more prescriptive language than ‘before being placed in operation’ is required. BPA recommends the SDT develop language to address a supplier that is unwilling or able to support the requirement.

Aaron Cavanaugh, On Behalf of: Bonneville Power Administration, WECC, Segments 1, 3, 5, 6

- 0 - 0

AZPS notes that Requirement R3 requires documented processes for verifying the "integrity and authenticity" of software and firmware before being place into operation and that such language may result in redundant verifications and processes.  In particular, software, firmware, etc. are often verified when they are received from the vendor and “incubated” on low risk systems before being pushed to BES Cyber Systems.  To avoid the need to “re-verify” these updates after incubation, but prior to placement in production on BES Cyber Systems, AZPS requests the following change to Requirement R3,

‘…verifying the integrity and authenticity of the following software and firmware being placed in operation on high and medium impact BES Cyber Systems, when received’.  Additionally, Requirement R3 addresses the verification of integrity and authenticity of software and firmware; however, it does not address the likelihood of a vendor’s inability or unwillingness to comply.  AZPS requests clarification of whether an inability to verify would be considered a failure to implement the process if verification is not possible due to vendor inability or unwillingness.

Stephanie Little, 3/6/2017

- 0 - 0

1)      How does the SDT propose that the responsible entity handle R3 for existing equipment when the vendor is out-of-business or will not cooperate? This equipment may have been purchased prior to the implementation of CIP-013 but not put in services until after the effective date.

2)      The applicability of this requirement should be limited to high and medium impact BES Cyber Systems with external routable connectivity.  This would align the standard with the applicability and risk-based approach of CIP-007 and CIP-010. 

3)      Suggest changing the format of the standard to use Applicability Tables like those used in CIP-004 through CIP-011.

4)      Provide clarity for when a system is pre-loaded by a vendor and delivered to an entity. Is the entity required to verify software authenticity?  If a computer is purchased from Dell, can Dell provide authenticity for all of the firm ware that is part of the system but not directly manufactured by Dell;  i.e.  system bios, sound system, network adapter, video controller.

 

Nathan Mitchell, On Behalf of: Nathan Mitchell, , Segments 3, 4

- 0 - 0

CPS Energy supports the comments provided by ERCOT and APPA

Glenn Pressler, CPS Energy, 3, 3/6/2017

- 0 - 0

See EEI comments

Louis Guidry, 3/6/2017

- 0 - 0

PSEG agrees with the intent of this requirement, but has the following questions/recommendations below:

  • The way this requirement is written, it may not be possible to perform a technical verification of software integrity and authenticity. How does the standard drafting team expect registered entities to address this if it cannot be done in a technical manner?

  • Requirements R1 and R2 do not require the registered entity to go back and revise previous contracts. In order to comply with this requirement, R3, changes to past contracts / vendor service agreements may be required. Alignment is needed between R1, R2, and R3.  

PSEG REs, Segment(s) 5, 6, 3, 1, 3/6/2017

- 1 - 0

Colorado Springs Utilities (CSU) requests that the scope of R3 be limited to high and medium BES Cyber Systems with ERC or Dial-up Connectivity in alignment with the risk-based approach in existing CIP-007 and CIP-010. 

Colorado Springs Utilities, Segment(s) 5, 3, 1, 6, 5/6/2015

- 0 - 0

Within the Rationale, the word “ensure” is inappropriate. Even good controls do not “ensure” a desired outcome.  It should also state that “software being installed in the BES Cyber System was not modified or altered without the knowledge of the supplier AND the recipient or licensee.  Consider replacement of “ensure” with “confirm”.

 

R1. This requirement puts a substantial responsibility on the Responsible Entity without any authority or recourse if the vendor is unwilling or unable to agree. To address these concern, The IESO request that the SDT consider the use of provisional language to protect Responsible Entities such as use of a TFE. 

 

R1. The SDT should consider the use of “validate” instead of “verify” in this requirement.

 

R1. The SDT should address situations that are outside the usual upgrade and patch processes. This includes the obligations for signature updates, and where a vendor brings code onsite (binary or source code) that the entity is not allowed to review.

Leonard Kula, Independent Electricity System Operator, 2, 3/6/2017

- 0 - 0

Seattle City Light requests that the scope of R3 be limited to high and medium BES Cyber Systems with ERC or Dial-up Connectivity in alignment with the risk-based approach in existing CIP-007 and CIP-010. 

Seattle City Light Ballot Body, Segment(s) 1, 4, 6, 5, 3, 12/2/2016

- 0 - 0

FEUS supports the comments submitted by APPA

Linda Jacobson-Quinn, City of Farmington, 3, 3/6/2017

- 0 - 0

FMPA agrees with comments submitted by American Public Power Association.

FMPA, Segment(s) , 12/5/2016

- 0 - 0

Jay Barnett, 3/6/2017

- 0 - 0

We recommend the SDT address virtualization and CIP Exceptional Circumstance with respect to this requirement aligned with project 2016-02. 

Also please see our earlier comments with regards to redundancy between R3 and R1.2.5.

Payam Farahbakhsh, Hydro One Networks, Inc., 1, 3/6/2017

- 0 - 0

The NYPA Comments

Erick Barrios, 3/6/2017

- 0 - 0

 

SMUD requests that the scope of R3 be limited to high and medium BES Cyber Systems with ERC or Dial-up Connectivity in alignment with the approach in existing CIP-007 and CIP-010. 

 

- 0 - 0

Security Objective

Requirement R3 and the associated guidance is not sufficient to explain the security objective this requirement is trying to address and the difference between integrity and authenticity controls.

The authenticity verification is already addressed in the procurement and vendor risk assessment process. Based on the vendor provided information in 1.1.5, 1.2 should identify the method or source to obtain the software that provides reasonable assurance of the authenticity of the vendor provided software.

Methods to minimize the integrity risk is determined based on the vendor and Responsible Entity’s capability and could include hash verification, vendor program review with acceptable assurance of good SDLC process and defined distribution source, through operational and security testing of software in test environment prior to installation on applicable assets, etc.

We recommend the following language for consideration by the SDT:

R3.  Prior to installing new (1) operating systems(s); (2) firmware; (3) commercially available or open-source application software; and (4) patches, updates and upgrades to these, use one or more documented method(s) to minimize the risk of adversely or unintentionally modified software.

Requirement Placement (CIP-010)

Requirement R3 may also fit better within CIP-010 (e.g., after R3, Part 3.3) since it is more of an operational security control. However, the security objective for this requirement is focused on risk the vendor may introduce by delivering software that has been altered before or during transit to the Responsible Entity so keeping it in a separate, supply chain standard may also make sense. Also, to implement R3, Responsible Entities will likely need to work with the vendor during procurement (R1 and R2) to ensure that they can meet R3.

Verifying integrity and authenticity may also not be possible. This requirement should be about minimizing risk and recognize that the Responsible Entity may not be able to be verify that all risk has been eliminated, especially since the risk is from a third party, a vendor.  

Melanie Seader, On Behalf of: Edison Electric Institute, NA - Not Applicable, Segments NA - Not Applicable

- 1 - 0

Tacoma concurs with the comments provided by the LPPC.

Marc Donaldson, Tacoma Public Utilities (Tacoma, WA), 3, 3/6/2017

- 0 - 0

- 0 - 0

    SDG&E agrees with EEI comments and proposed language.  Furthermore, operational checks to verify security controls are not adversely affected are covered in other CIP standards. 

  

Jeff Johnson, On Behalf of: Sempra - San Diego Gas and Electric, WECC, Segments 1, 2, 3, 4, 5, 6, 7

- 0 - 0

 LCRA supports ERCOT’s comments.  CIP-013 R3 directly impacts baseline data and as such should be located within CIP-010.

 

- 0 - 0

Requirement R3 and the associated guidance is not sufficient to explain the security objective this requirement is trying to address and the difference between integrity and authenticity controls.

 

The authenticity verification is already addressed in the procurement and vendor risk assessment process. Based on the vendor provided information in 1.1.5, 1.2 should identify the method or source to obtain the software that provides reasonable assurance of the authenticity of the vendor provided software.

 

Methods to minimize the integrity risk is determined based on the vendor and Responsible Entity’s capability and could include hash verification, vendor program review with acceptable assurance of good SDLC process and defined distribution source, through operational and security testing of software in test environment prior to installation on applicable assets, etc.

 

We recommend the following language for consideration by the SDT:

 

R3.  Prior to installing new (1) operating systems(s); (2) firmware; (3) commercially available or open-source application software; and (4) patches, updates and upgrades to these, use one or more documented method(s) to minimize the risk of adversely or unintentionally modified software.

 

Requirement Placement (CIP-010)

 

Requirement R3 may also fit better within CIP-010 (e.g., after R3, Part 3.3) since it is more of an operational security control. However, the security objective for this requirement is focused on risk the vendor may introduce by delivering software that has been altered before or during transit to the Responsible Entity so keeping it in a separate, supply chain standard may also make sense. Also, to implement R3, Responsible Entities will likely need to work with the vendor during procurement (R1 and R2) to ensure that they can meet R3.

 

Verifying integrity and authenticity may also not be possible. This requirement should be about minimizing risk and recognize that the Responsible Entity may not be able to be verify that all risk has been eliminated, especially since the risk is from a third party, a vendor.

William Wenz, On Behalf of: AES - Dayton Power and Light Co., RF, Segments NA - Not Applicable

- 0 - 0

Within the Rationale, the word “ensure” is inappropriate. Even good controls do not “ensure” a desired outcome.  It should also state that “software being installed in the BES Cyber System was not modified or altered without the knowledge of the supplier AND the recipient or licensee.  Consider replacement of “ensure” with “confirm”.

R1. This requirement puts a substantial responsibility on the Responsible Entity without any authority or recourse if the vendor is unwilling or unable to agree. To address these concern, The IRC and SWG request that the SDT consider the use of provisional language to protect Responsible Entities such as use of a TFE. 

R1. The SDT should consider the use of “validate” instead of “verify” in this requirement.

R1. The SDT should address situations that are outside the usual upgrade and patch processes. This includes the obligations for signature updates, and where a vendor brings code onsite (binary or source code) that the entity is not allowed to review.

IRC-SRC, Segment(s) 2, 11/18/2016

- 0 - 0

Requirement R3 and the associated guidance is not sufficient to explain the security objective this requirement is trying to address and the difference between integrity and authenticity controls.

 

The authenticity verification is already addressed in the procurement and vendor risk assessment process. Based on the vendor provided information in 1.1.5, 1.2 should identify the method or source to obtain the software that provides reasonable assurance of the authenticity of the vendor provided software.

 

Methods to minimize the integrity risk is determined based on the vendor and Responsible Entity’s capability and could include hash verification, vendor program review with acceptable assurance of good SDLC process and defined distribution source, through operational and security testing of software in test environment prior to installation on applicable assets, etc.

 

We recommend the following language for consideration by the SDT:

 

R3.  Prior to installing new (1) operating systems(s); (2) firmware; (3) commercially available or open-source application software; and (4) patches, updates and upgrades to these, use one or more documented method(s) to minimize the risk of adversely or unintentionally modified software.

 

Requirement Placement (CIP-010)

 

Requirement R3 may also fit better within CIP-010 (e.g., after R3, Part 3.3) since it is more of an operational security control. However, the security objective for this requirement is focused on risk the vendor may introduce by delivering software that has been altered before or during transit to the Responsible Entity so keeping it in a separate, supply chain standard may also make sense. Also, to implement R3, Responsible Entities will likely need to work with the vendor during procurement (R1 and R2) to ensure that they can meet R3.

 

Verifying integrity and authenticity may also not be possible. This requirement should be about minimizing risk and recognize that the Responsible Entity may not be able to be verify that all risk has been eliminated, especially since the risk is from a third party, a vendor.

William Wenz, On Behalf of: AES - Dayton Power and Light Co., RF, Segments NA - Not Applicable

- 0 - 0

GTC disagrees with the proposed requirement.  CIP-013-1 R3 requires actions to be taken by the Responsible Entity that are outside of the supply chain context.  Paragraph 45 of Order No. 829, specifies this objective of software integrity and authenticity should be applied to “The Plan” identified in the core directive in the context of addressing supply chain management risks.  The SDT has chosen to identify controls in R3 that are executed only as part of the day-to-day management of BES Cyber Systems.  These controls fail to effectively address the security objective of addressing software integrity and authenticity, will have minimal security value, are administratively burdensome on industry, and are inconsistent with the supply chain context.  SAFECode’s (http://www.safecode.org/publication/SAFECode_Software_Integrity_Controls0610.pdf) Software Integrity Control’s whitepaper outlines controls that effectively address software integrity and authenticity.  Nearly all of these controls must be implemented by the vendor.  As such, Responsible Entity’s should have the flexibility to require the vendor to provide software assurance through contractual means.  Such as “supplier provides customer ways to differentiate genuine from counterfeit software”

 

Unfortunately, the SDT has not provided controls that effectively address software integrity and authenticity and has instead focused its control as demonstrated by the language in the measure on ensuring the “entity performed the actions.”  In order to provide entities the flexibility to effectively address the security risks associated with the supply chain, we respectfully request that the SDT revise its draft standard to be more in line with the framework identified in FERC Order 829.  Our recommendation, consistent with our response to question 1, is as follows

 

GTC recommends the SDT reconsider relocating the attributes of R3 in a manner that addresses the security objective to “The Plan” specified in R1 to align with the FERC Order.  This would allow the Responsible Entity to handle contractually with the vendor i.e. “supplier provides customer ways to differentiate genuine from counterfeit software (such as digital signatures)”.  Our recommendation is consistent with our response to question 1, which is summarized as follows:

 

See GTC’s comment for Question #1.

Upon close review of FERC’s directives summarized beginning on paragraph 43 through paragraph 62, the Order essentially directs this new Standard as outlined:

 

Paragraphs 43 – 45:

R1:  Develop a plan to include security controls for supply chain management that address controls for mitigating Supply Chain risks to hardware, software, and computing and networking services which are intended to support Bulk Electric System operations; that include the following four specific security objectives in the context of addressing supply chain management risks:

R1.1 Security objective 3 (information system planning)

R1.2 Security objective 4 (vendor risk management and procurement controls)

R1.3 Security objective 1 (software integrity and authenticity)

R1.4 Security objective 2 (vendor remote access)

 

Paragraph 43:

              R2: Implement the plan specified in R1 in a forward looking manner.

 

Paragraphs 46 - 47:

R3: Review and update, as necessary its supply chain cyber security risk management plan(s) specified in R1 at least once every 15 calendar months

R3.1 Evaluation of revisions…

R3.2 Obtaining CIP Senior Manager or delegate approval.

 

Paragraphs 48 – 50:

FERC prescribes the various ways to address the first objective to the plan.

Paragraphs 51 – 55:

FERC prescribes the various ways to address the second objective to the plan.

Paragraphs 56 – 58:

FERC prescribes the various ways to address the third objective to the plan.

Paragraphs 59 – 62:

FERC prescribes the various ways to address the fourth objective to the plan.

 

FERC goes on to respond to comments on Existing CIP Reliability Standards, beginning with paragraph 71, “while we recognize that existing CIP Reliability Standards include requirements that address aspects of supply chain management, we determine that existing Reliability Standards do not adequately protect against supply chain risks that are within a responsible entity’s control. Specifically, we find that existing CIP Reliability Standards do not provide adequate protection for the four aspects of supply chain risk management that underlie the four objectives for a new or modified Reliability Standard discussed above.”  FERC summary continues to focus on CIP-013-1 being limited to aspects of supply chain risk management.

Jason Snodgrass, 3/6/2017

- 0 - 0

The NERC Entity is the customer of the hardware supplier and software supplier, not the designer, manufacturer and developer of what is being procured.  As such, the Entity can only clearly state what they want the hardware and software to do – at a high level, likely derived from what the vendor said there product could do, along with the expectation that the product will be “bug free”.  But the Entity should not be expected to have the expertise and tools to “verify the integrity and authenticity of software and firmware”.  Integrity and authenticity can only be assured by each link backwards in the Supply Chain, and collectively that will only happen if each link of the Supply Chain agrees to control their link.  CIP-013 is not in a position to impose those controls on the entire Supply Chain, but only on the end customer - NERC Registered Entity.   That said, software and firmware should be expected to be checked for proper "functionality" by the Registered Entity, per past CIP practice.

Bob Case, On Behalf of: Black Hills Corporation, WECC, Segments 1, 3, 5, 6

- 0 - 0

Refer to CSU comments.

Devin Elverdi, 3/6/2017

- 0 - 0

See comments submitted by Black Hills Corporation

Maryanne Darling-Reich, 3/6/2017

- 0 - 0

This Standard, and therefore this Requirement needs to be squarely focused on the vendor product or service being procured and not on the categorization of a BES Cyber System.  Requirement R3 should not be limited to High and Medium Impact BES Cyber Systems.  A SEL-421 is a SEL-421 and the same risks of procurement, including firmware updates, apply to all SEL-421s impacted regardless of where they are deployed.  Software/firmware updates are often acquired once and widely deployed.  This is especially true in the substation environment where the exact same firmware release will be used to update Medium and Low Impact relays.

Bob Reynolds, On Behalf of: Bob Reynolds, , Segments 10

- 0 - 0

Avista supports the comments filed by the Edison Electric Institute (EEI).

- 0 - 0

1)      R3 creates confusion and possible double jeopardy with CIP-007 R2 and CIP-010 R4 part 1.4.4.  Recommend moving R3 into these Standards/Requirements. This modification to CIP-007 and CIP-010 addresses FERC order No. 829.

 

2)      How does the SDT propose that the responsible entity handle R3 for existing equipment when the vendor is out-of-business, is unable to cooperate, or is unwilling to cooperate? This equipment may have been purchased prior to the implementation of CIP-013 but not put in services until after the effective date. Recommend rewording this Requirement to allow exceptions for these situations

 

3)      Request clarification (in the Standard) on how the SDT expects current and past contract negotiations to impact R3

 

Does R3 allow the Entity to “accept the risk?”

We are concerned that this requirement requires vendor cooperation or else it may not be possible to verify the integrity or authenticity of software and firmware provided by the vendor. Vendors do not fall under the jurisdiction of NERC.

 

·         Request “per system capability” wording for R3. Not all vendors provide a “golden hash” or other mechanism to validate.

·         To be consistent with not requiring R1.2.5 we suggest adding the language “subject to procurement contract.”

 

To be consistent with not requiring R1.2.5, we suggest adding the language “subject to procurement contract.” There should be provisions to allow an entity to accept the risk of selecting a vendor that will not or cannot supply authentication.

 

Additionally, R3 may hinder an entity’s ability to meet the 35-day patch window in CIP-007-6 R2.2 and R2.3. In the case of a non-cooperative vendor, entities will be left in a position of choosing to violate CIP-013, R3 or CIP-007, R2.

 

Is R3 the implementation of R.1.2.5? Should there be more explicit tie-ins? Seems to be in conflict with provision in R1 where “obtaining specific controls in the negotiated contract may not be feasible and is not considered failure to implement an entity’s plan”

 

We request clarification on relationships with resellers. Is verification of integrity and authenticity adequate from the reseller? Or does validation have to reach back to the original manufacturer?

 

RSC no Dominion and NextEra, Segment(s) 1, 0, 2, 4, 5, 6, 7, 3, 3/6/2017

- 0 - 0

For a smaller CIP applicable medium impact BES Cyber System, we apply between 5,000 and 7,000 patches a year. The only feasible means for us to apply any meaningful integrity check is through automated, cryptographic mechanisms. This is a good practice, which should be followed, but we haven’t found a good adoption rate by the Vendors developing the software.  Even still, authenticity controls do very little without better software development lifecycle controls in place by the vendor. Additionally, the poor record of Certificate Authorities to control certificate validation should be raised.

The cost of putting a process like this in place involves a heavily centralized procurement team and the time to research a large number of vendor practices pertaining to verification. We do not believe the risk reduction justifies this very costly requirement. We propose meeting the FERC directive through R1 and dropping this Requirement altogether.

Philip Huff, On Behalf of: Philip Huff, , Segments 3, 4, 5, 6

- 0 - 0

See Black Hills Corp comments

George Tatar, 3/6/2017

- 0 - 0

The NERC Entity is the customer of the hardware supplier and software supplier, not the designer, manufacturer and developer.  As such the Entity can only clearly state what they want the hardware and software to do – at a high level, likely derived from what the vendor said it could do, plus expecting that it will be “bug free”.  But the Entity should not be expected to have the expertise and tools to “verify the integrity and authenticity of software and firmware” – that is required to be ensured by each step back in the Supply Chain, and that will only happen if each link of the Supply Chain agrees to control their link.  CIP-013 is not in a position to impose those controls on the Supply Chain, but only on the end customer.   Software and firmware should be expected to be checked for functionality by the Entity.

Wes Wingen, 3/6/2017

- 0 - 0

We generally agree with EEI’s comments, except for the exclusion of EACMS, PACs and PCAs for Requirement 1.

Jamie Monette, Allete - Minnesota Power, Inc., 1, 3/6/2017

- 0 - 0

SunPower believes this Requirement is already covered in CIP-007. Having a CIP-013 requirement, that if violated, opens the door to double jeopardy (a finding in CIP-013 would also lead to a finding in CIP-007). There is no need for this Requirement. If there are additional requirements that must be identified, then CIP-013 is not the place for it, CIP-007 is a more appropriate place.

Bradley Collard, 3/6/2017

- 0 - 0

Kansas City Power and Light Company incorporates by reference Edison Electric Institute’s comments to Question 3. In addition, we offer the following comments:

Ambiguous Language – “integrity” and “authenticity”

The crux of the Requirement is to develop and implement plan(s) that address verification of the “integrity” and “authenticity” of operating systems, firmware, open-source software, and certain patches and upgrades prior to use. Without defining or providing a framework as to what “integrity” and “authenticity” mean, the terms are not measurable for CMEP purposes.

We suggest the Requirement include language that points to established and accepted security frameworks and standards. We offer the following alternative language:

R3. Each Responsible Entity shall manage its Cyber Asset Systems supply chain informed by well-established and accepted cyber security frameworks and standards for verifying the integrity and authenticity of the following software and firmware before being placed in operation on high and medium impact BES Cyber Systems:

Douglas Webb, 3/6/2017

- 0 - 0

N/A

Oxy, Segment(s) 7, 5, 9/6/2016

- 0 - 0

Heather Morgan, EDP Renewables North America LLC, 5, 3/6/2017

- 0 - 0

Sergio Banuelos, On Behalf of: Tri-State G and T Association, Inc., MRO, WECC, Segments 1, 3, 5

- 0 - 0

Concur with EEI’s Position

Linsey Ray , 3/6/2017

- 0 - 0

see APPA's comments, with which SVP agrees.

Val Ridad, On Behalf of: Silicon Valley Power, WECC, Segments 1

- 0 - 0

R3 – line 2 – for clarity purposes NRECA recommends removing “software and firmware.”

Additionally, to the extent possible, NRECA recommends that this requirement should be incorporated into CIP-007 R2 or CIP-010 R1.  This is a System Security Management requirement and belongs in the appropriate location.  CIP-013-1 and R3.1-R3.4 are all components of the CIP-010 baseline.  Placing this topic in a separate standard and requirement creates compliance confusion.

Barry Lawson, 3/6/2017

- 0 - 0

Scott Downey, 3/6/2017

- 0 - 0

EPE shares the comments and concerns voiced by the Edison Electric Institute (EEI) in this Ballot #1.  Please refer to the EEI ballot for detailed comments on each of the proposed requirements. 

 

In addition, the concerns expressed by EPE in response to Requirement 1 with respect to the proposed verification requirements also applies with respect to Requirement 3.  Requiring a Responsible Entity to have a process to address verification is different from making a Responsible Entity responsible for software and firmware verification.  EPE has had experiences in the past where the developers/vendors of software products provided to EPE products that they considered authentic and to have integrity.  EPE’s testing in a strong test environment (before the products were placed in service) did not reveal any errors, yet, as the products were placed in service, errors were revealed that could not be explained by the software developers themselves.  Under the new standard, as worded currently, would this experience create an instance of noncompliance?  If so, how would a Responsible Entity avoid being noncompliant in a situation in which the product vendor created the product and still could not predict or explain the error?

 

As EEI explains in its comments,  methods to minimize the integrity risk is determined based on the vendor and Responsible Entity’s capability, and could include hash verification, vendor program review with acceptable assurance of good SDLC process and defined distribution source, through operational and security testing of software in a test environment prior to installation on applicable assets, etc.  If a Responsible Entity may satisfy its compliance responsibilities for integrity verification through such methods, the requirement should be recrafted with language that makes this clear to the Responsible Entity.

 

 

Luis Rodriguez, El Paso Electric Company, 6, 3/6/2017

- 0 - 0

EPE shares the comments and concerns voiced by the Edison Electric Institute (EEI) in this Ballot #1.  Please refer to the EEI ballot for detailed comments on each of the proposed requirements. 

 

In addition, the concerns expressed by EPE in response to Requirement 1 with respect to the proposed verification requirements also applies with respect to Requirement 3.  Requiring a Responsible Entity to have a process to address verification is different from making a Responsible Entity responsible for software and firmware verification.  EPE has had experiences in the past where the developers/vendors of software products provided to EPE products that they considered authentic and to have integrity.  EPE’s testing in a strong test environment (before the products were placed in service) did not reveal any errors, yet, as the products were placed in service, errors were revealed that could not be explained by the software developers themselves.  Under the new standard, as worded currently, would this experience create an instance of noncompliance?  If so, how would a Responsible Entity avoid being noncompliant in a situation in which the product vendor created the product and still could not predict or explain the error?

 

As EEI explains in its comments,  methods to minimize the integrity risk is determined based on the vendor and Responsible Entity’s capability, and could include hash verification, vendor program review with acceptable assurance of good SDLC process and defined distribution source, through operational and security testing of software in a test environment prior to installation on applicable assets, etc.  If a Responsible Entity may satisfy its compliance responsibilities for integrity verification through such methods, the requirement should be recrafted with language that makes this clear to the Responsible Entity.

Pablo Onate, El Paso Electric Company, 1, 3/6/2017

- 0 - 0

We don’t believe it is reasonable to expect entities to be able to “verify” the integrity and authenticity of software and firmware in all cases.  We can attempt to minimize the risk and/or provide reasonable assurance that we have received what was intended.  There also needs to be a recognition of the many varied ways that updates and installations of software and firmware might be done most effectively, including the use of automated solutions.

Luminant, Segment(s) 6, 7, 5, 1/24/2017

- 1 - 0

EPE shares the comments and concerns voiced by the Edison Electric Institute (EEI) in this Ballot #1.  Please refer to the EEI ballot for detailed comments on each of the proposed requirements. 

 

In addition, the concerns expressed by EPE in response to Requirement 1 with respect to the proposed verification requirements also applies with respect to Requirement 3.  Requiring a Responsible Entity to have a process to address verification is different from making a Responsible Entity responsible for software and firmware verification.  EPE has had experiences in the past where the developers/vendors of software products provided to EPE products that they considered authentic and to have integrity.  EPE’s testing in a strong test environment (before the products were placed in service) did not reveal any errors, yet, as the products were placed in service, errors were revealed that could not be explained by the software developers themselves.  Under the new standard, as worded currently, would this experience create an instance of noncompliance?  If so, how would a Responsible Entity avoid being noncompliant in a situation in which the product vendor created the product and still could not predict or explain the error?

 

As EEI explains in its comments,  methods to minimize the integrity risk is determined based on the vendor and Responsible Entity’s capability, and could include hash verification, vendor program review with acceptable assurance of good SDLC process and defined distribution source, through operational and security testing of software in a test environment prior to installation on applicable assets, etc.  If a Responsible Entity may satisfy its compliance responsibilities for integrity verification through such methods, the requirement should be recrafted with language that makes this clear to the Responsible Entity.

Victor Garzon, 3/6/2017

- 0 - 0

Scott Kinney, Avista - Avista Corporation, 3, 3/6/2017

- 0 - 0

ERCOT supports the IRC comments on this question and offers the following supplemental comments.

 

ERCOT recognizes the need for the concepts contained in Requirement R3.  However, ERCOT disagrees with the placement of the requirement in a new standard. Since this requirement is applicable to only high and medium impact BES Cyber Systems, it should be placed within CIP-010. The requirement directly impacts the baselines that have been established within CIP-010 R1. The SDT could insert a new part between existing Parts 1.1 and 1.2 in that standard. The new part could use the following language: “For any updates or patches that that deviate from the existing baseline configuration, verify the authenticity and integrity of the update or patch.” As mentioned previously, in developing the CIP Version 5 standards, the SDT performed extensive work to ensure that all requirements related to a particular subject were included in one standard instead of being spread across multiple standards. The proposed language will disrupt that framework. Including the requirement in CIP-010 will ensure that a single standard captures all parts of the change process, including inventory (Part 1.1), validation of the code (NEW), authorization of implementation (Part 1.2), update of the inventory (Part 1.3), and testing of the change (Parts 1.4 and 1.5). This approach would give Responsible Entities a complete view of what is required from the start to the end of a change. It also prevents entities from keeping separate inventories to meet the CIP-010 requirement and the CIP-013 requirement.

 

Additionally, ERCOT requests guidance on how to demonstrate compliance when using automated solutions to obtain the most current patches applicable to their systems. In large environments, these automated solutions are critical to meeting the timing obligations of CIP-007 R2. Inserting the manual step of verifying integrity and authenticity of updates and patches can prevent the use of these solutions that entities have invested in and rely upon for addressing security risks and regulatory obligations. If it is intended that the entity may simply document the source used by these solutions, it would be helpful to put such clarifying language in the requirement.

 

Additional use cases for the SDT to consider in developing guidance include: (1) how signature and pattern updates are contemplated within the requirement since these are not updates to the operating system, software, or firmware noted, (2) instances when code is packaged and mailed to an entity, (3) software and firmware that are part of a vendor black-box type of appliance solution where the entity has no visibility to the code on the device, and (4) vendors bringing code onsite that the entity is not allowed to review.  Any of these cases could present an obstacle to strict compliance with the draft standard language.

 

As with Requirement R1, this requirement puts a substantial responsibility on the Responsible Entity without any authority or recourse if the vendor is unwilling or unable to agree. The drafting team should address situations in which vendors will not or cannot provided the levels of service mandated by this requirement. To address the concern, the drafting team should include a limited exemption from compliance, such as a Technical Feasibility Exception (TFE), which would protect Responsible Entities in the event a vendor is unwilling to agree to the terms otherwise required by R3.  NERC’s Appendix 4D to the Rules of Procedure provides for a basis of approval of a TFE beyond strict technical limitations of a system.  (See Section 3.0 of the appendix.) 

Elizabeth Axson, 3/6/2017

- 0 - 0

Hot Answers

- 0 - 0

Southern Company strongly disagrees with the direction the proposed R4 requirement is taking, while recognizing the time constraints placed on the SDT to file a new or modified Standard addressing Supply Chain risks.  As currently drafted, R4 carries significant overlap and repetition with existing CIP Standards, specifically with CIP-004-6 R4, CIP-005-5 R1, CIP-007-6 R4, and CIP-008-5 R2.  “Authorization of remote access” should be deleted because in no way can you circumvent CIP-004-6 R4.1 requiring authorization of remote access to a high or medium impact BES Cyber System and there is no need to replicate that requirement again in this Standard.  Additionally, CIP-005 R1.3 requires explicit access permissions and documented business justifications for all ‘system-to-system’ access, including vendor-initiated access.  With respect to “logging and monitoring”, and the detection of “unauthorized activity”, we have serious concerns over the proposed language and provide that CIP-005-5 R1.5 already requires the detection of inbound and outbound malicious communications, CIP-007-6 R4 already requires the logging and controlling of access at each ESP boundary and to BES Cyber Systems, and CIP-008-5 R2 already requires response to detected Cyber Security Incidents, which includes unauthorized activity during a vendor remote access session.  As drafted, a failure to comply with R4 could place a Responsible Entity in possible double jeopardy with those other requirements.  Additionally, as written, R4 creates a scope expansion of the existing CIP-005-5 R1.5 currently applicable to High Impact BES Cyber Systems and Medium Impact BES Cyber Systems at Control Centers to now ropes in all Medium Impact BES Cyber Systems – leaving entities (and auditors) to determine “which Standard wins?”  

 

Based on those concerns, Southern Company recommends the complete removal of R4 from the Standard, and where additional controls not already covered in an existing Standard are directed in the FERC Order, those controls should be covered under “the plan(s)” under R1 in a similar manner as the proposed edits provided under R1.

 

If R4 is not removed in this manner, we provide the below edits for consideration with the following comments.  In addition to the justified removal of “authorization of remote access”, logging and controlling are achievable concepts due to their requirement under existing Standards and therefore should not be required again here in this Standard and removed.  This leaves “methods to disable remote access sessions”, which we propose moving under the main R4 for the applicable scenarios.  Again, detecting and responding to “unauthorized activity” is already required under existing Standards, and should be removed from R4.  If not removed, the SDT must address the discrepancy between the scope collision between the draft R4 and CIP-005-5 R1.5. 

 

Additionally, if there is an expectation beyond the use of IDS/IPS for “detecting unauthorized activity”, then we would argue that it is nearly impossible for an entity to look at a stream of 1’s and 0’s flowing by at a several megabits per second and determine whether there is “unauthorized activity” or not in that stream.  With the difficulty in determining “unauthorized activity” in a stream of bits flying by, we respectfully recommend striking this and request the SDT to consider focusing the controls in this requirement specifically to having methods to rapidly “disable remote access” to prevent remote control of entity assets. 

 

Modify R4 language as follows:

 

R4. Each Responsible Entity shall implement one or more documented process(es) for controlling vendor remote access to high and medium impact BES Cyber Systems. The process(es) shall address methods to disable remote access sessions for (i) vendor-initiated Interactive Remote Access and (ii) system-to-system remote access with a vendor(s).  [Violation Risk Factor: Medium] [Time Horizon: Operations Planning]

Southern Company, Segment(s) 1, 3, 5, 6, 8/3/2016

- 0 - 0

Other Answers

Dennis Minton, 1/19/2017

- 0 - 0

Dennis Minton, 1/19/2017

- 0 - 0

Dennis Minton, 1/19/2017

- 0 - 0

Dennis Minton, 1/19/2017

- 0 - 0

Tom Anthony, On Behalf of: Tom Anthony, , Segments 1, 3

- 0 - 0

Tom Anthony, On Behalf of: Tom Anthony, , Segments 1, 3

- 0 - 0

Glen Farmer, Avista - Avista Corporation, 5, 2/6/2017

- 0 - 0

Russel Mountjoy, 2/24/2017

- 0 - 0

The NSRF believes the following items will cause double jeopardy if there is a non-compliance action with the proposed R4:

 R4, Part 4.1 is duplicative with CIP-004-6 R4, Part 4.1

                        R4, Part 4.2 is duplicative with CIP-007-6 R4, Part 4.1

                        R4, P4.3 should be taken care of by complying with CIP-005-5.  Part 1.3 of CIP-005-5 requires inbound and outbound access permissions which prevent unauthorized activity.

Remove “disable or other responding” and replace with “Response”. Leave the options for response with the Register Entity.

MRO NSRF, Segment(s) 1, 2, 3, 4, 5, 6, 2/24/2017

- 1 - 0

The standard as written doesn’t clearly address the objectives as listed in its Requirements. It also creates confusion and possible double jeopardy with other CIP Standards.

faranak sarbaz, Los Angeles Department of Water and Power, 1, 2/27/2017

- 0 - 0

Richard Kinas, 2/28/2017

- 0 - 0

R1.2.6 is duplicative of R4.  These requirements should be made consistent, or one of them should be deleted.

Much of R4 is already covered by CIP-005 (R1 and R2), CIP-007 (R4) and CIP-008.  Requirements for a single topic should be consolidated within a single standard.

Donald Lock, 2/28/2017

- 0 - 0

See APPA's, TAP's, and USI's comments.

Marty Hostler, Northern California Power Agency, 4, 2/28/2017

- 0 - 0

R4 is applicable to all BES Cyber Systems and, as applicable, EACMS PACS and PCA.  The philosophy used by preceding CIP standard drafting teams has been to write any requirements for low impact BES Cyber Systems in Attachment 1 of CIP-003 R2.  AEP believes this is a practice that results in a greater potential for compliance of all Responsible Entities.  AEP recommends that the essence of R1 be rewritten to address the lower risk associated with low impact BES Cyber Systems and moved to CIP-003 R2 Attachment 1.  In addition, CIP-013-1 R4 should be rewritten to be only applicable to high and medium impact BES Cyber Systems.

Thomas Foltz, AEP, 5, 3/2/2017

- 0 - 0

This appears to meet the FERC directive.

Rachel Coyne, Texas Reliability Entity, Inc., 10, 3/2/2017

- 0 - 0

Mike Smith, Manitoba Hydro , 3, 3/2/2017

- 0 - 0

This risk should be evaluated during the procurement and deployment of vendor products and services (CIP-013-1 R1), and mitigated as part of the CIP-005 R2, CIP-004 R4, and CIP-007 R4.

 

IID feels that there should be an exclusion comparable to a CIP Exceptional Circumstance (or Technical Feasibility Exception) added to this requirement for situations where the vendor does not cooperate or is otherwise unavailable.

 

Jesus Sammy Alcaraz, Imperial Irrigation District, 1, 3/2/2017

- 0 - 0

Please consider consolidation of R4 requirements into CIP-005 instead of a separate requirement to assist REs who may utilized shared processes and systems for providing Interactive Remote Access, regardless of the origin of the remote access.

Tennessee Valley Authority, Segment(s) 1, 3, 5, 6, 9/1/2016

- 0 - 0

Eric Ruskamp, Lincoln Electric System, 6, 3/2/2017

- 0 - 0

Deborah VanDeventer, On Behalf of: Edison International - Southern California Edison Company, WECC, Segments 1, 3, 5, 6

- 0 - 0

Please refer to comments submitted by Deborah VanDeventer on behalf of Southern California Edison.

Romel Aquino, Edison International - Southern California Edison Company, 3, 3/2/2017

- 0 - 0

Duke Energy recommends that the drafting team consider creating a definition for the terms “vendor” and “unauthorized activity”. Without clear expectations as to what is considered unauthorized activity, and further technical guidance on how to detect this type of activity, the Responsible Entity will not be able to determine what to look for to comply with R4.2, and will not know when to disable this activity to comply with R4.3.

We request further clarification from the drafting team on what is meant by “vendor-initiated Interactive Remote Access”. Does this refer to access that originates from a non-Responsible Entity system? Also, does “remote access” apply in the instance where a non-Responsible Entity party accesses a BES Cyber System remotely to the ESP, but is originating on a network inside of the Responsible Entity’s infrastructure? Should the requirement language be revised to better categorize remote access as “external” remote access originating from a location that is not a Responsible Entity’s facility or location?

Duke Energy , Segment(s) 1, 5, 6, 4/10/2014

- 0 - 0

 

  1. The rationale section in Requirement R4 speaks to “machine-to-machine vendor remote access” while the actual requirement speaks to “system-to-system remote access with a vendor”.  ReliabilityFirst recommends the SDT use consistent language so that there is no confusion on terminology or definitions.

  2. Requirement R4 mentions high and medium BES Cyber Systems, but does not include their associated Electronic Access Control and Monitoring Systems (EACMs), Physical Access Controls(PACS), and Protected Cyber Assets (PCAs).  ReliabilityFirst offers the following modifications for consideration:

    1. Each Responsible Entity shall implement one or more documented process(es) for controlling vendor remote access to high and medium impact BES Cyber Systems [and if applicable, associated Electronic Access Control or Monitoring Systems, Physical Access Control Systems, and Protected Cyber Assets]. The process(es) shall provide the following for (i) vendor-initiated Interactive Remote Access and (ii) system-to-system remote access with a vendor(s): [Violation Risk Factor: Medium] [Time Horizon: Operations Planning]

Anthony Jablonski, ReliabilityFirst , 10, 3/3/2017

- 0 - 0

We request confirmation that vendor access does not include onsite staff augmentation contract resources.  Clarification is also requested on whether “system to system” access applies to access that is “one-way” where the remote end conducts only monitoring activity and no control is possible.  Can the procedure for access make distinctions for each method of monitoring each type of access, Interactive Remote, system to system with control and system to system for monitoring only? Finally, the term “unauthorized activity” is unclear.  We recommend using the term “unauthorized access”.

PPL NERC Registered Affiliates, Segment(s) 3, 1, 5, 6, 2/9/2017

- 1 - 0

See NPCC comments.

ALAN ADAMSON, New York State Reliability Council, 10, 3/3/2017

- 0 - 0

Please refer to comments submitted by Deborah VanDeventer on behalf of Southern California Edison

Thomas Rafferty, 3/3/2017

- 0 - 0

AECI supports the following comments from the MRO NSRF:

“The NSRF believes the following items will cause double jeopardy if there is a non-compliance action with the proposed R4:

R4, Part 4.1 is duplicative with CIP-004-6 R4, Part 4.1

R4, Part 4.2 is duplicative with CIP-007-6 R4, Part 4.1

R4, P4.3 should be taken care of by complying with CIP-005-5.  Part 1.3 of CIP-005-5 requires inbound and outbound access permissions which prevent unauthorized activity.”

Furthermore, AECI contends that the SDT should remove this requirement and address vendor remote access in the implementation of the supply chain risk management plan(s) as detailed in the requirement concepts proposed by AECI in Question 1.  This concept will allow Responsible Entities to address the issue contractually with applicable vendors.

Mark Riley, Associated Electric Cooperative, Inc., 1, 3/3/2017

- 0 - 0

CHPD requests that the scope of R4 be limited to high and medium BES Cyber Systems with ERC or Dial-up Connectivity as these systems have the highest risk associated with remote access.

Elements of R4 (authorization, logging/monitoring) appear duplicative of existing CIP requirements.  CHPD requests that the scope of R4 be limited to disabling remote access.

For R4.3, the phrase “during remote access” does not seem to align with the “timely manners” guidance given on page 15, line 23 of the Technical Guidance and Examples document. The capability to disable during the remote access session may not always be possible and would be dependent on how the unauthorized activity was detected. CHPD requests changing the language to “upon detected unauthorized activity”.

Mick Neshem, 3/3/2017

- 0 - 0

PRPA requests that the scope of R4 be limited to high and medium BES Cyber Systems with ERC or Dial-up Connectivity as these systems have the highest risk associated with remote access.

Elements of R4 (authorization, logging/monitoring) appear duplicative of existing CIP requirements.  PRPA requests that the scope of R4 be limited to disabling remote access.

For R4.3, the phrase “during remote access” does not seem to align with the “timely manners” guidance given on page 15, line 23 of the Technical Guidance and Examples document. The capability to disable during the remote access session may not always be possible and would be dependent on how the unauthorized activity was detected. PRPA requests changing the language to “upon detected unauthorized activity”.

Tyson Archie, Platte River Power Authority, 5, 3/3/2017

- 1 - 0

Please refer to comments submitted by Deborah VanDeventer on behalf of Southern California Edison.

Steven Mavis, 3/3/2017

- 0 - 0

AE requests that the scope of R4 be limited to high and medium BES Cyber Systems with ERC or Dial-up Connectivity as these systems have the highest risk associated with remote access.

Elements of R4 (authorization, logging/monitoring) appear duplicative of existing CIP requirements.  AE requests that the scope of R4 be limited to disabling remote access.

For R4.3, the phrase “during remote access” does not seem to align with the “timely manners” guidance given on page 15, line 23 of the Technical Guidance and Examples document. The capability to disable during the remote access session may not always be possible and would be dependent on how the unauthorized activity was detected. AE requests changing the language to “upon detected unauthorized activity”.

Andrew Gallo, 3/3/2017

- 1 - 0

  1. R4 creates confusion and possible double jeopardy with other standards. Recommend modifying modify CIP-005 R2 , CIP-007 R4 Subpart 4.1.5 and/or CIP-008 R1 part 1.6 address the FERC order No. 829.

  2. Recommend that this Rationale needs to be updated from “machine-to-machine” to “system-to-system” for consistency

  3. The first sentence of R2 is broader than the second sentence. The first sentence is “Each Responsible Entity shall implement one or more documented process(es) for controlling vendor remote access to high and medium impact BES Cyber Systems.” The second sentence is “The process(es) shall provide the following for (i) vendor-initiated Interactive Remote Access and (ii) system-to-system remote access with a vendor(s):“  Recommend that the first sentence needs to be consistent with the Order  and reference vendor-initiated remote access and not vendor remote access.

  4. Request guidance. “Vendor-Initiated” could be considered a single word and not associated with the proposed definition of “vendor”.

     

  5. Recommend changing R4.3, from “Disabling or otherwise responding to unauthorized activity during remote access sessions“ to “Disabling or otherwise responding to detected unauthorized activity.“

  6. For R4.3, the “during remote access” does not seem to align with the “timely manners” guidance given on page 15, line 23   of the Guidance and Examples document. This capability to disable during the remote access session may not always be possible and would be dependent on how the unauthorized activity was detected. Suggest changing to “detected unauthorized activity”.

  7. Suggest changing the format of the standard to use Applicability Tables like those used in CIP-004 through CIP-011.

Brian Evans-Mongeon, Utility Services, Inc., 4, 3/3/2017

- 0 - 0

CHPD requests that the scope of R4 be limited to high and medium BES Cyber Systems with ERC or Dial-up Connectivity as these systems have the highest risk associated with remote access.

 

Elements of R4 (authorization, logging/monitoring) appear duplicative of existing CIP requirements.  CHPD requests that the scope of R4 be limited to disabling remote access.

 

For R4.3, the phrase “during remote access” does not seem to align with the “timely manners” guidance given on page 15, line 23 of the Technical Guidance and Examples document. The capability to disable during the remote access session may not always be possible and would be dependent on how the unauthorized activity was detected. CHPD requests changing the language to “upon detected unauthorized activity”.

Janis Weddle, 3/3/2017

- 0 - 0

CHPD requests that the scope of R4 be limited to high and medium BES Cyber Systems with ERC or Dial-up Connectivity as these systems have the highest risk associated with remote access.

Elements of R4 (authorization, logging/monitoring) appear duplicative of existing CIP requirements.  CHPD requests that the scope of R4 be limited to disabling remote access.

For R4.3, the phrase “during remote access” does not seem to align with the “timely manners” guidance given on page 15, line 23 of the Technical Guidance and Examples document. The capability to disable during the remote access session may not always be possible and would be dependent on how the unauthorized activity was detected. CHPD requests changing the language to “upon detected unauthorized activity”.

Haley Sousa, 3/3/2017

- 0 - 0

Jeanie Doty, 3/3/2017

- 0 - 0

I support the comments of Andrew Gallo at Austin Energy.

W. Dwayne Preston, 3/3/2017

- 0 - 0

We agree with the LPPC/APPA comments.

JEA Voters, Segment(s) , 3/3/2017

- 0 - 0

While in overall agreement with this Requirement R4, ACEC would recommend the following change:

1.  Move Requirement 1, Part 1.2.2, "Process(es) for notification when vendor employee remote or onsite access should no longer be granted" and Part 1.2.6 "Coordination of remote access controls for (i) vendor-initiated Interactive Remote Access and (ii) system-to-system remote access with a vendor(s)" to Requirement R4 since this requirement is where Vendor Remote  Access is addressed.

Alan Farmer, On Behalf of: ACEC/Burns & McDonnell, NA - Not Applicable, Segments NA - Not Applicable

- 0 - 0

CIP-013 R4.1 is duplicative of CIP-004 R4.3 as all persons already require authorization of electronic access to the systems in scope of this requirement.  As entities will have to follow duplicate requirements in two different standards, CIP-004 and CIP-013, there is an increased likelihood of a violation.

CIP-013 R4.2, Logging, monitoring, and alerting is already covered in CIP-007 R4.1 and R4.2.  An additional requirement part in CIP-007 R4 would be the most effective place to meet this FERC expectation.  As entities will have to follow duplicate requirements in two different standards, CIP-007 and CIP-013, there is an increased likelihood of a violation.

CIP-013 R4.3 would be handled best as a component of CIP-007 R4 for detected inappropriate access.  Alerting is already required by CIP-007 R4.2 and a simple additional step (requirement part) would require a response to the alert.  The guidelines and technical basis should discuss use of intrusion prevention systems to meet this requirement without requiring significant additional compliance evidence.

Michael Haff, On Behalf of: Seminole Electric Cooperative, Inc., FRCC, Segments 1, 3, 4, 5, 6

- 0 - 0

CHPD requests that the scope of R4 be limited to high and medium BES Cyber Systems with ERC or Dial-up Connectivity as these systems have the highest risk associated with remote access.

 

Elements of R4 (authorization, logging/monitoring) appear duplicative of existing CIP requirements.  CHPD requests that the scope of R4 be limited to disabling remote access.

 

For R4.3, the phrase “during remote access” does not seem to align with the “timely manners” guidance given on page 15, line 23 of the Technical Guidance and Examples document. The capability to disable during the remote access session may not always be possible and would be dependent on how the unauthorized activity was detected. CHPD requests changing the language to “upon detected unauthorized activity”.

Chad Bowman, 3/3/2017

- 0 - 0

SRP requests that the scope of R4 be limited to high and medium BES Cyber Systems with ERC or Dial-up Connectivity as these systems have the highest risk associated with remote access.

 

Elements of R4 (authorization, logging/monitoring) appear duplicative of existing CIP requirements.  SRP requests that the scope of R4 be limited to disabling remote access.

For R4.3, the phrase “during remote access” does not seem to align with the “timely manners” guidance given on page 15, line 23 of the Technical Guidance and Examples document. The capability to disable during the remote access session may not always be possible and would be dependent on how the unauthorized activity was detected. SRP requests changing the language to “upon detected unauthorized activity”.

Lona Calderon, On Behalf of: Salt River Project, WECC, Segments 1, 3, 5, 6

- 1 - 0

Please refer to comments submitted by Deborah VanDeventer on behalf of Southern California Edison

Kenya Streeter, Edison International - Southern California Edison Company, 6, 3/3/2017

- 0 - 0

R4 could give entities the impression that they do not need to follow the CIP-005-5 R2 controls for Interactive Remote Access. If an entity did not leverage its existing Interactive Remote Access (CIP-005-5 R2) processes to support this Requirement, WECC is concerned that separate vendor remote access processes may provide additional ingress/egress points into the ESP. An entity should ensure that vendor remote processes are protected at least to the level of CIP-005-5 R2. At no point in time, should there ever be an unmonitored connection into a BCS. This is something that is totally under the control of the entity. Even if the vendor includes a "phone-home" feature on a system or application, the ingress and egress of that connection should still be monitored and controlled by the entity to minimize the risk of third-party penetration into the BCS. The SCRM team should work closely with the CIP-005-5 team to ensure all remote access connections are managed, monitored, and controlled through an Electronic Access Control and Monitoring System [EACMS] and/or Intermediate System [IS]

Steven Rueckert, Western Electricity Coordinating Council, 10, 3/3/2017

- 0 - 0

John Hagen, 3/3/2017

- 0 - 0

  • The scope of CIP-013-1 R4 appears to overlap with parts of CIP-005-5R1.3, R1.5, R2.1 - 2.3; and CIP-007 R4.1, R4.2, R5.7.  (Both of the CIP-007 and CIP-005 requirements apply to High and Medium BCS and associated EACMS, PACs, and PCAs).  However, the logging and monitoring requirements in CIP-007-6 R4.1, 4.2 specifically cite “per Cyber Asset capability” and “after-the-fact investigations.” 

    • Additionally, the CIP-013 requirement indicates “Disabling or otherwise responding to unauthorized activity during remote access sessions.”  Not all technologies would have the capability of real-time cyber asset level user activity monitoring, needed to detect activity and disable sessions.

    • CIP-013 R4 does not consider the variability of cyber asset capability.  Not all technologies can support cyber asset level logging.

  • A definition of “unauthorized activity” is needed.  Note: existing processes in CIP-004 establish authorized activity for vendors, contractors, and employees, including: training, PRA, and access management.  Security controls in CIP-005 and CIP-007 enforce the limits of those authorizations.  Vendors who are granted specific access rights to remotely access systems are, by definition, authorized to perform certain functions.  Jump-hosts, firewalls, user accounts, and application privileges already limit activity to permitted activity.

  • “Machine-to-machine vendor remote access” should be defined, or the formal definition of “Interactive Remote Access” should be modified to include machine access.

  • “Monitoring” should be defined.  Suggested clarification is that monitoring includes information regarding the startup and termination of the connection, but does not include the capturing of user activity during the session.

Aaron Ghodooshim, FirstEnergy - FirstEnergy Corporation, 3, 3/3/2017

- 0 - 0

Please refer to RSC- NPCC comments

Si Truc Phan, On Behalf of: Hydro-Qu?bec TransEnergie, NPCC, Segments 1

- 0 - 0

Support FirstEnergy Comments submitted by Aaron Ghodooshim – Segment 4). 

Aubrey Short, 3/3/2017

- 0 - 0

R4 appears to be in parallel to requirements that already exist in CIP-004, CIP-005, CIP-007 and CIP-008.  Basin Electric would prefer the requirements be integrated with the existing standards.

 

 

Basin Electric believes the following items will cause double jeopardy if there is a non-compliance action with the proposed R4:

R4, Part 4.1 is duplicative with CIP-004-6 R4, Part 4.1

R4, Part 4.2 is duplicative with CIP-007-6 R4, Part 4.1

R4, Part 4.3 should be taken care of by complying with CIP-005-5 Part 1.3 which requires inbound and outbound access permissions which prevent unauthorized activity.

R4, Part 4.3 “otherwise responding” should be taken care of by complying with CIP-008-5 R2.

 

In the context of R1–R3, the term “vendor” appears to apply to a company as stated in the rationale section.  In context of R4, the same term “vendor” now appears to mean individual personnel who represent a company.  Clarity is needed on who this requirement actually applies to. 

Mike Kraft, 3/3/2017

- 0 - 0

R4 creates confusion and possible double jeopardy with other standards. Recommend moving R4 into the following Standards/Requirements CIP-005 R2, CIP-007 R4 Subpart 4.1.5 and/or CIP-008 R1 part 1.6 to address FERC order No. 829.

The phrase “during remote access” does not seem to align with the “timely manners” guidance given on page 15, line 23   of the Guidance and Examples document. This capability to disable during the remote access session may not always be possible and would be dependent on how the unauthorized activity was detected.

Consider eliminating sub requirements 4.1 and 4.2 since they are covered in CIP-005 and CIP-007, R5 respectively. Consider addressing sub requirement 4.3 by modifying CIP-005 thus eliminating R4 from the proposed CIP-013 standard.

R4 should be moved to CIP-005 since this requirement, as written in CIP-013, only applies to vendors having remote access. This does not address other sources of remote access threats as written.

After moving to CIP-005, R4.2 should be revised to say: “Capability to detect unauthorized activity; and”

R4.3 should add the word “detected” before the term “unauthorized activity.”

For R4.2, we suggest limiting the retention period for evidence logs to 90 days to be consistent with CIP-007 R4, Parts 4.1, 4.2, and 4.3.

This would increase the scope of file integrity monitoring to Medium impact devices, some which are not capable of logging. This would discourage entities from allowing vendors to ever log in remotely, which might hinder reliability in the case of required emergency troubleshooting/support. Lack of timely support would also force entities to be non-compliant with other standards, such as other CIPs.

Remove vendor remote access from scope and only include system-to-system. Vendor remote access is already addressed in CIP-005 R2.

Suggest that this Rationale needs to be updated from “machine-to-machine” to “system-to-system.”

SDT appears to be building on top of CIP-005 R1.5; however, R4.3 says “during the remote access session,” which may not reasonable amount of time since this is a real-time action.

Con Edison, Segment(s) 1, 3, 5, 6, 0, 6/24/2016

- 0 - 0

Seminole Electric comments submitted by Michael Haff

Michael Ward, 3/3/2017

- 0 - 0

OSI Open Systems International, On Behalf of: OSI Open Systems International, NA - Not Applicable, Segments NA - Not Applicable

- 0 - 0

See Comments on Requirement R4 in attached file.

William Harris, 3/4/2017

Resilient Societies CIP 013-1 Comments 03042017.docx

- 0 - 0

Authorization of remote access to BES Cyber Systems (Part 4.1) is already addressed by CIP-004-6 R4 for user-initiated remote access and implicitly by CIP-005-5 R1 Part 1.3 (“Require inbound and outbound access permissions, including the reason for granting access, and deny all other access by default.”) for machine-to-machine access. It should be deleted.

Nicholas Lauriat, Network and Security Technologies, 1, 3/4/2017

- 0 - 0

We suggest that Requirement R4 Section 4.1 language be moved to the CIP-004 Standard. The group feels that CIP-004 Part 4.1 already handles access controls in that particular Cyber Standard. Additionally, we feel that a potential conflict may exist between CIP-013 Requirement R4 and CIP-004 Requirement R4 if this Requirement stays in its current position.

As for Section 4.2 language being moved to the CIP-007 Standard, our group feels that the CIP-007 Standard already addresses logging.

Finally, we suggest moving Section 4.3 Language to the CIP-005 Standard because, we feel that the CIP-005 Standard already addresses interactive access to BES Cyber Systems.

SPP Standards Review Group, Segment(s) , 3/5/2017

- 0 - 0

Preston Walker, On Behalf of: PJM Interconnection, L.L.C., SERC, RF, Segments 2

- 0 - 0

We propose the SDT modify standard language based on Vectren's proposed language below:

 R4.

             Each Responsible Entity shall implement one or more documented process(es) for controlling vendor remote access to high and medium impact BES Cyber Systems. The process(es) shall provide the following for (i) vendor-initiated Interactive Remote Access and (ii) machine-to-machine remote access with a vendor(s): 

4.1  Authorization of remote access by the Responsible Entity;

4.2  Log and review vendor remote access;

4.3  Disabling or otherwise responding to unauthorized access during remote access sessions.

 

Consider removing R4 and refer to CIP-005 R2 regarding Interactive Remote Access.  If this is not an option, Vectren offers the following suggestions:

Consider defining system-to-system access (is this aka machine-to-machine)?   See page 13 of Technical Guidance and Examples, paragraph #9. 

Consider direct application access servers, such as those that deliver anti-virus signature updates, are not considered in scope.

Consider defining “unauthorized activity” if that is not changed to “unauthorized access”.

For future consideration, format CIP-013 into a table format similar to CIP-008 & CIP-009 for clarity.  Expanded comments could then be moved to Technical Guidance and Examples.

 

In the event the SDT does not accept the above changes, Vectren asks the following comments be considered:

 

R4

This requirement is too broad to implement or audit and, therefore, outweighs the purpose of the regulatory efforts.  Same question as in R1.2.6 concerning anti-virus signature updates.  Unauthorized activity is not defined.  This is open to interpretation such as to include a user opening files they should not be viewing, or looking at settings that are not related to the task at hand.  This could also be interpreted that we must monitor every move, such as monitoring only through a WebEx while the vendor is accessing the system.  Auditor could interpret this in many ways.

- 0 - 0

This seems not to be a supply-chain issue.  It would seem that NERC’s intent is to wrap-up order 829 into a single standard instead of modifying the existing standards (CIP-005 Requirement 2), where necessary, to address these weaknesses.

There should most definitely be a feasibility exception with respect to 4.2 and 4.3.

What does ‘during remote access sessions’ mean in 4.3?  If the session is active, it would be prudent to expect immediate termination of the connection as the Guidance suggests – responding in a timely manner.  Termination during a remote access session could imply a normal, or ‘timed’ termination of the connection, long after an intended response to unauthorized activity would ordinarily occur.

John Williams, 3/6/2017

- 2 - 0

The proposed Requirement creates significant overlap with existing CIP Requirements.  Requirement R4, as well as Requirements R3 and R5, should be modified so that CIP-013 only addresses those aspects of software integrity and authenticity (R3), remote access (R4), and authenticity and remote access for low impact BES Cyber Systems (R5) not covered by other Standards.  Exelon understands that the timeframe dictated by FERC in Order No. 829 does not allow for revisions by this SDT to the relevant Standards that address these topics.  However, overlap between the Standards should be avoided as much as possible to avoid double jeopardy concerns in the event of potential non-compliance with CIP-013 R3, R4, and R5. 

For example, Exelon’s review of the draft CIP-013-1 Standard indicates the following areas of overlap:

•    CIP-013-1 R3.1 through R3.4 require authentication of operating systems, firmware, software, and patches.  However, the configuration change management requirements under CIP-010-2 R1 already require that the configuration of operating systems, firmware, and software be carefully tracked such that counterfeit operating systems, firmware, software, and patches would be identified (e.g. a software difference would be identified as a change from the existing baseline configuration) and would be evaluated. 

•    CIP-013-1 R3.4 requires authentication of patches, updates, and upgrades, but CIP-007-6 R2.1 already imposes a patch management process for tracking, evaluating, and installing cyber security patches, including the identification of patching sources.  Part of the identification of patching sources under CIP-007-6 is the verification that those sources are authentic as CIP-013-1 R3.4 would appear to require. 

•    CIP-013-1 R4.1 requires authorization of remote access to certain BES Cyber Systems by the vendor.  CIP-004-5 R4.1.1 already contains a process for authorizing electronic access to these assets by all personnel, including vendors. 

•    CIP-013-1 R4.2 requires logging and monitoring or remote access sessions.  CIP-007-6 R4.1 already requires logging of all access and CIP-007-6 R4.2 requires alerting for any malicious code as well as any “security ecent that the Responsible Entity determines necessitates an alert.” 

•    CIP-013-1 R4.3 also requires responding to detected unauthorized activity, and because unauthorized activity on a BES Cyber System would constitute a “Cyber Security Incident,” CIP-008-5 already requires a response to such incidents. 

•    CIP-013-1 R5 requires a process for controlling vendor remote access to low impact BES Cyber Systems.  This overlaps with CIP-003-6 Attachment 1 Section 3 which already requires electronic access controls for low impact BES Cyber Systems the limit access to necessary access. 

The draft CIP-013-1 requirements should be modified so that overlaps are removed and that CIP-013-1 only addresses vendor issues not covered within existing Standards.  To the extent the SDT believes there is no overlap between CIP-013 and the existing CIP Standards, the SDT should explain in each instance where the CIP-013 Requirement ends and the other CIP Requirement begins.  In the absence of such guidance, a Compliance Monitoring and Enforcement Process could conclude that a particular instance of non-compliance with CIP-013 is also a simultaneous violation of another Reliability Standard, doubling the available penalty range.  For example, draft CIP-013-1 R4 requires the Responsible Entity to authorize remote access by vendor personnel.  The current CIP-004-6 R4.1.1 also requires authorization of vendor personnel to have electronic access.  Therefore noncompliance with CIP-013-1 R4 would appear to, per se, constitute noncompliance with CIP-004-6 R4.1.1.  Such double jeopardy serves no apparent reliability purpose.  If the current CIP-013-1 R4 language is adopted as-is, the SDT should explain how its requirements differ from those under CIP-004-6 R4.1.1.     

Finally, Exelon suggests that R4.3 may be difficult to accomplish in all cases and is overly prescriptive and thus should be removed from CIP-013.  Order No. 829, P.52 references the Ukraine event and the threat that “vendor credentials could be stolen and used to access a BES Cyber System without the responsible entity’s knowledge, as well as the threat that a compromise at a trusted vendor could traverse over an unmonitored connection into a responsible entity’s BES Cyber System.”  There are alternate methods to address this threat.  First, two factor identification methods can be used to mitigate the risk of stolen credentials.  Second, the use of WebEx or Skype sessions or active control of vendor access (i.e. opening a port for access only when needed) can be used to address emergent issues and reduce the need for remote persistent sessions.

 

Daniel Gacek, Exelon, 1, 3/6/2017

- 0 - 0

Vectren proposes that the SDT modify standard language based on Vectren's proposed language below:

 

R4.

             Each Responsible Entity shall implement one or more documented process(es) for controlling vendor remote access to high and medium impact BES Cyber Systems. The process(es) shall provide the following for (i) vendor-initiated Interactive Remote Access and (ii) machine-to-machine remote access with a vendor(s): 

4.1  Authorization of remote access by the Responsible Entity;

4.2  Log and review vendor remote access;

4.3  Disabling or otherwise responding to unauthorized access during remote access sessions.

 

Consider removing R4 and refer to CIP-005 R2 regarding Interactive Remote Access.  If this is not an option, Vectren offers the following suggestions:

Consider defining system-to-system access (is this aka machine-to-machine)?   See page 13 of Technical Guidance and Examples, paragraph #9. 

Consider direct application access servers, such as those that deliver anti-virus signature updates, are not considered in scope.

Consider defining “unauthorized activity” if that is not changed to “unauthorized access”.

For future consideration, format CIP-013 into a table format similar to CIP-008 & CIP-009 for clarity.  Expanded comments could then be moved to Technical Guidance and Examples.

 

In the event the SDT does not accept the above changes, Vectren asks the following comments be considered:

R4

This requirement is too broad to implement or audit and, therefore, outweighs the purpose of the regulatory efforts.  Same question as in R1.2.6 concerning anti-virus signature updates.  Unauthorized activity is not defined.  This is open to interpretation such as to include a user opening files they should not be viewing, or looking at settings that are not related to the task at hand.  This could also be interpreted that we must monitor every move, such as monitoring only through a WebEx while the vendor is accessing the system.  Auditor could interpret this in many ways.
 

Fred Frederick, 3/6/2017

- 0 - 0

Specific operational cyber security controls are best addressed as revisions to CIP-002 through -011.

 

Refer to EEI comments on R4 which point out overlaps to existing requirements in CIP-004, -005 and -008.

 

We recommend the CIP-013 SDT request NERC to assign the CIP revisions SDT to assist the CIP-013 team to draft the technical revisions for each of the four directives in CIP-002 through CIP-013.  The CIP revisions SDT has met their Order 822 directive that had a deadline. To get the best standards for reliability and meet the FERC Order 829 directives’ deadlines, NERC and industry should reprioritize SDT teams’ work and resources.

 

We further point out the FERC Order 829 has directed revisions to remote access (for vendors) by Sept. 2017 which is before FERC’s Order 822 P64 directive to NERC for a CIP version 5 remote  access controls effectiveness study is even due. The remote access controls effectiveness study is not due till June 30, 2017.

Darnez Gresham, Berkshire Hathaway Energy - MidAmerican Energy Co., 3, 3/6/2017

- 2 - 0

We propose the SDT modify standard language based on Vectren's proposed language below:

 

R4.

             Each Responsible Entity shall implement one or more documented process(es) for controlling vendor remote access to high and medium impact BES Cyber Systems. The process(es) shall provide the following for (i) vendor-initiated Interactive Remote Access and (ii) machine-to-machine remote access with a vendor(s): 

4.1  Authorization of remote access by the Responsible Entity;

4.2  Log and review vendor remote access;

4.3  Disabling or otherwise responding to unauthorized access during remote access sessions.

 

 

Consider removing R4 and refer to CIP-005 R2 regarding Interactive Remote Access.  If this is not an option, Vectren offers the following suggestions:

Consider defining system-to-system access (is this aka machine-to-machine)?   See page 13 of Technical Guidance and Examples, paragraph #9. 

Consider direct application access servers, such as those that deliver anti-virus signature updates, are not considered in scope.

Consider defining “unauthorized activity” if that is not changed to “unauthorized access”.

For future consideration, format CIP-013 into a table format similar to CIP-008 & CIP-009 for clarity.  Expanded comments could then be moved to Technical Guidance and Examples.

 

In the event the SDT does not accept the above changes, Vectren asks the following comments be considered:

 

R4

This requirement is too broad to implement or audit and, therefore, outweighs the purpose of the regulatory efforts.  Same question as in R1.2.6 concerning anti-virus signature updates.  Unauthorized activity is not defined.  This is open to interpretation such as to include a user opening files they should not be viewing, or looking at settings that are not related to the task at hand.  This could also be interpreted that we must monitor every move, such as monitoring only through a WebEx while the vendor is accessing the system.  Auditor could interpret this in many ways.
 

Steve Rawlinson, 3/6/2017

- 0 - 0

  • Interactive Remote Access controls are defined in CIP-005 and in CIP-007.  These requirements are duplicative and create the possibility of double-jeopardy for non-compliance.  In addition, CIP-004-6 R4 Part 4.1.1 specifically addresses electronic access.  Dominion is of the opinion that CIP-013-1 should concentrate on supply chain obligations for system-to-system communications which isn’t addressed under the existing CIP standards.  Operational requirements, such as the proposed R3, should be added to the appropriate CIP standard. 

  • Dominion recommends removal of Part 4.2.  Complying with the logging requirement could degrade system performance to the point where the BES reliability would be negatively impacted.  Additionally, the monitoring requirement further degrades the performance, and may not be technically feasible.

  • If Part 4.2 is retained, the requirements should state the minimum criteria for logging and monitoring unauthorized access, as currently outlined in CIP-007-6 Part 4.1.

  • The terms “access” and “activity” as used in the proposed CIP-013-1 need to be defined.

  • Read only access should be excluded from the final requirement based on definition of Interactive Remote Access.

  • Dominion recommends the removal of Part 4.3  Disabling or otherwise responding to unauthorized activity during remote access sessions seems to imply an on-going monitoring of active connections to a degree that’s not technically feasible. 

  • If Part 4.3 is retained, we recommend that the minimum criteria for logging and monitoring be limited to disabling what has been detected.  Dominion recommend the following language to achieve this goal:

    4.3: Disabling or otherwise responding to detected, logged, and monitored unauthorized activity during remote access sessions.

  • Dominion recommends creating a definition “system-to-system remote access” in the NERC glossary.  Using a broad undefined term can lead to inconsistent results.

Sean Bodkin, Dominion - Dominion Resources, Inc., 6, 3/6/2017

- 0 - 0

NRG suggests that R4, Section 4.1, Section 4.2, Section 4.3 language be moved to CIP-005. Since this is interactive remote session specific, NRG recommends moving all of these requirements into CIP-005 because of the implied real-time monitoring and logging requirements. Even though there are monitoring requirements in CIP-007, the monitoring requirements of CIP-007 are more forensic in nature. Various vendors and entities will likely want to implement individualized solutions to manage this requirement which will become administratively burdensome to the industry.  These varied solutions can also present more ports being open (a reliability /security risk) to High and Medium BES Cyber Systems which could lessen reliability.  NRG recommends that scope of this requirement should be for High and Medium with ERC BCS.  

NRG requests that the SDT provide clarity that “system-to-system” is equivalent to “machine-machine” and what does it mean (i.e. application interface vs. laptop/server level).  NRG recommends reference to the OSI layers. The R4 rationale appears to be inconsistent with the FERC directive regarding “machine to machine”.  NRG requests clarification of whether the rationale / intent of “system-to-system” is meaning that a direct machine to machine interface is needed or that it needs to go through an intermediate or third host (jump host).  NRG requests that the term “vendor” be defined to clarify intent of meaning a company or an individual (in the context of interactive remote access). 

In the implementation plan for this standard, NRG recommends a staggered implementation plan for R1, R2 & , R5 being 15 calendar months.  However, NRG recommends a 24-month implementation plan for R3 & R4would be needed for Registered Entities to manage this process on all impacted systems due to the need to re-negotiate processes with vendors (individualized solutions).

Kara White, On Behalf of: NRG - NRG Energy, Inc., FRCC, MRO, WECC, Texas RE, NPCC, SERC, SPP RE, RF, Segments 3, 4, 5, 6

- 0 - 0

  1. R4 creates confusion and possible double jeopardy with other standards. Recommend moving R4 into the following Standards/Requirements CIP-005 R2, CIP-007 R4 Subpart 4.1.5 and/or CIP-008 R1 part 1.6 to address FERC order No. 829.

  2. Recommend that this Rationale needs to be updated from “machine-to-machine” to “system-to-system” for consistency

  3. The first sentence of R2 is broader than the second sentence. The first sentence is “Each Responsible Entity shall implement one or more documented process(es) for controlling vendor remote access to high and medium impact BES Cyber Systems.” The second sentence is “The process(es) shall provide the following for (i) vendor-initiated Interactive Remote Access and (ii) system-to-system remote access with a vendor(s):“  Recommend that the first sentence needs to be consistent with the Order  and reference vendor-initiated remote access and not vendor remote access.

  4. Request guidance. “Vendor-Initiated” could be considered a single word and not associated with the proposed definition of “vendor”.

  5. Recommend changing R4.3, from “Disabling or otherwise responding to unauthorized activity during remote access sessions“ to “Disabling or otherwise responding to detected unauthorized activity.“

  6. The phrase “during remote access” does not seem to align with the “timely manners” guidance given on page 15, line 23   of the Guidance and Examples document. This capability to disable during the remote access session may not always be possible and would be dependent on how the unauthorized activity was detected.

  7. Consider eliminating sub requirements 4.1 and 4.2 since they are covered in CIP-005 and CIP-007, R5 respectively. Consider addressing sub requirement 4.3 by modifying CIP-005 thus eliminating R4 from the proposed CIP-013 standard.

  8. R4 should be moved to CIP-005 since this requirement, as written in CIP-013, only applies to vendors having remote access. This does not address other sources of remote access threats as written.

  9. For R4.2, we suggest limiting the retention period for evidence logs to 90 days to be consistent with CIP-007 R4, Parts 4.1, 4.2, and 4.3.

  10. This would increase the scope of file integrity monitoring to Medium impact devices, some which are not capable of logging. This would discourage entities from allowing vendors to ever log in remotely, which might hinder reliability in the case of required emergency troubleshooting/support. Lack of timely support would also force entities to be non-compliant with other standards, such as other CIPs.

  11. Remove vendor remote access from scope and only include system-to-system. Vendor remote access is already addressed in CIP-005 R2.

  12. SDT appears to be building on top of CIP-005 R1.5; however, R4.3 says “during the remote access session,” which may not reasonable amount of time since this is a real-time action.

David Rivera, New York Power Authority, 3, 3/6/2017

- 0 - 0

Same as RoLynda Shumpert's comments from SCE&G:

SCE&G agrees with EEI in its assessment regarding R4:

 “The use of “activity” in 4.2 and 4.3 is a concern because it may be difficult for a Responsible Entity to determine whether the activity is authorized or unauthorized. Also, there is no such thing as “escorted cyber access.” In almost all cases, the reason the Responsible Entity is allowing the remote vendor to support the system is that they have knowledge and skills that the Responsible Entity does not. Therefore the Responsible Entity would not be able to recognize inappropriate actions… We recommend that the SDT consider changing “activity” to “access” in parts 4.2 and 4.3.”

Alyssa Hubbard, 3/6/2017

- 0 - 0

We propose the SDT modify standard language based on Vectren's proposed language below:

 

R4.

             Each Responsible Entity shall implement one or more documented process(es) for controlling vendor remote access to high and medium impact BES Cyber Systems. The process(es) shall provide the following for (i) vendor-initiated Interactive Remote Access and (ii) machine-to-machine remote access with a vendor(s): 

4.1  Authorization of remote access by the Responsible Entity;

4.2  Log and review vendor remote access;

4.3  Disabling or otherwise responding to unauthorized access during remote access sessions.

 

 

Consider removing R4 and refer to CIP-005 R2 regarding Interactive Remote Access.  If this is not an option, Vectren offers the following suggestions:

Consider defining system-to-system access (is this aka machine-to-machine)?   See page 13 of Technical Guidance and Examples, paragraph #9. 

Consider direct application access servers, such as those that deliver anti-virus signature updates, are not considered in scope.

Consider defining “unauthorized activity” if that is not changed to “unauthorized access”.

For future consideration, format CIP-013 into a table format similar to CIP-008 & CIP-009 for clarity.  Expanded comments could then be moved to Technical Guidance and Examples.

 

In the event the SDT does not accept the above changes, Vectren asks the following comments be considered:

 

R4

This requirement is too broad to implement or audit and, therefore, outweighs the purpose of the regulatory efforts.  Same question as in R1.2.6 concerning anti-virus signature updates.  Unauthorized activity is not defined.  This is open to interpretation such as to include a user opening files they should not be viewing, or looking at settings that are not related to the task at hand.  This could also be interpreted that we must monitor every move, such as monitoring only through a WebEx while the vendor is accessing the system.  Auditor could interpret this in many ways.
 

Brad Lisembee, 3/6/2017

- 0 - 0

The California ISO supports the comments submitted by the ISO/RTO Council (IRC) and the Security Working Group (SWG)

Richard Vine, 3/6/2017

- 0 - 0

The Technical Guidance and Examples state that “for Requirement R4 Part 4.1, an entity may already have some authorization controls in place that will support meeting this objective”, including CIP-004 and CIP-007 R5 controls if they are fully implemented for vendor-initiated Interactive Remote Access.  Please confirm that implementation of these controls for all remote access, vendor or entity initiated, would meet compliance with this requirement.  If so, would it be beneficial to caveat the requirement and have it read “4.1 Authorization of remote access, not previously approved by CIP-004, by the Responsible Entity?”

A responsible entity may have numerous contractors from various vendors that perform a number of tasks within CIP environments that are on-site, sitting right next to employees engaged in similar activities.  Both the contractors and the employees normal work process may have them utilize Interactive Remote Access to perform their responsibilities efficiently.  Are these contractors, embedded and onsite, to have each of their connections explicitly approved and monitored at a different level of scrutiny than actual employees of the responsible entity, simply because they are not employees?  Or will there be a distinction between on-site and off-site “vendors?” 

Entergy/NERC Compliance, Segment(s) 1, 5, 3/1/2017

- 0 - 0

1)      R4 creates confusion and possible double jeopardy with other standards. Recommend moving R4 into the following Standards/Requirements CIP-005 R2, CIP-007 R4 Subpart 4.1.5 and/or CIP-008 R1 part 1.6 to address FERC order No. 829.

 

2)      Recommend that this Rationale needs to be updated from “machine-to-machine” to “system-to-system” for consistency

 

3)      The first sentence of R2 is broader than the second sentence. The first sentence is “Each Responsible Entity shall implement one or more documented process(es) for controlling vendor remote access to high and medium impact BES Cyber Systems.” The second sentence is “The process(es) shall provide the following for (i) vendor-initiated Interactive Remote Access and (ii) system-to-system remote access with a vendor(s):“  Recommend that the first sentence needs to be consistent with the Order  and reference vendor-initiated remote access and not vendor remote access.

 

4)      Request guidance. “Vendor-Initiated” could be considered a single word and not associated with the proposed definition of “vendor”.

 

5)      Recommend changing R4.3, from “Disabling or otherwise responding to unauthorized activity during remote access sessions“ to “Disabling or otherwise responding to detected unauthorized activity.“

 

6)      The phrase “during remote access” does not seem to align with the “timely manners” guidance given on page 15, line 23   of the Guidance and Examples document. This capability to disable during the remote access session may not always be possible and would be dependent on how the unauthorized activity was detected.

Quintin Lee, Eversource Energy, 1, 3/6/2017

- 0 - 0

As written, R4 is more appropriately addressed in other existing standards, CIP-004 for authorization, CIP-005 for remote access, CIP-007 for logging, and CIP-008 for response. Furthermore, it confuses the expectation of all these standards from an audit perspective by duplicating or undermining existing requirements. Authorization for interactive remote access is already covered in CIP-004 R4. Logging and monitoring of access to an Intermediate System or BES Cyber Asset is already covered in CIP-007 R4. If an entity requires separate evidence for those standards and CIP-013 R4, this could present a double jeopardy situation for compliance where an entity can be audited and penalized twice for similar requirements if a Regional Entity does not find their methods of compliance satisfactory.

Controlling remote access, including vendor remote access, is already addressed in CIP-005 R1 and R2 so CIP-013 R4 will overlap with those existing requirements.  CenterPoint Energy recommends changing “system-to-system remote access with a vendor” to “vendor initiated system-to-system remote access” and modifying existing requirements if necessary, rather than including the requirements in CIP-013. 

R4.3 is part of an entity’s incident response plan, and should be in CIP-008.

R4.2, R4.3 sub-requirements both need clauses for per Cyber Asset capability or technical feasibility exceptions.

Amelia Sawyer Anderson, On Behalf of: CenterPoint Energy Houston Electric, LLC, Texas RE, Segments 1

- 0 - 0

Nicolas Turcotte, Hydro-Qu?bec TransEnergie, 1, 3/6/2017

- 0 - 0

No additional comments.
 

DTE Energy - DTE Electric, Segment(s) 5, 4, 3, 2/27/2017

- 0 - 0

SCE&G agrees with EEI in its assessment regarding R4:

 “The use of “activity” in 4.2 and 4.3 is a concern because it may be difficult for a Responsible Entity to determine whether the activity is authorized or unauthorized. Also, there is no such thing as “escorted cyber access.” In almost all cases, the reason the Responsible Entity is allowing the remote vendor to support the system is that they have knowledge and skills that the Responsible Entity does not. Therefore the Responsible Entity would not be able to recognize inappropriate actions… We recommend that the SDT consider changing “activity” to “access” in parts 4.2 and 4.3.”

RoLynda Shumpert, On Behalf of: SCANA - South Carolina Electric and Gas Co., SERC, Segments 1, 3, 5, 6

- 0 - 0

I support the comments submitted by Brian Evans-Mongeon, Utility Services, Inc, and Marty Hostler, Northern California Power Agency.

Dennis Sismaet, Northern California Power Agency, 6, 3/6/2017

- 0 - 0

OUC requests that the scope of R4 be limited to high and medium BES Cyber Systems with ERC or Dial-up Connectivity as these systems have the highest risk associated with remote access.

Elements of R4 (authorization, logging/monitoring) appear duplicative of existing CIP requirements.  OUC requests that the scope of R4 be limited to disabling remote access.

For R4.3, the phrase “during remote access” does not seem to align with the “timely manners” guidance given on page 15, line 23 of the Technical Guidance and Examples document. The capability to disable during the remote access session may not always be possible and would be dependent on how the unauthorized activity was detected. OUC requests changing the language to “upon detected unauthorized activity”.

Ballard Mutters, Orlando Utilities Commission, 3, 3/6/2017

- 0 - 0

Requirement R4:

ATC agrees with the value provided through the implementation of controls to address logging and controlling third-party initiated remote access; however, ATC has voted “No” to the proposed language developed CIP-013-1 Requirement R4 because existing Reliability Standards accomplish this objective rendering the need for this requirement in CIP-013-1 moot. In its redundancy, it is at odds with the former efforts associated to the FERC filing of proposed retired standards for Project 2013-02 Paragraph 81, and the intent to eliminate duplicative or unnecessary requirements that do not provide security or reliability value.

Requirement R4 Sub Requirement 4.1 – 4.3:

CIP-013-1 R4 is simultaneously duplicative and additive to the language and/or intent of several existing approved and effective CIP Cyber Security Reliability Standards and is therefore providing no additional security or reliability value and creating a condition of double jeopardy for Registered Entities where a violation of CIP-013-1 R4 would constitute a violation of another CIP Standard and requirement.

  1. CIP-004-6 R4 and R5 address access management and revocation for individuals having cyber access to specified high and/or medium impact-rated BES Cyber Systems and associated Cyber Assets.  The existing enforceable CIP-004-6 standard is silent to the capacity with which a given individual is engaged with a Registered Entity, and therefore in its silence it addresses employees, contractors, interns, apprentices, or even vendors etc. These access requirements within CIP-004-6 are more prescriptive than what is proposed for CIP-013-1 therefore providing no additional security or reliability value and ultimately rendering CIP-013-1 R4.1 superfluous and unnecessary.

  2. CIP-005-5 R1 Parts 1.1 – 1.4 addresses CIP-013-1 R4(i), R4.1, ultimately rendering CIP-013-1 R4(i), R4.1 superfluous and unnecessary in that:

    • CIP-005-5 R1 Parts 1.3 mandates authorization for system-to-system remote access through the requirement for inbound and outbound access permissions through an identified Electronic Access Point protecting high and/or medium impact-rated BES Cyber Systems,

      • where those BES Cyber Systems must already be protected as a function of being inside an identified Electronic Security Perimeter pursuant to CIP-005-5 Requirement R1 Part 1.1, and

      • where all External Routable Connectivity must be through an identified Electronic Access Point pursuant to CIP-005-5 Requirement R1 Part 1.2. 

    • Additionally, CIP-005-5 R1 Part 1.4 obligates Registered Entities to perform authentication for establishing Dial-up connections to high and/or medium impact-rated BES Cyber Systems, where technically feasible.  The broad reference to system-to system remote access (which is silent to Dial-up) in combination with the absence of the provision for technical feasibility within this draft Requirement is effectively and expansion in scope to the already approved and enforceable CIP-005-5 R1 Part 1.4 Reliability Standard. Any expansion in scope to remote access requirements or controls for high or medium impact BES Cyber Systems as defined in the currently approved and enforceable Standard should be subject to the Standards Authorization Request, Development, Commenting, and Balloting Processes for CIP-005-5 so as not to be effectively revising an existing approved and enforceable Reliability Standard through the creation of a separate one. Furthermore, it is a contradiction between standards where compliance with one requirement in CIP-005-5 R1 Part 1.4 through a CIP Senior Manager and regional regulator approved Technical Feasibility Exception becomes a matter of non-compliance pursuant to CIP-013-1 R4.  

  3. CIP-005-5 R2 Parts 2.1 – 2.3 and CIP-007-6 R5 Parts 5.1 goes beyond in addressing CIP-013-1 R4(ii), R4.1, ultimately rendering CIP-013-1 R4(ii), R4.1 superfluous and unnecessary in that:

    • CIP-005-5 R1 Parts 2.1 mandates authorization for all Interactive Remote Access (IRA) (including vendor-initiated IRA) through the requirement to use an Intermediate System such that any remotely-initiated IRA does not directly access the high and/or medium impact-rated BES Cyber System(s),

    • where those Intermediate System must also utilize encryption that terminates at the Intermediate System pursuant to CIP-005-5 Requirement R2 Part 2.2, and

    • where all IRA sessions must require multi-factor authentication pursuant to CIP-005-5 Requirement R2 Part 2.2. 

    • CIP-007-6 R5 Parts 5.1 further mandates methods to enforce authentication of interactive user access (including vendor-initiated users) where technically feasible for high and/or medium impact-rated BES Cyber System(s),

  4. CIP-005-5 R1 Parts 1.2 - 1.5, in combination with CIP-007-6 R4 Parts 4.1-4.4 and CIP-007-6 R5 Part 5.7 collectively addresses, and in some cases exceeds, the logging, monitoring, and detection of unauthorized activity proposed in CIP-013-1 R4, R4.2, ultimately rendering in CIP-013-1 R4, R4.2 superfluous and unnecessary in that:

    • CIP-005-5 R1 Part 1.5 mandates one or more methods for detecting known or suspected malicious communications both inbound and outbound on the Electronic Access Points protecting high and/or medium impact-rated BES Cyber System(s), and because all remote access must also be through an identified Electronic Access Point pursuant to CIP-005-5 Requirement R1 Part 1.2, the two existing enforceable requirements in combination already satisfying the detection component intended by CIP-013-1 R4, R4.2; and consequently, the detection component intended by CIP-013-1 R4, R4.2 adds no security or reliability value and rather creates a condition of potential double jeopardy for existing approved and enforceable Standard CIP-005-05 R1.

    • CIP-007-6 R4 Parts 4.1-4.4 mandates that, per BES Cyber System capability or at the Cyber Asset level for high and/or medium impact-rated BES Cyber System(s),

      • specified access-related events are logged,

      • alerts are generated for said events,

      • event logs are retained as technically feasible for 90 consecutive calendar days except in CIP Exceptional Circumstances,

      • thereby already satisfying the logging and monitoring component intended by CIP-013-1 R4, R4.2; Consequently, the logging and monitoring component intended by CIP-013-1 R4, R4.2 adds no security or reliability value and rather creates a condition of potential double jeopardy for existing approved and enforceable Standard CIP-007-6 R4 that is also at odds with efforts associated to the FERC filing of proposed retired standards for Project 2013-02 Paragraph 81, and the intent to eliminate duplicative or unnecessary requirements that do not provide security or reliability value.

      • Furthermore, in its redundancy of CIP-007-6 R4, CIP-013-1 R4, R4.2 is simultaneously an expansion in scope in that CIP-013-1 R4, R4.2 is silent to the provisions for “Per Cyber System capability”, per cyber Asset capability”, “technical feasibility”, and “CIP Exceptional Circumstances”, is effectively and expansion in scope to the already approved and enforceable CIP-007-6 R4 Reliability Standard. Any expansion in scope to logging, monitoring, or detection activity related to requirements or controls for high or medium impact BES Cyber Systems as defined in the currently approved and enforceable Standard should be subject to the Standards Authorization Request, Development, Commenting, and Balloting Processes for CIP-007-6 so as not to be effectively revising an existing approved and enforceable Reliability Standard through the creation of a separate one. Furthermore, it is a contradiction between standards where compliance with one requirement in CIP-007-6 R4 through:

        • a CIP Senior Manager and regional regulator approved Technical Feasibility Exception,

        • a CIP Senior Manager approved CIP Exceptional Circumstance,

        • a documented per BES Cyber System incapability, and/or

        • a documented per Cyber Asset incapability

          becomes a matter of non-compliance pursuant to CIP-013-1 R4.2

    • CIP-007-6 R5 Part 5.7 mandates limiting of the number of unsuccessful authentication attempts or the generation of alerts of unsuccessful authentication attempts exceeding a Registered Entity defined threshold, where technically feasible and scope to high impact BES Cyber Systems and medium impact BES Cyber Systems at Controls Centers. The broad reference high and medium impact BES Cyber Systems, in combination with the absence of the provision for technical feasibility within this draft Requirement for CIP-013-1 R4 is effectively and expansion in scope to the already approved and enforceable CIP-007-6 R5.7 Reliability Standard. Any expansion in scope to logging, monitoring, or detection activity related to requirements or controls for high or medium impact BES Cyber Systems as defined in the currently approved and enforceable Standard should be subject to the Standards Authorization Request, Development, Commenting, and Balloting Processes for CIP-007-6 so as not to be effectively revising an existing approved and enforceable Reliability Standard through the creation of a separate one. Furthermore, it is a contradiction between standards where compliance with one requirement in CIP-007-6 R5 Part 5.7 through a CIP Senior Manager and regional regulator approved Technical Feasibility Exception becomes a matter of non-compliance pursuant to CIP-013-1 R4.

Lauren Price, 3/6/2017

- 0 - 0

CPS Energy supports the comments provided by ERCOT and APPA

Brian Bartos, On Behalf of: Brian Bartos, , Segments 1, 3, 5

- 0 - 0

Xcel Energy supports the comments filed by the Edison Electric Institute (EEI).

- 0 - 0

1.      As mentioned above, the standard drafting team should not create additional requirements for which entities are already being audited against. This creates confusion and risks the entity to being in double jeopardy for the same activity.

 

R4, Part 4.1 is covered under CIP-004-6 R4, Part 4.1

R4, Part 4.2 is covered under CIP-007-6 R4, Part 4.1

R4, P4.3 is covered under with CIP-005-5.  Part 1.3 of CIP-005-5

Warren Cross, On Behalf of: ACES Power Marketing, MRO, WECC, Texas RE, SERC, SPP RE, Segments 1, 3, 4, 5

- 0 - 0

Though each of the objectives in Order 829 is addressed, Reclamation recommends a more simplified format for the requirements as the SDT originally suggested in the webinar on November 10, 2016.

 

Reclamation recommends that Requirement R4 be deleted. There would be no need for Requirement R4 if all aspects of the supply chain risk management plan(s) are to be addressed in Requirement R1 and its sub-requirements.

Wendy Kalidass, U.S. Bureau of Reclamation, 5, 3/6/2017

- 0 - 0

Rationale for Requirement R4:

The rationale language for R4 states, “The proposed requirement addresses Order No. 829 directives for controls on vendor-initiated remote access to BES Cyber Systems covering both user-initiated and machine-to-machine vendor remote access (P. 51).” R1, R2, and the Rationale for Requirement R3 and R4 do not specify the impact classifications (High, Medium and Low) when referencing the BES Cyber System. R3 and R4 specifically state the impact classification of the BES Cyber System “applicable to High and Medium Impact BES Cyber Systems (R3)” or “Each Responsible Entity shall implement one or more documented process(es) for controlling vendor remote access to high and medium impact BES Cyber Systems (R4).” IPC would like to know if the inconsistent impact classification references were intended or were an oversight by the SDT?

R4

IPC does not believe CIP-013-1 is an appropriate standard to address R4.1, R4.2 and R4.3. IPC believes R4.1 belongs in CIP-004-6, as R4.1 is related to authorization and R4.2 and R4.3 belongs in CIP-005-6 as R4.2 and R4.2 are related to remote access. IPC feels the intent of CIP-013-1 is to address supply chain controls, whereas CIP-004-6 addresses access management and CIP-005-6 addresses remote access. 

M4

Some of the measure language for R4 states, “hard copy or electronic listing of alert capabilities applicable to vendor remote access of the BES Cyber System; or records of response to unauthorized vendor remote access.“ R1, R2, and the Rationale for Requirement R3, R4, and M4 do not specify the impact classifications (High, Medium and Low) when referencing the BES Cyber System. R3 and R4 specifically states the impact classification of the BES Cyber System “applicable to High and Medium Impact BES Cyber Systems (R3)” or “Each Responsible Entity shall implement one or more documented process(es) for controlling vendor remote access to high and medium impact BES Cyber Systems (R4).” IPC would like to know if the inconsistent impact classification references were intended or were an oversight by the SDT?

Laura Nelson, 3/6/2017

- 0 - 0

Santee Cooper requests that the scope of R4 be limited to high and medium BES Cyber Systems with ERC or Dial-up Connectivity as these systems have the highest risk associated with remote access.

Elements of R4 (authorization, logging/monitoring) appear duplicative of existing CIP electronic access requirements.  Santee Cooper requests that the scope of R4 be limited to disabling remote access.

For R4.3, the phrase “during remote access” does not seem to align with the “timely manners” guidance given on page 15, line 23 of the Technical Guidance and Examples document.  The capability to disable during the remote access session may not always be possible and would be dependent on how the unauthorized activity was detected.  Santee Cooper requests changing the language to “upon detected unauthorized activity”.

Santee Cooper , Segment(s) 1, 5, 3/6/2017

- 0 - 0

This requirement is duplicative of existing requirements within CIP standards.

Authorization of access is covered in CIP-004-6 R4.1.  The language in this CIP-004-6 R4.1 does not exclude vendors.

The rationale for CIP-007-6 R4 explicitly states that security event monitoring’s purpose is to detect unauthorized activity.

A detection of unauthorized activity would be investigated as a potential Cyber Security Incident and appropriate action would be taken from there.

Teresa Krabe, Lower Colorado River Authority, 5, 3/6/2017

- 0 - 0

BPA believes the scope should be limited to High and Medium BES cyber systems with ERC or dialup. All requirements for Low impact systems should be addressed in CIP-003.

BPA suggests modification of existing CIP standards to address gaps:

Remote access CIP-013 R4, P4.1 is addressed in CIP-004-6 R4, Part 4.1

Logging and monitoring CIP-013 R4, P4.2 is addressed in CIP-007-6 R4, P4.1

Remote access sessions CIP-013 R4, P4.3 is addressed in CIP-005 R2

Aaron Cavanaugh, On Behalf of: Bonneville Power Administration, WECC, Segments 1, 3, 5, 6

- 0 - 0

AZPS requests changing Requirement R4.3 to read ‘disabling or otherwise responding to detected, unauthorized activity during remote access session’.  It further notes that, as written, the proposed Requirement R4 would place Registered Entities in “double jeopardy” where similar controls are already required under CIP-004-6.  Accordingly, AZPS requests that the SDT consider revising this requirement to remove such redundancy or to include a clarification regarding how this risk for “double jeopardy” will be managed relative to access controls required under CIP-004-6.

Stephanie Little, 3/6/2017

- 0 - 0

1)      R4 creates confusion and possible double jeopardy with other standards. Recommend modifying modify CIP-005 R2 , CIP-007 R4 Subpart 4.1.5 and/or CIP-008 R1 part 1.6 address the FERC order No. 829.

2)    For R4.3, the “during remote access” does not seem to align with the “timely manners” guidance given on page 15, line 23   of the Guidance and Examples document. This capability to disable during the remote access session may not always be possible and would be dependent on how the unauthorized activity was detected. Suggest changing to “detected unauthorized activity”.

3)     Suggest changing the format of the standard to use Applicability Tables like those used in CIP-004 through CIP-011.

Nathan Mitchell, On Behalf of: Nathan Mitchell, , Segments 3, 4

- 0 - 0

CPS Energy supports the comments provided by ERCOT and APPA

Glenn Pressler, CPS Energy, 3, 3/6/2017

- 0 - 0

See EEI comments

Louis Guidry, 3/6/2017

- 0 - 0

PSEG agrees with the intent of this requirement, but has the following questions/recommendations below:

 

  • Recommend changing Requirement 4.3, from “Disabling or otherwise responding to unauthorized activity during remote access sessions“ to “Disabling or otherwise responding to detected unauthorized activity associated with remote access sessions.“ PSEG finds that inclusion of the word “during” in the requirement overreaches the intent of relevant FERC directive (p.51).

  • Requirements R1 and R2 do not require the registered entity to go back and revise previous contracts. In order to comply with this requirement, R4, past contracts / vendor service agreements may be required. Alignment is needed between R1, R2, and R4.

  • Vendor-initiated Interactive remote access is no different than Interactive remote access. Recommendation to incorporate Requirement R4 into CIP-007 R5 System Access Control. 

  • Requirement R4 overlaps with CIP-005 for Interactive Remote Access, which applies to vendors, only 4.2 monitoring and 4.3 is new. Recommend streamlining R4 to fit in CIP-005 R2.

  • Recommend changing “activity” to “access”. Use of the word “activity” in 4.2 and 4.3 because it may be difficult for a Responsible Entity to determine whether the activity is authorized or unauthorized. In almost all cases, the vendor has more in depth technical knowledge of the system they developed beyond the Registered Entity’s level of expertise on the system. Therefore it would be difficult for the Responsible Entity to recognize inappropriate actions/activity. If “activity” is left, this will likely result in Responsible Entities requiring vendors to perform their work onsite, which will add considerable costs without any security benefits. If the person is doing something inappropriate, they’ll be able to do it onsite. If the intent of this requirement is to monitor “unauthorized activity”, the term “unauthorized activity” should be defined.

PSEG REs, Segment(s) 5, 6, 3, 1, 3/6/2017

- 1 - 0

Colorado Springs Utilities (CSU) requests that the scope of R4 be limited to high and medium BES Cyber Systems with ERC or Dial-up Connectivity as these systems have the highest risk associated with remote access.

 

Elements of R4 (authorization, logging/monitoring) appear duplicative of existing CIP electronic access requirements.  CSU requests that the scope of R4 be limited to disabling remote access.

 

For R4.3, the phrase “during remote access” does not seem to align with the “timely manners” guidance given on page 15, line 23 of the Technical Guidance and Examples document. The capability to disable during the remote access session may not always be possible and would be dependent on how the unauthorized activity was detected. CSU requests changing the language to “upon detected unauthorized activity”.

Colorado Springs Utilities, Segment(s) 5, 3, 1, 6, 5/6/2015

- 0 - 0

The IESO request that the SDT consider moving this requirement to existing CIP Standard to prevent overlap, conflict, or omission of existing requirements.

 

The SDT should address whether system-to-system access is when vendor-initiated. Lack of clarity there will impact automated updates from vendors that are time-sensitive, as well as outbound connections to vendors for health checks, licensing, and other system information. 

Leonard Kula, Independent Electricity System Operator, 2, 3/6/2017

- 0 - 0

The attached document has comments compiled for all the questions.  Please note that the BOLD paragraphs below  (YELLOW highlighted in attachment) are uniquely Seattle City Lights.  The un-highlighted comments were developed in collaboration with other entities and trade organizations such as LPPC.  These comments may be like those submitted by other entities but not necessarily.  City Light recognizes the challenges facing the SDT and appreciates the efforts the SDT is placing into working towards developing a solid standard. 

 

Seattle City Light requests that the scope of R4 be limited to high and medium BES Cyber Systems with ERC or Dial-up Connectivity as these systems have the highest risk associated with remote access.

Elements of R4 (authorization, logging/monitoring) appear duplicative of existing CIP electronic access requirements.  Seattle City Light requests that the scope of R4 be limited to disabling remote access.

For R4.3, the phrase “during remote access” does not seem to align with the “timely manners” guidance given on page 15, line 23 of the Technical Guidance and Examples document. The capability to disable during the remote access session may not always be possible and would be dependent on how the unauthorized activity was detected. Seattle City Light requests changing the language to “upon detected unauthorized activity”.

Furthermore, because it may not be technically feasible to remotely disable a vendor from equipment provided by that vendor (which the entity purchased from them, and may be dependent upon the vendor for maintenance), Seattle City Light requests the inclusion of a Technical Feasibility Exception (TFE) for R4. Seattle City Light suggests the following language: “WHERE TECHNICALLY FEASIBLE, each responsible entity shall implement one or more documented process(es) for controlling vendor remote access to…” (emphasis added).

Seattle City Light Ballot Body, Segment(s) 1, 4, 6, 5, 3, 12/2/2016

CIP-013 Comment Mar 2 revision SCL 2017-3-6.docx

- 0 - 0

FEUS supports the comments submitted by APPA

Linda Jacobson-Quinn, City of Farmington, 3, 3/6/2017

- 0 - 0

FMPA agrees with comments submitted by American Public Power Association.

FMPA, Segment(s) , 12/5/2016

- 0 - 0

Jay Barnett, 3/6/2017

- 0 - 0

We recommend the SDT address CIP Exceptional Circumstance with respect to this requirement aligned with project 2016-02. 

Also please see our earlier comments with regards to redundancy between R4 and R1.2.6.

Payam Farahbakhsh, Hydro One Networks, Inc., 1, 3/6/2017

- 0 - 0

The NYPA Comments

Erick Barrios, 3/6/2017

- 0 - 0

 

SMUD requests that the scope of R4 be limited to high and medium BES Cyber Systems with ERC or Dial-up Connectivity as these systems have the highest risk associated with remote access.

 

 

 

Elements of R4 (authorization, logging/monitoring) appear duplicative of existing CIP requirements.  SMUD requests that the scope of R4 be limited to disabling remote access.

 

 

 

For R4.3, the phrase “during remote access” does not seem to align with the “timely manners” guidance given on page 15, line 23 of the Technical Guidance and Examples document. The capability to disable during the remote access session may not always be possible and would be dependent on how the unauthorized activity was detected. SMUD requests changing the language to “upon detected unauthorized activity”.

 

 

 

- 0 - 0

Authorization of Remote Access

The existing CIP-004 requirements already address authorization of vendor individuals and CIP-005 requirements address system-to-system authorization. We recommend that the SDT consider deleting Requirement R4, Part 4.1 to avoid this unnecessary overlap.

Activity v. Access

The use of “activity” in 4.2 and 4.3 is a concern because it may be difficult for a Responsible Entity to determine whether the activity is authorized or unauthorized. Also, there is no such thing as “escorted cyber access.” In almost all cases, the reason the Responsible Entity is allowing the remote vendor to support the system is that they have knowledge and skills that the Responsible Entity does not. Therefore the Responsible Entity would not be able to recognize inappropriate actions. If “activity” is left, this will likely result in Responsible Entities requiring vendors to perform their work onsite, which will add considerable costs without any security benefits. If the person is doing something inappropriate, they’ll be able to do it onsite. We recommend that the SDT consider changing “activity” to “access” in parts 4.2 and 4.3.

Remote Access Session Monitoring

Although the Commission mentions monitoring of third-party initiated remote access sessions, they direct that the standard “must address responsible entities’ logging and controlling all third-party (i.e., vendor) initiated remote access sessions.” (Order No. 829, P51) The security objective is to address “the threat that vendor credentials could be stolen and used to access a BES Cyber System without the responsible entity’s knowledge, as well as the threat that a compromise at a trusted vendor could traverse over an unmonitored connection into a responsible entity’s BES Cyber System.” (Order No. 829, P 52).

First, the CIP-005 two factor authentication requirement would prevent access via stolen vendor credentials, except for in a sophisticated “Charlie’s Angels” style attack (2000 movie) designed to overcome multifactor authentication, which was not the case in the Ukraine attack.

Second, monitoring remote access sessions to detect unauthorized activity is a method to control unwanted access or a “how” to implement the security objective. There are other methods to address the security objective, including controlled log-in and log-outs for specific activities and limiting the vendor’s ability to access BES Cyber Systems.

Third, session monitoring of system to system activity, as prescribed by the proposed standard is not practical due to technology constraints and the likelihood that time sensitive network traffic supporting reliability tasks could be adversely impacted. For example, where a 2 millisecond response is required in an energy management system and continuous monitoring of remote vendor access reduces system response time to 5 milliseconds.  Also, technology constraints may prevent Responsible Entities from determining whether a vendor or an employee is accessing the BES Cyber System. These complications may force Responsible Entities from disallowing remote access by vendors, which may actually harm reliability rather than improve it. Vendors know their systems best since they designed and manufactured them and therefore they are in the best position for remote access to complete certain tasks.

To address the concerns, we recommend that the SDT consider changing the “monitoring” language to “control” and focus on the second part of the security objective, controlling persistent machine-to-machine remote access sessions by vendors.  Controlling persistent machine-to-machine remote access is possible by different methods, including one way communications and time limiting access sessions. Vendor Interactive Remote Access is already controlled by CIP-005 requirements.

Disabling/Responding to Unauthorized Activity

Disabling remote access (Part 4.3) may also not be possible and would likely force Responsible Entities to disallow vendor remote access. We recommend that the SDT remove this part.

Requirement Placement (CIP-005)

Because Requirement R4 is an operational control, we recommend that the SDT consider putting this requirement into CIP-005 R2 and not create duplicative requirements.

Definitions

Machine-to-machine or system-to-system remote access is also not defined so it’s unclear what new systems this brings into scope for this requirement. If the SDT uses one of these terms, we recommend that they define it. Also, if the SDT uses our suggestion for addressing persistent, machine-to-machine remote access, we also recommend defining persistent, perhaps leveraging the concept used by the transient cyber asset definition. We also recommend that the SDT consider defining vendor, for example, does it include an ISO ICCP connection to an EMS?

We recommend the following language for consideration by the SDT:

R4.  Each Responsible Entity shall implement one or more documented method(s) to control persistent, machine-to-machine remote access sessions by vendors to high and medium impact BES Cyber Systems.

Melanie Seader, On Behalf of: Edison Electric Institute, NA - Not Applicable, Segments NA - Not Applicable

- 1 - 0

Tacoma concurs with the comments provided by the LPPC.

Marc Donaldson, Tacoma Public Utilities (Tacoma, WA), 3, 3/6/2017

- 0 - 0

- 0 - 0

    SDG&E agrees with EEI comments and proposed language.  These operations requirements are covered in other CIP standards.   

Jeff Johnson, On Behalf of: Sempra - San Diego Gas and Electric, WECC, Segments 1, 2, 3, 4, 5, 6, 7

- 0 - 0

This requirement is duplicative of existing requirements within CIP standards.

 

Authorization of access is covered in CIP-004-6 R4.1.  The language in this CIP-004-6 R4.1 does not exclude vendors.

The rationale for CIP-007-6 R4 explicitly states that security event monitoring’s purpose is to detect unauthorized activity.

A detection of unauthorized activity would be investigated as a potential Cyber Security Incident and appropriate action would be taken from there.

 

- 0 - 0

Authorization of Remote Access

 

The existing CIP-004 requirements already address authorization of vendor individuals and CIP-005 requirements address system-to-system authorization. We recommend that the SDT consider deleting Requirement R4, Part 4.1 to avoid this unnecessary overlap.

 

Activity v. Access

 

The use of “activity” in 4.2 and 4.3 is a concern because it may be difficult for a Responsible Entity to determine whether the activity is authorized or unauthorized. Also, there is no such thing as “escorted cyber access.” In almost all cases, the reason the Responsible Entity is allowing the remote vendor to support the system is that they have knowledge and skills that the Responsible Entity does not. Therefore the Responsible Entity would not be able to recognize inappropriate actions. If “activity” is left, this will likely result in Responsible Entities requiring vendors to perform their work onsite, which will add considerable costs without any security benefits. If the person is doing something inappropriate, they’ll be able to do it onsite. We recommend that the SDT consider changing “activity” to “access” in parts 4.2 and 4.3.

 

Remote Access Session Monitoring

 

Although the Commission mentions monitoring of third-party initiated remote access sessions, they direct that the standard “must address responsible entities’ logging and controlling all third-party (i.e., vendor) initiated remote access sessions.” (Order No. 829, P51) The security objective is to address “the threat that vendor credentials could be stolen and used to access a BES Cyber System without the responsible entity’s knowledge, as well as the threat that a compromise at a trusted vendor could traverse over an unmonitored connection into a responsible entity’s BES Cyber System.” (Order No. 829, P 52).

 

First, the CIP-005 two factor authentication requirement would prevent access via stolen vendor credentials, except for in a sophisticated “Charles Angels” style attack (2000 movie) designed to overcome multifactor authentication, which was not the case in the Ukraine attack.

 

Second, monitoring remote access sessions to detect unauthorized activity is a method to control unwanted access or a “how” to implement the security objective. There are other methods to address the security objective, including controlled log-in and log-outs for specific activities and limiting the vendor’s ability to access BES Cyber Systems.

 

Third, session monitoring of system to system activity, as prescribed by the proposed standard is not practical due to technology constraints and the likelihood that time sensitive network traffic supporting reliability tasks could be adversely impacted. For example, where a 2 millisecond response is required in an energy management system and continuous monitoring of remote vendor access reduces system response time to 5 milliseconds.  Also, technology constraints may prevent Responsible Entities from determining whether a vendor or an employee is accessing the BES Cyber System. These complications may force Responsible Entities from disallowing remote access by vendors, which may actually harm reliability rather than improve it. Vendors know their systems best since they designed and manufactured them and therefore they are in the best position for remote access to complete certain tasks.

 

To address the concerns, we recommend that the SDT consider changing the “monitoring” language to “control” and focus on the second part of the security objective, controlling persistent machine-to-machine remote access sessions by vendors.  Controlling persistent machine-to-machine remote access is possible by different methods, including one way communications and time limiting access sessions. Vendor Interactive Remote Access is already controlled by CIP-005 requirements.

 

Disabling/Responding to Unauthorized Activity

 

Disabling remote access (Part 4.3) may also not be possible and would likely force Responsible Entities to disallow vendor remote access. We recommend that the SDT remove this part.

 

Requirement Placement (CIP-005)

 

Because Requirement R4 is an operational control, we recommend that the SDT consider putting this requirement into CIP-005 R2 and not create duplicative requirements.

 

Definitions

 

Machine-to-machine or system-to-system remote access is also not defined so it’s unclear what new systems this brings into scope for this requirement. If the SDT uses one of these terms, we recommend that they define it. Also, if the SDT uses our suggestion for addressing persistent, machine-to-machine remote access, we also recommend defining persistent, perhaps leveraging the concept used by the transient cyber asset definition. We also recommend that the SDT consider defining vendor, for example, does it include an ISO ICCP connection to an EMS?

 

We recommend the following language for consideration by the SDT:

 

R4.  Each Responsible Entity shall implement one or more documented method(s) to control persistent, machine-to-machine remote access sessions by vendors to high and medium impact BES Cyber Systems.

William Wenz, On Behalf of: AES - Dayton Power and Light Co., RF, Segments NA - Not Applicable

- 0 - 0

The IRC and SWG request that the SDT consider moving this requirement to existing CIP Standard to prevent overlap, conflict, or omission of existing requirements.

The SDT should address whether system-to-system access is when vendor-initiated. Lack of clarity there will impact automated updates from vendors that are time-sensitive, as well as outbound connections to vendors for health checks, licensing, and other system information. 

IRC-SRC, Segment(s) 2, 11/18/2016

- 0 - 0

Authorization of Remote Access

 

The existing CIP-004 requirements already address authorization of vendor individuals and CIP-005 requirements address system-to-system authorization. We recommend that the SDT consider deleting Requirement R4, Part 4.1 to avoid this unnecessary overlap.

 

Activity v. Access

 

The use of “activity” in 4.2 and 4.3 is a concern because it may be difficult for a Responsible Entity to determine whether the activity is authorized or unauthorized. Also, there is no such thing as “escorted cyber access.” In almost all cases, the reason the Responsible Entity is allowing the remote vendor to support the system is that they have knowledge and skills that the Responsible Entity does not. Therefore the Responsible Entity would not be able to recognize inappropriate actions. If “activity” is left, this will likely result in Responsible Entities requiring vendors to perform their work onsite, which will add considerable costs without any security benefits. If the person is doing something inappropriate, they’ll be able to do it onsite. We recommend that the SDT consider changing “activity” to “access” in parts 4.2 and 4.3.

 

Remote Access Session Monitoring

 

Although the Commission mentions monitoring of third-party initiated remote access sessions, they direct that the standard “must address responsible entities’ logging and controlling all third-party (i.e., vendor) initiated remote access sessions.” (Order No. 829, P51) The security objective is to address “the threat that vendor credentials could be stolen and used to access a BES Cyber System without the responsible entity’s knowledge, as well as the threat that a compromise at a trusted vendor could traverse over an unmonitored connection into a responsible entity’s BES Cyber System.” (Order No. 829, P 52).

 

First, the CIP-005 two factor authentication requirement would prevent access via stolen vendor credentials, except for in a sophisticated “Charles Angels” style attack (2000 movie) designed to overcome multifactor authentication, which was not the case in the Ukraine attack.

 

Second, monitoring remote access sessions to detect unauthorized activity is a method to control unwanted access or a “how” to implement the security objective. There are other methods to address the security objective, including controlled log-in and log-outs for specific activities and limiting the vendor’s ability to access BES Cyber Systems.

 

Third, session monitoring of system to system activity, as prescribed by the proposed standard is not practical due to technology constraints and the likelihood that time sensitive network traffic supporting reliability tasks could be adversely impacted. For example, where a 2 millisecond response is required in an energy management system and continuous monitoring of remote vendor access reduces system response time to 5 milliseconds.  Also, technology constraints may prevent Responsible Entities from determining whether a vendor or an employee is accessing the BES Cyber System. These complications may force Responsible Entities from disallowing remote access by vendors, which may actually harm reliability rather than improve it. Vendors know their systems best since they designed and manufactured them and therefore they are in the best position for remote access to complete certain tasks.

 

To address the concerns, we recommend that the SDT consider changing the “monitoring” language to “control” and focus on the second part of the security objective, controlling persistent machine-to-machine remote access sessions by vendors.  Controlling persistent machine-to-machine remote access is possible by different methods, including one way communications and time limiting access sessions. Vendor Interactive Remote Access is already controlled by CIP-005 requirements.

 

Disabling/Responding to Unauthorized Activity

 

Disabling remote access (Part 4.3) may also not be possible and would likely force Responsible Entities to disallow vendor remote access. We recommend that the SDT remove this part.

 

Requirement Placement (CIP-005)

 

Because Requirement R4 is an operational control, we recommend that the SDT consider putting this requirement into CIP-005 R2 and not create duplicative requirements.

 

Definitions

 

Machine-to-machine or system-to-system remote access is also not defined so it’s unclear what new systems this brings into scope for this requirement. If the SDT uses one of these terms, we recommend that they define it. Also, if the SDT uses our suggestion for addressing persistent, machine-to-machine remote access, we also recommend defining persistent, perhaps leveraging the concept used by the transient cyber asset definition. We also recommend that the SDT consider defining vendor, for example, does it include an ISO ICCP connection to an EMS?

 

We recommend the following language for consideration by the SDT:

 

R4.  Each Responsible Entity shall implement one or more documented method(s) to control persistent, machine-to-machine remote access sessions by vendors to high and medium impact BES Cyber Systems.

William Wenz, On Behalf of: AES - Dayton Power and Light Co., RF, Segments NA - Not Applicable

- 0 - 0

GTC disagrees with the proposed requirement.  CIP-013-1 R4 requires actions to be taken by the Responsible Entity that are outside of the supply chain context.  FERC Order 829 specifically stated in paragraph 45 that the plan should address the security objectives in “the context of addressing supply chain management risks.” NIST 800-53 provides a definition of supply chain that is as follows: “Linked set of resources and processes between multiple tiers of developers that begins with the sourcing of products and services and extends through the design, development, manufacturing, processing, handling, and delivery of products and services to the acquirer.”  FERC Order 829 acknowledges this definition in paragraph 32, footnote 61.  However, the SDT has chosen to identify controls in R4 that are executed only as part of the day-to-day management of BES Cyber Systems and introduce double jeopardy with existing CIP Reliability Standards. 

 

R4 as written contains three parts to each be implemented for “(i) vendor-initiated Interactive Remote Access and (ii) system-to-system remote access with a vendor(s).”  

 

4.1: Authorization of remote access.  Electronic access to high and medium impact BES Cyber Systems, whether local or remote, and regardless of whether the individual is a vendor, is already required by CIP-004-6 R4, Part 4.1.  System to system remote access must be explicitly permitted through the ESP along with documented justification according to CIP-005-5 R1, Part 1.3.

 

4.2: Logging and monitoring of remote access sessions:  CIP-005-5 R1, Part 1.5 requires methods for detecting malicious communications for high impact BES Cyber Systems and medium impact BES Cyber Systems at Control Centers.  CIP-007-6 R4, Part 4.1 requires logging of successful and failed access attempts.  The applicable systems for CIP-007-6 R4, Part 4.1 includes EACMSs associated with medium and high impact BES Cyber Systems, effectively including logging that occurs at the perimeter of the ESP as well as access to the BES Cyber Systems directly.  CIP-007-6 R4 additional requires monitoring of the logs.

 

4.3: Disabling or responding to unauthorized activity:  CIP-008-5 R2 requires that entities respond to unauthorized activity according to their defined incident response plans.  As a Cyber Security Incident includes any incident that “compromises, or was an attempt to compromise, the ESP…” or “disrupts, or was an attempt to disrupt, the operation of a BES Cyber System,” response to any unauthorized activity (whether local or remote, physical or electronic) is already required by CIP-008-5 R2.

That said, there are gaps remaining between the existing CIP standards and the directive as specified by FERC Order 829.

 

As such, all controls required by CIP-013-1 R4 already exist in other CIP Reliability Standards, effectively making any non-compliance with R4 a case of double jeopardy with either CIP-004-6 R4, CIP-005-5 R1, CIP-007-6 R4, or CIP-008-5 R2, depending on the facts and circumstances of the specific compliance issue.  While CIP-013-1 R4 suggests the implementation of technical security controls, it is unclear what additional controls would be implemented that are not already required by the existing CIP Standards.  CIP-013-1 R4 only provides for additional paperwork, administrative burden, and double jeopardy compliance risk.  As such, the standard drafting team should not create additional requirements for which entities are already being audited against and it should be removed.

 

That said, we do believe that addressing remote access in the supply chain context (not in the day-to-day operations context) could provide supply chain security risk management benefits.  Unfortunately, the SDT has not constructed its requirement as such.  Consistent with our response to question 1, we recommend that the SDT consider a plan based approach to addressing security risks in the context of the supply chain.

 

R4 is written in a manner that implies the Responsible Entity shall implement a separate documented process in addition to the plan specified in R1.  Paragraph 45 of Order No. 829, clearly specifies this objective of vendor remote access should be applied to “The Plan” identified in the core directive in the context of addressing supply chain management risks. 

 

(P. 45) The plan required by the new or modified Reliability Standard developed by NERC should address, at a minimum, the following four specific security objectives in the context of addressing supply chain management risks: (1) software integrity and authenticity; (2) vendor remote access; (3) information system planning; and (4) vendor risk management and procurement controls.

 

GTC recommends the SDT remove this requirement and include a security objective for vendor remote access in “The Plan” specified in R1 to align with the FERC Order.  See GTC’s comment for Question #1.

Jason Snodgrass, 3/6/2017

- 0 - 0

Bob Case, On Behalf of: Black Hills Corporation, WECC, Segments 1, 3, 5, 6

- 0 - 0

Refer to CSU comments.

Devin Elverdi, 3/6/2017

- 0 - 0

Maryanne Darling-Reich, 3/6/2017

- 0 - 0

Control of Interactive Remote Access to High and Medium Impact BES Cyber Systems is already required by CIP-005-5, Requirement R2.  To that end, including that aspect in this Requirement is duplicative to some extent.  Similarly, it could be argued that authorization of remote access is covered by CIP-004-6, Requirement R4, and logging of access is required by CIP-007-6, Requirement R4.  The Standards Drafting Team should either incorporate the few remaining elements into the existing Requirements in the other CIP Standards, or rewrite this Requirement to only include the additional expectations not covered elsewhere.

Bob Reynolds, On Behalf of: Bob Reynolds, , Segments 10

- 0 - 0

Avista supports the comments filed by the Edison Electric Institute (EEI).

- 0 - 0

1)      R4 creates confusion and possible double jeopardy with other standards. Recommend moving R4 into the following Standards/Requirements CIP-005 R2, CIP-007 R4 Subpart 4.1.5 and/or CIP-008 R1 part 1.6 to address FERC order No. 829.

 

2)      Recommend that this Rationale needs to be updated from “machine-to-machine” to “system-to-system” for consistency

 

3)      The first sentence of R2 is broader than the second sentence. The first sentence is “Each Responsible Entity shall implement one or more documented process(es) for controlling vendor remote access to high and medium impact BES Cyber Systems.” The second sentence is “The process(es) shall provide the following for (i) vendor-initiated Interactive Remote Access and (ii) system-to-system remote access with a vendor(s):“  Recommend that the first sentence needs to be consistent with the Order  and reference vendor-initiated remote access and not vendor remote access.

 

4)      Request guidance. “Vendor-Initiated” could be considered a single word and not associated with the proposed definition of “vendor”.

 

5)      Recommend changing R4.3, from “Disabling or otherwise responding to unauthorized activity during remote access sessions“ to “Disabling or otherwise responding to detected unauthorized activity.“

 

6)      The phrase “during remote access” does not seem to align with the “timely manners” guidance given on page 15, line 23   of the Guidance and Examples document. This capability to disable during the remote access session may not always be possible and would be dependent on how the unauthorized activity was detected.

 

Consider eliminating sub requirements 4.1 and 4.2 since they are covered in CIP-005 and CIP-007, R5 respectively. Consider addressing sub requirement 4.3 by modifying CIP-005 thus eliminating R4 from the proposed CIP-013 standard.

 

R4 should be moved to CIP-005 since this requirement, as written in CIP-013, only applies to vendors having remote access. This does not address other sources of remote access threats as written.

 

For R4.2, we suggest limiting the retention period for evidence logs to 90 days to be consistent with CIP-007 R4, Parts 4.1, 4.2, and 4.3.

 

This would increase the scope of file integrity monitoring to Medium impact devices, some which are not capable of logging. This would discourage entities from allowing vendors to ever log in remotely, which might hinder reliability in the case of required emergency troubleshooting/support. Lack of timely support would also force entities to be non-compliant with other standards, such as other CIPs.

 

Remove vendor remote access from scope and only include system-to-system. Vendor remote access is already addressed in CIP-005 R2.

 

SDT appears to be building on top of CIP-005 R1.5; however, R4.3 says “during the remote access session,” which may not reasonable amount of time since this is a real-time action.

RSC no Dominion and NextEra, Segment(s) 1, 0, 2, 4, 5, 6, 7, 3, 3/6/2017

- 0 - 0

The NERC CIP Cyber Security Standards already have one of the most specific remote access security standard through CIP-005. Additional specifications to remote access should not be placed in a supply chain cyber security risk management Standard.

Philip Huff, On Behalf of: Philip Huff, , Segments 3, 4, 5, 6

- 0 - 0

George Tatar, 3/6/2017

- 0 - 0

Wes Wingen, 3/6/2017

- 0 - 0

We generally agree with EEI’s comments, except for the exclusion of EACMS, PACs and PCAs for Requirement 1.

Jamie Monette, Allete - Minnesota Power, Inc., 1, 3/6/2017

- 0 - 0

SunPower believes identifying and logging unauthorized access is already covered. In CIP-005. Furthermore, SunPower believes that 4.3, disabling the threat of unauthorized access to BES Cyber Systems should be addressed through a revision to CIP-007, where controls for external access are covered. 

Bradley Collard, 3/6/2017

- 0 - 0

Kansas City Power and Light Company incorporates by reference Edison Electric Institute’s comments to Question 4.

Douglas Webb, 3/6/2017

- 0 - 0

N/A

Oxy, Segment(s) 7, 5, 9/6/2016

- 0 - 0

This Requirement is duplicative of CIP-005-5.

Heather Morgan, EDP Renewables North America LLC, 5, 3/6/2017

- 0 - 0

We have questions and concerns about how R4 would be applied. Please see the associated comments in Question 9. 

Sergio Banuelos, On Behalf of: Tri-State G and T Association, Inc., MRO, WECC, Segments 1, 3, 5

- 0 - 0

Concur with EEI’s Position

Linsey Ray , 3/6/2017

- 0 - 0

- See APPA's comments, with which SVP agrees.

Val Ridad, On Behalf of: Silicon Valley Power, WECC, Segments 1

- 0 - 0

The standard should not create additional requirements for which entities are already being audited against. This creates confusion and risks the entity to being in double jeopardy for the same activity.  NRECA recommends revising R4 to address the following:

 

R4, Part 4.1 is already covered under CIP-004-6 R4, Part 4.1

R4, Part 4.2 is already covered under CIP-007-6 R4, Part 4.1

R4, P4.3 is already covered under with CIP-005-5

Barry Lawson, 3/6/2017

- 0 - 0

Access into the ESP is controlled for vendors the same as FTEs. That process is already outlined in other CIP requirements. If this is meant to be an alternative avenue of access outside the rest of the standards that is not clear.

Scott Downey, 3/6/2017

- 0 - 0

EPE shares the comments and concerns voiced by the Edison Electric Institute (EEI) in this Ballot #1.  Please refer to the EEI ballot for detailed comments on each of the proposed requirements.  

Luis Rodriguez, El Paso Electric Company, 6, 3/6/2017

- 0 - 0

EPE shares the comments and concerns voiced by the Edison Electric Institute (EEI) in this Ballot #1.  Please refer to the EEI ballot for detailed comments on each of the proposed requirements.

Pablo Onate, El Paso Electric Company, 1, 3/6/2017

- 0 - 0

We are in general agreement with EEI comments on this requirement.

Luminant, Segment(s) 6, 7, 5, 1/24/2017

- 1 - 0

EPE shares the comments and concerns voiced by the Edison Electric Institute (EEI) in this Ballot #1.  Please refer to the EEI ballot for detailed comments on each of the proposed requirements

Victor Garzon, 3/6/2017

- 0 - 0