2021-04 Modifications to PRC-002 | Draft 1
Description:
Start Date: 06/09/2022
End Date: 07/25/2022
Associated Ballots:
Ballot Name | Project | Standard | Pool Open | Pool Close | Voting Start | Voting End |
---|---|---|---|---|---|---|
2021-04 Modifications to PRC-002 | Draft 1 PRC-002-4 IN 1 ST | 2021-04 Modifications to PRC-002 | Draft 1 | PRC-002-4 | 06/09/2022 | 07/08/2022 | 07/15/2022 | 07/25/2022 |
2021-04 Modifications to PRC-002 | Draft 1 PRC-002-4 | Non-binding Poll IN 1 NB | 2021-04 Modifications to PRC-002 | Draft 1 | PRC-002-4 | Non-binding Poll | 06/09/2022 | 07/08/2022 | 07/15/2022 | 07/25/2022 |
2021-04 Modifications to PRC-002 | Draft 1 Implementation Plan IN 1 OT | 2021-04 Modifications to PRC-002 | Draft 1 | Implementation Plan | 06/09/2022 | 07/08/2022 | 07/15/2022 | 07/25/2022 |
Hot Answers
1) Manitoba Hydro is unclear on the intent of the changes made to R1, which requires SER and FR data for the remote end? 2) For clarity, Manitoba Hydro recommends that the sentance: "Notify other owners of BES Elements, for which the Transmission Owner does not record SER or FR data, connected directly to those BES buses that they are responsible for recording the SER or FR data. This notification is required within 90 calendar days of completion of Part 1.1. If the owner of a BES Element is no longer required to have SER or FR data, notify the owner within 90 calendar days." be reworded to read "Notify other owners of BES Elements directly connected to those BES buses, for which the Transmission Owner does not record SER or FR data that they are responsible for recording the SER or FR data. This notification is required within 90 calendar days of completion of Part 1.1. If the owner of a BES Element is no longer required to have SER or FR data, notify the owner within 90 calendar days.”
Nazra Gladu, Manitoba Hydro , 1, 6/28/2022
- 0 - 0
Wendy DeVries, On Behalf of: CMS Energy - Consumers Energy Company, RF, Segments 1, 5
- 0 - 0
Other Answers
Jessica Cordero, On Behalf of: Unisource - Tucson Electric Power Co., WECC, Segments 1
- 0 - 0
Hot Answers
Manitoba Hydro proposes that language in sections 13.1. and 13.2. be revised to read:
13.1. Within three (3) years of receiving notification under Requirement R1, Parts 1.2 and 1.3, have SER or FR data as applicable for BES Elements directly connected to BES buses identified during the re-evaluation.
13.2. Within three (3) years of receiving notification under Requirement R5, Parts 5.3 and 5.4, have DDR data for BES Elements identified during the re-evaluation.
Nazra Gladu, Manitoba Hydro , 1, 6/28/2022
- 0 - 0
The 3 year implementation time frame might be to constrictive especially in light of recent material shortages. Suggest a 7 year time frame would allow BES element owners time to work the project into their schedule and procure equipment and resources.
Wendy DeVries, On Behalf of: CMS Energy - Consumers Energy Company, RF, Segments 1, 5
- 0 - 0
Other Answers
Jessica Cordero, On Behalf of: Unisource - Tucson Electric Power Co., WECC, Segments 1
- 0 - 0
Hot Answers
Manitoba Hydro proposes that language for requirement R3 be updated to read “Each Transmission Owner and Generator Owner shall have FR data to determine the following electrical quantities for each triggered FR for the BES Elements it owns that are directly connected to the BES buses identified in Requirement R1".
Nazra Gladu, Manitoba Hydro , 1, 6/28/2022
- 0 - 0
The implementation time frame of 3 years isn't long enough for a BES element owner to gather bids, procure materials, and schedule the work, and then install the equipment. Time frame should be extended to 7 years if not that at least, 5 years.
Wendy DeVries, On Behalf of: CMS Energy - Consumers Energy Company, RF, Segments 1, 5
- 0 - 0
Other Answers
Jessica Cordero, On Behalf of: Unisource - Tucson Electric Power Co., WECC, Segments 1
- 0 - 0