2020-03 Supply Chain Low Impact Revisions (Draft 2)

Description:

Start Date: 02/25/2022
End Date: 04/15/2022

Associated Ballots:

Ballot Name Project Standard Pool Open Pool Close Voting Start Voting End
2020-03 Supply Chain Low Impact Revisions CIP-003-X AB 2 ST 2020-03 Supply Chain Low Impact Revisions CIP-003-X 08/27/2021 09/27/2021 04/06/2022 04/15/2022

Filter:

Hot Answers

Southern Company, Segment(s) 1, 3, 6, 5, 1/14/2021

- 0 - 0

Cowlitz PUD supports the comments submitted by Utility Services Inc.

Deanna Carlson, Cowlitz County PUD, 5, 4/15/2022

- 0 - 0

Other Answers

Patricia Lynch, NRG - NRG Energy, Inc., 5, 3/23/2022

- 0 - 0

Jay Sethi, On Behalf of: Manitoba Hydro - MRO - Segments 1, 3, 5, 6

- 0 - 0

Reclamation recommends the SDT align the CIP-003 Attachment 1 Section 6 language with CIP-005-6 R2 and use NERC-defined terms where possible. The content of Section 6 should be included within Attachment 1 Section 3 and not made into a new section. Reclamation recommends adding “if technically feasible” to Section 6.2 to account for leagacy systems that are not capable of detecting known or suspected malicious communications for both inbound and outbound communications.

Reclamation recommends the following changes to Section 6:

From:

Vendor remote access: For assets containing low impact BES Cyber System(s) identified pursuant to CIP-002, the Responsible Entity shall implement a process to mitigate risks associated with vendor remote access (including interactive and system-to-system access) to low impact BES Cyber Systems that includes:

6.1 Having one or more method(s) for determining vendor remote access sessions;

6.2 Having one or more method(s) for detecting known or suspected malicious communications for both inbound and outbound communications; and

6.3 Having one or more method(s) for disabling vendor remote access.

To:

Vendor remote access: For assets containing low impact BES Cyber System(s) identified pursuant to CIP-002, the Responsible Entity shall implement a process to mitigate risks associated with active vendor remote access sessions (including Interactive Remote Access and system-to-system remote access) to low impact BES Cyber Systems that includes:

6.1 Having one or more method(s) for identifying active vendor remote access sessions;

6.2 If technically feasible, have one or more method(s) for detecting known or suspected malicious communications for both inbound and outbound communications; and

6.3 Having one or more method(s) for disabling active vendor remote access.

The phrase “determining active vendor remote access sessions” is not clear. Reclamation recommends using the same language as in the Technical Rationale, which refers more specifically to ”when sessions are initiated.”

Richard Jackson, On Behalf of: U.S. Bureau of Reclamation, , Segments 1, 5

- 0 - 0

Jennifer Malon, On Behalf of: Black Hills Corporation - MRO, WECC - Segments 1, 3, 5, 6

- 0 - 0

Tennessee Valley Authority, Segment(s) 1, 3, 5, 6, 10/18/2018

- 0 - 0

Joseph Amato, Berkshire Hathaway Energy - MidAmerican Energy Co., 3, 4/6/2022

- 0 - 0

Santee Cooper, Segment(s) 1, 3, 5, 6, 4/6/2022

- 0 - 0

Mike Marshall, 4/6/2022

- 0 - 0

As with the previous draft, Section 6.3 still creates a higher bar for some assets containing low impact BCS than for most medium impact BCS.  Section 6.3 would require detection of malicious inbound and outbound communications for low impact BCS with vendor remote connectivity.  In the current version and next effective version of CIP-005, Part 1.5 requires detection of malicious inbound and outbound communications only for medium impact BCS at Control Centers.

The Technical Rationale points out that Mediums already have other requirements (“use of intermediate systems and multi-factor authentication”) which can be used to PROTECT against malicious communication; however, none of those requirements specifically require that entities DETECT malicious communication at Mediums.  Until this gap is fixed, entities will be expected to detect malicious communications at certain of their Low assets but none of their Medium assets outside of a control center.

In addition, BPA is concerned that by not properly limiting the scope statement for Section 6 to sites with vendor remote access, we may have to prove a negative.

BPA recommends the following revision:

Section 6. Electronic Vendor Remote Access Security Controls: For assets containing low impact BES Cyber System(s) with vendor remote access identified pursuant to CIP-002, the Responsible Entity shall implement a process to mitigate risks associated with electronic vendor remote access. These processes shall include…

Andrea Jessup, On Behalf of: Bonneville Power Administration, WECC, Segments 1, 3, 5, 6

- 0 - 0

While we agree with the updated language as a whole, we support EEI’s proposed modification to Attachment 1 Section 6, as it adds clarity.

Ellese Murphy, On Behalf of: Duke Energy - MRO, WECC, Texas RE, SERC, RF - Segments 1, 3, 5, 6

- 0 - 0

Lan Nguyen, On Behalf of: CenterPoint Energy Houston Electric, LLC, Texas RE, Segments 1

- 0 - 0

No comment

Wes DeKemper, On Behalf of: Southern Indiana Gas and Electric Co., RF, Segments 3, 5, 6

- 0 - 0

Donald Lock, On Behalf of: Talen Generation, LLC, , Segments 5

- 0 - 0

JT Kuehne, AEP, 6, 4/8/2022

- 0 - 0

Scott Miller, 4/8/2022

- 0 - 0

Jeanne Kurzynowski, On Behalf of: CMS Energy - Consumers Energy Company, RF, Segments 1, 3, 5

- 0 - 0

Lindsey Mannion, ReliabilityFirst , 10, 4/11/2022

- 0 - 0

The introduction of “detecting known or suspected malicious communications” for low impact BES Cyber Systems would be more stringent as compared to CIP-005 R1.5 since Medium Impact BES Cyber Systems are not applicable in the current version of the standards without adding any additional reliability benefits.

Dominion, Segment(s) 3, 5, 1, 9/19/2019

- 0 - 0

Steve Toosevich, NiSource - Northern Indiana Public Service Co., 1, 4/11/2022

- 0 - 0

WECC Entity Monitoring, Segment(s) 10, 1/30/2022

- 0 - 0

Michelle Amarantos, APS - Arizona Public Service Co., 5, 4/11/2022

- 0 - 0

It does address the risk, but as written increases some security requirements beyond what is required for Medium Impact BES Cyber Systems.

Glen Farmer, Avista - Avista Corporation, 5, 4/11/2022

- 0 - 0

Jesus Sammy Alcaraz, Imperial Irrigation District, 1, 4/11/2022

- 0 - 0

Tim Kelley, On Behalf of: Nicole Looney, Sacramento Municipal Utility District, 1,3,4,5,6; Foung Mua, Sacramento Municipal Utility District, 1,3,4,5,6; Nicole Goi, Sacramento Municipal Utility District, 1,3,4,5,6; Kevin Smith, Balancing Authority of Northern California, 1; Charles Norton, Sacramento Municipal Utility District, 1,3,4,5,6

- 0 - 0

Lindsay Wickizer, Berkshire Hathaway - PacifiCorp, 6, 4/11/2022

- 0 - 0

Israel Perez, On Behalf of: Salt River Project - WECC - Segments 1, 3, 5, 6

- 0 - 0

Texas Re appreciates the SDT and NERC legal looking into the issue of whether or not Part 1 of the NERC resolution has been satisfied.  Texas RE suggests the SAR and the report do provide flexibility for the SDT to consider language for detecting known or suspected malicious communications for all inbound and outbound communications, and not be limited to vendor inbound and outbound communications.  Texas RE continues to recommend the SDT clarify that CIP-003 low impact monitoring obligations extend to all inbound and outbound network traffic to mitigate the risk of suspicious or malicious traffic going unnoticed, not just in situations of vendor remote access.  Texas RE notes this approach is consistent with FERC’s January 20, 2022 Notice of Proposed Rulemaking (NOPR) regarding internal network security monitoring.

Rachel Coyne, Texas Reliability Entity, Inc., 10, 4/12/2022

- 0 - 0

While the proposed language addresses the risks outlined by the NERC Board resolution, adding the word “vendor”, not a NERC defined term, to the requirement from the previously posted :  “One or more method(s) for detecting known or suspected malicious communications for both inbound and outbound vendor communications” doesn’t materially change this requirement is more stringent than those required by CIP-005 R1.5 for medium impact BES Cyber Systems NOT at Control Centers.  Further reducing the scope of the requirement to only vendor communications, we don’t feel reduces risks to an acceptable level for NERC or FERC.  If entities are going to be required to detect malicious communications, it should be all or nothing.  Additionally, vendor is not a NERC defined term, so having to prove each monitored communication path is or isn’t for a vendor would be overly burdensome. 

Susan Sosbe, Wabash Valley Power Association, 3, 4/12/2022

- 0 - 0

See EEI comment.

Clay Walker, On Behalf of: John Lindsey, Cleco Corporation, 1,3,5,6; Robert Hirchak, Cleco Corporation, 1,3,5,6; Maurice Paulk, Cleco Corporation, 1,3,5,6

- 0 - 0

It does address the risk, but as written increases some security requirements beyond what is required for Medium Impact BES Cyber Systems.

Scott Kinney, Avista - Avista Corporation, 3, 4/12/2022

- 0 - 0

AEPCO is signing on to ACES comments below:

ACES Comments:  While the proposed language addresses the risks outlined by the NERC Board resolution, adding the word “vendor”, not a NERC defined term, to the requirement from the previously posted :  “One or more method(s) for detecting known or suspected malicious communications for both inbound and outbound vendor communications” doesn’t materially change this requirement is more stringent than those required by CIP-005 R1.5 for medium impact BES Cyber Systems NOT at Control Centers.  Further reducing the scope of the requirement to only vendor communications, we don’t feel reduces risks to an acceptable level for NERC or FERC.  If entities are going to be required to detect malicious communications, it should be all or nothing.  Additionally, vendor is not a NERC defined term, so having to prove each monitored communication path is or isn’t for a vendor would be overly burdensome.

Jennifer Bray, Arizona Electric Power Cooperative, Inc., 1, 4/12/2022

- 0 - 0

PNM supports the EEI inclusion of the word “active” in 6.1 and 6.2. However, with the inclusion of the word “active”, the current proposed language in 6.1 and 6.2 which reads, “where such access has been established under Section 3” may be redundant.

PNM supports EEI comments regarding 6.3 to more specifically narrow the scope of detecting known or suspected malicious communications for both inbound and outbound “electronic vendor remote access, where such access has been established under section 3.”

Lynn Goldstein, PNM Resources - Public Service Company of New Mexico, 1, 4/12/2022

- 0 - 0

Refer to NAGF comment

patricia ireland, DTE Energy, 4, 4/13/2022

- 0 - 0

Xcel Energy agrees that Attachment 1 Section 6 addresses the risk malicious communication posed by vendors accessing low impact BES cyber systems from remote locations. However, there is a lack of clarity of which types of cyber assets are in scope for subpart 6.3. Xcel Energy suggests that language of "as established in section 3" be added to section 6.3 as it is in sections 6.1 and 6.2.  

Joe Gatten, On Behalf of: Xcel Energy, Inc. - MRO, WECC - Segments 1, 3, 5, 6

- 0 - 0

Donna Wood, Tri-State G and T Association, Inc., 1, 4/13/2022

- 0 - 0

Larry Heckert, Alliant Energy Corporation Services, Inc., 4, 4/13/2022

- 0 - 0

LaTroy Brumfield, American Transmission Company, LLC, 1, 4/13/2022

- 0 - 0

FirstEnergy feels Attachment 1 Section 6.3 is not clear in its intention of the standard and obligation of industry. We feel Attachment 1 Section 6.3 needs to be drafted to be as clear as 6.1 and 6.2

FE Voter, Segment(s) 1, 3, 5, 6, 4, 12/20/2021

- 0 - 0

Based on comments below, we conclude the proposed updates do not adequately address the risk of malicious communication and vendor remote access.

Carl Pineault, On Behalf of: Hydro-Qu?bec Production, , Segments 1, 5

- 0 - 0

Evergy supports and incorporates the comments from the Edison Electric Institute (EEI) for questions #1.

- 0 - 0

BC Hydro appreciates the opportunity to reeview and provides the following comments.

BC Hydro's assessment is that the language proposed in CIP-003-X attachment 1 Section 6 does not comprehensively address the risk of malicious communication and vendor remote access to low impact BES cyber systems with possible areas of improvement as follows:

  • The language used in CIP-003-X attachment 1 Section 6.3 is referring to 'known or suspected malicious communications'. BC Hydro recommends adding more clarity and provide examples of use cases and applicability. Specifically, context and usage of the term 'malicious communication' needs more clarity and BC Hydro requests to provide the context and usage with pertinent examples and use case scenarios to improve understanding and to better scope the requirements.
  • Similarly, BC Hydro proposes defining and adding the term 'Electronic Vendor Remote Access' to NERC Glossary of Terms
  • Bc Hydro also suggests that who and what is to be considered a 'Vendor' needs to be defined in the Glossary of Terms for clarity.

CIP-005-5 R1.5 does not apply to Medium impact BCS if they are not at Control Centers. Why and how the Requirement in Section 6.3 applies to 'Low Impact BCS' is not very clear from the language used. The Section 6.3 does offer possible mitigation of the risks i.e., 'malicious communication and vendor remote access; however, this is even more stringent on Low Impact BCS in comparison to CIP-005-5 R1.5. BC Hydro recommends rewording or removing Section 6.3 completely.

BC Hydro, Segment(s) 3, 5, 1, 12/18/2018

- 0 - 0

We agee because this gives the ability to disconnect, we ask the drafting team to include examples of evidence for this requirement (log ins?).

David Jendras, Ameren - Ameren Services, 3, 4/14/2022

- 0 - 0

For this question we conclude the proposed updates do not adequately address the risk of malicious communication and vendor remote access.

Gerry Adamski, On Behalf of: Cogentrix Energy Power Management, LLC, , Segments 5

- 0 - 0

The MRO NERC Standards Review Forum (NSRF) agrees proposed language addresses the risk. 

MRO NSRF, Segment(s) 2, 3, 5, 1, 4, 6, 4/11/2022

- 0 - 0

Acciona Energy supports Midwest Reliability Organization’s (MRO) NERC Standards Review Forum’s (NSRF) comments on this question.

George Brown, Acciona Energy North America, 5, 4/14/2022

- 0 - 0

It does address the risk, but as written increases some security requirements beyond what is required for Medium Impact BES Cyber Systems.

Mike Magruder, Avista - Avista Corporation, 1, 4/14/2022

- 0 - 0

No Comment

Brian Lindsey, Entergy, 1, 4/14/2022

- 0 - 0

NextEra Energy respectfully submits the following language changes to Attachment 1 and Attachment 2 replacing “electronic vendor remote access” with “Vendor Electronic Remote Access” for consistency and clarification. 

Consider the following language:

x Attachment 1 

Section 6. Vendor Electronic Remote Access Security Controls: For assets containing low impact BES Cyber System(s) identified pursuant to CIP-002, the Responsible Entity shall implement a process to mitigate risks associated with vendor electronic remote access. These processes shall include: 

6.1 One or more method(s) for determining vendor electronic remote access where such access has been established under Section 3; 

6.2 One or more method(s) for disabling vendor electronic remote access where such access has been established under Section 3; and 

6.3 One or more method(s) for detecting known or suspected malicious communications for both inbound and outbound vendor communications supporting vendor electronic remote access

CIP-003-x Attachment 2 

Section 6. Vendor Electronic Remote Access Security Controls: Examples of evidence showing the implementation of the process for Section 6 to mitigate risks associated with vendor electronic remote access may include, but are not limited to: 

1. For Section 6.1, documentation showing method(s) for determining vendor electronic remote access where such access has been established under Section 3 that may including the following: 

  • steps to preauthorize access; 

  • alerts generated by vendor log on; 

  • session monitoring; 

  • Security Information Management logging alerts; 

  • time-of-need session initiation; 

  • session recording; 

  • system logs; or 

  • other operational, procedural, or technical controls. 

2. For Section 6.2, documentation showing method(s) for disabling vendor electronic remote access where such access has been established under Section 3 that may including the following

  • disabling vendor electronic remote access user or system accounts; 

  • disabling inbound and/or outbound hardware or software ports, services, or access permissions on applications, firewall, IDS/IPS, router, switch, VPN, Remote Desktop, remote control, or other hardware or software used for providing active vendor electronic remote access; 

  • disabling communications protocols (such as IP) used for systems which establish and/or maintain active vendor electronic remote access

  • Removing physical layer connectivity (e.g., disconnect an Ethernet cable, power down equipment); 

  • administrative control documentation listing the methods, steps, or systems used to disable active vendor electronic remote access; or 

  • other operational, procedural, or technical controls. 

3. For Section 6.3, documentation showing implementation of method(s) for detecting known or suspected malicious communications for both inbound and outbound vendor electronic access communications that may including the following

  • Firewall policies; 

  • Intrusion Detection System (IDS)/Intrusion Prevention System (IPS); 

  • Virtual Private Network (VPN) hosts; 

  • manual log reviews; or 

  • other operational, procedural, or technical controls. 

Mike ONeil, 4/14/2022

- 0 - 0

Anything  prompting action at the low impact level must be very succinct otherwise risk overwhelming already taxed resources devoted to cyber security.  More detail must be developed to limit the scope of communications that will be covered.

Gail Elliott, On Behalf of: International Transmission Company Holdings Corporation - MRO, RF - Segments NA - Not Applicable

- 0 - 0

LCRA believes the proposed language is improved upon since the last posting; however, LCRA believes it would be more clear and consistent to have the language in Attachement 1 Section 6 more closely resemble the language as written in the NERC Board resolution and the CIP-005 Standard.

LCRA Compliance, Segment(s) 6, 5, 1, 5/11/2015

- 0 - 0

The NAGF previously recommended that the SDT align the language to include the word “active”, which is utilized in both the Board Resolution and CIP-005 R2.4. The NAGF is concerned that using the word “electronic” may cause a differing definition and expectation to be developed over time compared to the objective of the language in the Board Resolution. Does the SDT view “active” and “electronic” as synonymous terms? If the SDT does not see “active” and “electronic” remote vendor access as synonymous further definition of “electronic” is required.

Wayne Sipperly, On Behalf of: North American Generator Forum, MRO, WECC, Texas RE, NPCC, SERC, RF, Segments 5

- 0 - 0

LCRA believes the proposed language is improved upon since the last posting; however, LCRA believes it would be more clear and consistent to have the language in Attachement 1 Section 6 more closely resemble the language as written in the NERC Board resolution and the CIP-005 Standard.

James Baldwin, Lower Colorado River Authority, 1, 4/15/2022

- 0 - 0

While the proposed language addresses the risks outlined by the NERC Board resolution, adding the word “vendor”, not a NERC defined term, to the requirement from the previously posted :  “One or more method(s) for detecting known or suspected malicious communications for both inbound and outbound vendor communications” doesn’t materially change this requirement is more stringent than those required by CIP-005 R1.5 for medium impact BES Cyber Systems NOT at Control Centers.  Further reducing the scope of the requirement to only vendor communications, we don’t feel reduces risks to an acceptable level for NERC or FERC.  If entities are going to be required to detect malicious communications, it should be all or nothing.  Additionally, vendor is not a NERC defined term, so having to prove each monitored communication path is or isn’t for a vendor would be overly burdensome. 

ACES Standard Collaborations, Segment(s) 1, 3, 5, 4, 4/15/2022

- 0 - 0

EEI recognizes that the proposed changes under this project are intended to align with the NERC Board resolution, however, EEI is concerned that the proposed Draft 2 language in Attachment 1, Section 6 goes beyond the intent of the Board resolution by being overly broad.  In addition, the proposed language in Section 6 is not risk-based and could be understood to mean all low impact BES Cyber System communications are included.   As a result, entities would be faced with difficult choices that include how to safely allocate scarce resources (i.e., limited budgets and qualified SMEs) to meet existing CIP-003 requirements while also covering the unfettered expansion of low impact BES Cyber System communications.  To address this concern, we ask that the SDT employ a risk-based approach that allows entities to develop processes that focus their resources on those systems that represent  known risks.

In addition to the above concern, EEI supports the proposed language in Section 6, subparts 6.1 and 6.2 but suggests some minor edits as indicated in the bold text below.  In particular the proposed language for subpart 6.3 is not sufficiently aligned with communications as established under Section 3.  The introduction of the new undefined term “vendor communications” needs additional explanation or clarification because it is treated separately and not aligned with Section 3.  For these reasons, we recommend adding the text in bold to define the scope more clearly.

Section 6: Electronic Vendor Remote Access Security Controls: For assets containing low impact BES Cyber System(s) identified pursuant to CIP-002, the Responsible entity shall implement a process to mitigate risks associated with electronic vendor remote access.  These process shall include:

6.1: One or more method(s) for determining when active electronic vendor remote access has been initiated; where such access has been established under Section 3;

6.2: One or more method(s) for disabling active electronic vendor remote access when necessary; where such access has been established under Section 3; and

6.3: One or more method(s) for detecting known or suspected malicious communications for both inbound and outbound electronic vendor remote access, where such access has been established under Section 3.

Mark Gray, On Behalf of: Edison Electric Institute, NA - Not Applicable, Segments NA - Not Applicable

- 0 - 0

Based on the comments below, we conclude the proposed updates do not adequately address the risk of malicious communication and vendor remote access.

NPCC Regional Standards Committee, Segment(s) 10, 2, 4, 7, 3, 1, 5, 6, 4/6/2022

- 0 - 0

Dwanique Spiller, Berkshire Hathaway - NV Energy, 5, 4/15/2022

- 0 - 0

No comment.

John Galloway, On Behalf of: Michael Puscas, ISO New England, Inc., 2

- 0 - 0

While GSOC agrees that the proposed language addresses the risks identified by the NERC Board Resolution, it is concerned that the absence of the term “active” broadens this requirement beyond the obligations set forth to manage vendor access for medium and high impact BES cyber assets.  In particular, the language of the similar requirements for vendor access management in CIP-005-7, R2.4 and R2.5 focuses the requirements on determining and disabling “active vendor remote access sessions.”  The language proposed in Attachment 1, Sections 6.1 and 6.2, however, could be interpreted to apply to any authorized vendor remote access – regardless of whether or not the vendor has initiated or is in an active remote access session.

Such a requirement would result in low impact BES cyber assets being subject to more stringent security controls than high or medium impact BES cyber assets and appears to conflict with the Technical Rationale for these sections as provided on page 5 of the proposed Technical Rationale document.  To ensure that the security controls applied to low impact BES cyber assets are commensurate with risk and not more stringent than those applied to high and medium impact BES cyber assets, GSOC recommends that the SDT mirror the language provided in CIP-005-7, R2.4 and R2.5 to the extent possible.  For example, revisions could be made as follows:

For assets containing low impact BES Cyber System(s) identified pursuant to CIP-002, the Responsible Entity shall implement a process to mitigate risks associated with electronic vendor remote access. These processes shall include:

6.1 One or more method(s) for determining active electronic vendor remote access sessions where such access has been established under Section 3;

6.2 One or more method(s) for disabling active electronic vendor remote access where such access has been established under Section 3; …

Benjamin Winslett, Georgia System Operations Corporation, 4, 4/15/2022

2020-03_Supply_Chain_Lows_Unofficial_Comment_Form.docx

- 0 - 0

The language used in of the NERC Board resolution states the CIP-003 is “to include policies for low impact BES Cyber Sytems…”. We agree with the SDT’s interpretation that 3 controls listed in the resolution should be addressed not only in the CIP-003 R1.2, policies but in the plans required in CIP-003 R2 and Attachment 1. While the R2 additions are an expansion beyond the NERC Board resolution, they are required to meet the intent of the resolution.

Because CIP-003 Attachment 1 is written to apply at the “assets containing low impact BES Cyber Systems” and not to just the “BES Cyber Systems”, the 3 controls listed in the NERC Board resolution could be required to be applied to more than low impact BCS. This expansion in scope beyond low impact BCS is not required by the NERC Board resolution. The expansion could include additional controls being required for medium and high impact Cyber Assets beyond what are included in as “Applicable Systems” in CIP-005 R1.5 and R3. Regarding the control concerning malicious communication, we feel that this should be limited to only low impact BCS at Control Centers to align with CIP-005 R1.5.

An interpretation of what the SDT has proposed could require the detection of malicious voice communication, text messages, or emails from anyone to anyone that is at an asset containing low impact BES Cyber Systems.

The NERC Board resolution includes the implementation of controls to “disable active vendor remote access.”  CIP-005 R2.5 addresses disabling active vendor remote access and R3.2 addresses terminating vendor initiated remote connections. The actions listed in Attachment 2 and the language used in the Technical Rational for Attachment 1 Section 6 Part 6.2 combine disabling and terminating as part of the required control. The SDT should limit the scope to disabling active vendor remote access.

Brian Evans-Mongeon, Utility Services, Inc., 4, 4/15/2022

- 0 - 0

Based on comments below, we conclude the proposed updates do not adequately address the risk of malicious communication and vendor remote access.

Devon Tremont, Taunton Municipal Lighting Plant, 1, 4/15/2022

- 0 - 0

Martin Sidor, NRG - NRG Energy, Inc., 6, 4/15/2022

- 0 - 0

Exelon believe registered entities could accomplish this, however it would be difficult to tell what the malicious intent really is.  We do understand, however IDS can help with the inspection of packets. But without the information it could be expensive.  Deploying controls at lows without having all of the information accounted for is concerning.  This would require the need to have IPS on all of the low firewalls, including monitoring.  Exelon has concerns around subpart 6.3 additional clarity is needed.  The new term “vendor communications” needs explanation.  

Daniel Gacek, Exelon, 1, 4/15/2022

- 0 - 0

Exelon believe registered entities could accomplish this, however it would be difficult to tell what the malicious intent really is.  We do understand, however IDS can help with the inspection of packets. But without the information it could be expensive.  Deploying controls at lows without having all of the information accounted for is concerning.  This would require the need to have IPS on all of the low firewalls, including monitoring.  Exelon has concerns around subpart 6.3 additional clarity is needed.  The new term “vendor communications” needs explanation.

Kinte Whitehead, Exelon, 3, 4/15/2022

- 0 - 0

Constellation has elected to align with Exelon in response to this question. 

Entities could accomplish this, however it could be difficult to tell what malicious intent really is.  We do understand IDS can help with the inspection of packets. Without the information it could be expensive.  Deploying controls at lows without having all of the information accounted for is concerning.  This would require the need to have IPS on all of the low firewalls, including monitoring.  Exelon has concerns around subpart 6.3 additional clarity is needed.  The new term “vendor communications” needs explanation. 

Kimberly Turco, Constellation, 6, 4/15/2022

- 0 - 0

Constellation has elected to align with Exelon in response to this question. 

Entities could accomplish this, however it could be difficult to tell what malicious intent really is.  We do understand IDS can help with the inspection of packets. Without the information it could be expensive.  Deploying controls at lows without having all of the information accounted for is concerning.  This would require the need to have IPS on all of the low firewalls, including monitoring.  Exelon has concerns around subpart 6.3 additional clarity is needed.  The new term “vendor communications” needs explanation. 

Alison Mackellar, Constellation, 5, 4/15/2022

- 0 - 0

Minnesota Power is in agreement with Edison Electrical Institute’s (EEI) comments and believes the drafted language more adequately addresses the purpose/goal as stated in the SAR and Technical Rationale

Jamie Monette, Allete - Minnesota Power, Inc., 1, 4/15/2022

- 0 - 0

FMPA supports comments from Utility Services, Inc. 

Florida Municipal Power Agency (FMPA), Segment(s) 5, 4, 3, 6, 4/15/2022

- 0 - 0

Selene Willis, Edison International - Southern California Edison Company, 5, 4/15/2022

- 0 - 0

Portland General Electric Company (PGE) supports the survey response provided by EEI.

PGE Group 2, Segment(s) 1, 3, 6, 5, 4/15/2022

- 0 - 0

Romel Aquino, Edison International - Southern California Edison Company, 3, 4/15/2022

- 0 - 0

Cowlitz PUD supports the comments submitted by Utility Services Inc.

Russell Noble, Cowlitz County PUD, 3, 4/15/2022

- 0 - 0

NST notes that the NERC BoT's resolution, as written, does not explicitly limit the application of a malicious code detection requirement to remote connections to or from vendors.

Roger Fradenburgh, On Behalf of: Nicholas Lauriat, Network and Security Technologies, 1

- 0 - 0

 PGE supports the survey response provided by EEI.

Daniel Mason, Portland General Electric Co., 6, 4/15/2022

- 0 - 0

Hot Answers

Header 6.1 and 6.2 - Add the word “active” in the requirement and move “electronic” adjective. One or more method(s) for determining active vendor electronic remote access where such access has been established in Section 3.

Southern Company, Segment(s) 1, 3, 6, 5, 1/14/2021

- 0 - 0

Cowlitz PUD supports the comments submitted by Utility Services Inc.

Deanna Carlson, Cowlitz County PUD, 5, 4/15/2022

- 0 - 0

Other Answers

If “remote access” is going to be brought into scope for low impact sites and the intent is for it to be limited strictly to remote access conducted by vendors, then the term needs to be in alignment with the “Interactive Remote Access” definition.  The manner in which Section 6 is currently written seems to imply that system-to-system communications will be included. 

Patricia Lynch, NRG - NRG Energy, Inc., 5, 3/23/2022

- 0 - 0

Jay Sethi, On Behalf of: Manitoba Hydro - MRO - Segments 1, 3, 5, 6

- 0 - 0

Reclamation recommends adding “Vendor” to the NERC Glossary of Terms and proposes the following definition:

Vendor - Persons, companies, or other organizations with whom the Responsible Entity, or its affiliates, contracts to supply equipment for BES Cyber Systems and related services. Vendor does not include other NERC-registered entities that provide reliability services (e.g., Balancing Authority or Reliability Coordinator services pursuant to NERC Reliability Standards). Vendor may include: (i) developers or manufacturers of information systems, system components, or information system services; (ii) product resellers; or (iii) system integrators. 

Richard Jackson, On Behalf of: U.S. Bureau of Reclamation, , Segments 1, 5

- 0 - 0

Jennifer Malon, On Behalf of: Black Hills Corporation - MRO, WECC - Segments 1, 3, 5, 6

- 0 - 0

Tennessee Valley Authority, Segment(s) 1, 3, 5, 6, 10/18/2018

- 0 - 0

Joseph Amato, Berkshire Hathaway Energy - MidAmerican Energy Co., 3, 4/6/2022

- 0 - 0

Santee Cooper, Segment(s) 1, 3, 5, 6, 4/6/2022

- 0 - 0

Mike Marshall, 4/6/2022

- 0 - 0

Andrea Jessup, On Behalf of: Bonneville Power Administration, WECC, Segments 1, 3, 5, 6

- 0 - 0

We believe that the language is clear.

Ellese Murphy, On Behalf of: Duke Energy - MRO, WECC, Texas RE, SERC, RF - Segments 1, 3, 5, 6

- 0 - 0

Remote access should be clearly defined as including interactive and system-to-system remote access.  CenterPoint Energy Houston Electric (CEHE)  proposes re-instating the wording from Draft 1 Attachment 1 Section 6 to give additional detail to remote access, “(including interactive and system-to-system access) to low impact BES Cyber Systems.”

Lan Nguyen, On Behalf of: CenterPoint Energy Houston Electric, LLC, Texas RE, Segments 1

- 0 - 0

Southern Indiana Gas and Electric (SIGE) does not believe that this language is clear or widely used. The most widely used description of remote access is interactive remote access. If the SDT intends to include system-to-system access then that should be made clear. Remote access should be clearly defined as interactive access and system-to-system remote access. SIGE proposes re-installing the wording from Draft 1 Attachment 1 Section 6 to give additional detail to remote access, “(including interactive and system-to-system access) to low impact BES Cyber Systems.”

Wes DeKemper, On Behalf of: Southern Indiana Gas and Electric Co., RF, Segments 3, 5, 6

- 0 - 0

Donald Lock, On Behalf of: Talen Generation, LLC, , Segments 5

- 0 - 0

JT Kuehne, AEP, 6, 4/8/2022

- 0 - 0

Scott Miller, 4/8/2022

- 0 - 0

Jeanne Kurzynowski, On Behalf of: CMS Energy - Consumers Energy Company, RF, Segments 1, 3, 5

- 0 - 0

Lindsey Mannion, ReliabilityFirst , 10, 4/11/2022

- 0 - 0

Dominion, Segment(s) 3, 5, 1, 9/19/2019

- 0 - 0

Steve Toosevich, NiSource - Northern Indiana Public Service Co., 1, 4/11/2022

- 0 - 0

WECC Entity Monitoring, Segment(s) 10, 1/30/2022

- 0 - 0

Michelle Amarantos, APS - Arizona Public Service Co., 5, 4/11/2022

- 0 - 0

The language is more clear, but does not really limit the effort to implement the control.

Glen Farmer, Avista - Avista Corporation, 5, 4/11/2022

- 0 - 0

Jesus Sammy Alcaraz, Imperial Irrigation District, 1, 4/11/2022

- 0 - 0

Tim Kelley, On Behalf of: Nicole Looney, Sacramento Municipal Utility District, 1,3,4,5,6; Foung Mua, Sacramento Municipal Utility District, 1,3,4,5,6; Nicole Goi, Sacramento Municipal Utility District, 1,3,4,5,6; Kevin Smith, Balancing Authority of Northern California, 1; Charles Norton, Sacramento Municipal Utility District, 1,3,4,5,6

- 0 - 0

Lindsay Wickizer, Berkshire Hathaway - PacifiCorp, 6, 4/11/2022

- 0 - 0

SRP would like to see “Electronic Vendor Remote Access” as a clearly defined term. For example, is web-conferencing considered electronic vendor remote access?

Israel Perez, On Behalf of: Salt River Project - WECC - Segments 1, 3, 5, 6

- 0 - 0

Rachel Coyne, Texas Reliability Entity, Inc., 10, 4/12/2022

- 0 - 0

Susan Sosbe, Wabash Valley Power Association, 3, 4/12/2022

- 0 - 0

See EEI comment.

Clay Walker, On Behalf of: John Lindsey, Cleco Corporation, 1,3,5,6; Robert Hirchak, Cleco Corporation, 1,3,5,6; Maurice Paulk, Cleco Corporation, 1,3,5,6

- 0 - 0

The language is more clear, but does not really limit the effort to implement the control.

Scott Kinney, Avista - Avista Corporation, 3, 4/12/2022

- 0 - 0

Jennifer Bray, Arizona Electric Power Cooperative, Inc., 1, 4/12/2022

- 0 - 0

PNM supports EEI comments regarding the needed clarity around “remote access” referring to user remote access, machine remote access, or both. 

Lynn Goldstein, PNM Resources - Public Service Company of New Mexico, 1, 4/12/2022

- 0 - 0

patricia ireland, DTE Energy, 4, 4/13/2022

- 0 - 0

Xcel Energy believes that the term "remote access" is commonly used to address electronic access originating from locations outside of protections established in an entities PSP and ESP.  

Joe Gatten, On Behalf of: Xcel Energy, Inc. - MRO, WECC - Segments 1, 3, 5, 6

- 0 - 0

Donna Wood, Tri-State G and T Association, Inc., 1, 4/13/2022

- 0 - 0

Larry Heckert, Alliant Energy Corporation Services, Inc., 4, 4/13/2022

- 0 - 0

LaTroy Brumfield, American Transmission Company, LLC, 1, 4/13/2022

- 0 - 0

FirstEnergy agrees with EEI’s comments: “While the term “remote access” is generally understood, it is unclear what it means in the context of this Reliability Standard.  Specifically, it is unclear whether the SDT meant this to mean user remote access, machine remote access or both.  For this reason, we ask that the SDT provide clearer direction within the Technical Rationale.”

FE Voter, Segment(s) 1, 3, 5, 6, 4, 12/20/2021

- 0 - 0

Recommend using the CIP terms of “interactive remote access” and “system-to-system access” instead of introducing a new term “Electronic vendor remote access.” Also, CIP-005 uses “vendor remote access.” Remote access implies “electronic” so “electronic” does not need inclusion in the term.

Carl Pineault, On Behalf of: Hydro-Qu?bec Production, , Segments 1, 5

- 0 - 0

Evergy supports and incorporates the comments from the Edison Electric Institute (EEI) for questions #2.

- 0 - 0

As mentioned in comments related to Question 1 above, ' Electronic Vendor Remote Access' needs additional clarity to ensure proper understanding of applicability as well as the use of term 'Vendor' e.g., whether consultant using same infrastructure is considered vendor?

BC Hydro, Segment(s) 3, 5, 1, 12/18/2018

- 0 - 0

David Jendras, Ameren - Ameren Services, 3, 4/14/2022

- 0 - 0

Recommend using the CIP terms of “interactive remote access” and “system-to-system access” instead of introducing a new term “Electronic vendor remote access.” Also, CIP-005 uses “vendor remote access.” Remote access implies “electronic” so “electronic” does not need inclusion in the term.

Gerry Adamski, On Behalf of: Cogentrix Energy Power Management, LLC, , Segments 5

- 0 - 0

The MRO NSRF believes that the language is properly scoped. 

MRO NSRF, Segment(s) 2, 3, 5, 1, 4, 6, 4/11/2022

- 0 - 0

Acciona Energy supports Midwest Reliability Organization’s (MRO) NERC Standards Review Forum’s (NSRF) comments on this question.

George Brown, Acciona Energy North America, 5, 4/14/2022

- 0 - 0

The language is more clear, but does not really limit the effort to implement the control.

Mike Magruder, Avista - Avista Corporation, 1, 4/14/2022

- 0 - 0

Generally “interactive” remote access is also used. Interactive means not only read only or view only access. This should be a part of the standard as if I am only viewing or retrieving read only data there is no ability for the remote connection to make changes or perform actions.

Brian Lindsey, Entergy, 1, 4/14/2022

- 0 - 0

Please see NEE’s response to question 1 respectfully submitting updated language  CIP-003 Attachment 1, Section 6 and Attachment 2, Section 6. 

Mike ONeil, 4/14/2022

- 0 - 0

More work should be undertaken to clearly define the terms remote access and the scenarios.

Gail Elliott, On Behalf of: International Transmission Company Holdings Corporation - MRO, RF - Segments NA - Not Applicable

- 0 - 0

LCRA Compliance, Segment(s) 6, 5, 1, 5/11/2015

- 0 - 0

The NAGF has no comments.

Wayne Sipperly, On Behalf of: North American Generator Forum, MRO, WECC, Texas RE, NPCC, SERC, RF, Segments 5

- 0 - 0

James Baldwin, Lower Colorado River Authority, 1, 4/15/2022

- 0 - 0

ACES Standard Collaborations, Segment(s) 1, 3, 5, 4, 4/15/2022

- 0 - 0

While the term “remote access” is generally understood, it is unclear what it means in the context of this Reliability Standard.  Specifically, it is unclear whether the SDT meant this to mean user remote access, machine remote access or both.  For this reason, we ask that the SDT provide clearer direction within the Technical Rationale.

Mark Gray, On Behalf of: Edison Electric Institute, NA - Not Applicable, Segments NA - Not Applicable

- 0 - 0

Recommend using the CIP terms “interactive remote access” and “system-to-system access” instead of introducing a new term “Electronic vendor remote access.” Also, CIP-005 uses “vendor remote access.” Remote access implies “electronic” so “electronic” does not need inclusion in the term.

NPCC Regional Standards Committee, Segment(s) 10, 2, 4, 7, 3, 1, 5, 6, 4/6/2022

- 0 - 0

Dwanique Spiller, Berkshire Hathaway - NV Energy, 5, 4/15/2022

- 0 - 0

No comment.

John Galloway, On Behalf of: Michael Puscas, ISO New England, Inc., 2

- 0 - 0

GSOC agrees that remote access is a widely used and understood term and would suggest that the language used in Attachment 1 more closely mirror the language utilized in CIP-005-7 to reduce the potential for additional confusion, ambiguity, and subjective interpretation.  Please see comments provided in response to question 1 above.

Benjamin Winslett, Georgia System Operations Corporation, 4, 4/15/2022

- 0 - 0

The SDT has used the word “electronic vendor remote access” and not the term “active vendor remote access” that is used in CIP-005-7 and in the NERC Board resolution. It is unclear why this inconsistency is needed or what the difference is between the two terms.

 

Furthermore when reviewing the Technical Rationale behind these proposed modifications, a footnote which had previously referenced guidance on the term “vendor” and how it may be used in the current version of CIP-013 and the future versions of CIP-005, CIP-010, and CIP-013, had been removed making for more confusion on what a vendor may be in this scope. Can the SDT please provide the reasoning for removing the footnote/reference from the Technical Rationale?

Brian Evans-Mongeon, Utility Services, Inc., 4, 4/15/2022

- 0 - 0

Recommend using the CIP terms of “interactive remote access” and “system-to-system access” instead of introducing a new term “Electronic vendor remote access.” 

Devon Tremont, Taunton Municipal Lighting Plant, 1, 4/15/2022

- 0 - 0

If “remote access” is going to be brought into scope for low impact sites and the intent is for it to be limited strictly to remote access conducted by vendors, then the term needs to be in alignment with the “Interactive Remote Access” definition.  The manner in which Section 6 is currently written seems to imply that system-to-system communications will be included. 

Martin Sidor, NRG - NRG Energy, Inc., 6, 4/15/2022

- 0 - 0

Exelon does not agree that it’s necessarily clear so can’t agree that its widely understood. The term ‘Remote’ can mean different things…a vendor thats internal/on site, physically remote externally to the site versus remote to the company, or a Verizon wireless card… or is it up to the Registered Entity to define it?

Daniel Gacek, Exelon, 1, 4/15/2022

- 0 - 0

Exelon does not agree that it’s necessarily clear so can’t agree that its widely understood. The term ‘Remote’ can mean different things…a vendor thats internal/on site, physically remote externally to the site versus remote to the company, or a Verizon wireless card… or is it up to the Registered Entity to define it?

Kinte Whitehead, Exelon, 3, 4/15/2022

- 0 - 0

Constellation has elected to align with Exelon in response to this question. 

Exelon doesn’t agree that it’s necessarily clear so can’t agree that its widely understood. The term ‘Remote’ can mean different things…a vendor thats internal/on site, physically remote externally to the site versus remote to the company, or a Verizon wireless card… or is it up to the Registered Entity to define it?

Kimberly Turco, Constellation, 6, 4/15/2022

- 0 - 0

Constellation has elected to align with Exelon in response to this question. 

Exelon doesn’t agree that it’s necessarily clear so can’t agree that its widely understood. The term ‘Remote’ can mean different things…a vendor thats internal/on site, physically remote externally to the site versus remote to the company, or a Verizon wireless card… or is it up to the Registered Entity to define it?

Alison Mackellar, Constellation, 5, 4/15/2022

- 0 - 0

Minnesota Power is in agreement with Edison Electric Institute’s (EEI) comments.  Draft 1 of Attachment 1 Section 6 included the clarifying language “(including interactive and system-to-system access)” which was removed from Draft 2, making it unclear what forms of access are in scope.  Additionally, the term “vendor” is an undefined term and should be clarified in the NERC Glossary of Terms.

Jamie Monette, Allete - Minnesota Power, Inc., 1, 4/15/2022

- 0 - 0

Florida Municipal Power Agency (FMPA), Segment(s) 5, 4, 3, 6, 4/15/2022

- 0 - 0

Selene Willis, Edison International - Southern California Edison Company, 5, 4/15/2022

- 0 - 0

 PGE supports the survey response provided by EEI.

PGE Group 2, Segment(s) 1, 3, 6, 5, 4/15/2022

- 0 - 0

Romel Aquino, Edison International - Southern California Edison Company, 3, 4/15/2022

- 0 - 0

Cowlitz PUD supports the comments submitted by Utility Services Inc.

Russell Noble, Cowlitz County PUD, 3, 4/15/2022

- 0 - 0

NST suggests dropping "electronic" from the phrase, "electronic vendor remote access." The only kind of remote access to electronic devices (including Cyber Assets) that presently exists is electronic. In addition, NST believes the remote access terms the SDT has used in CIP-003 Sections 6.1, 6.2 and elsewhere should be consistent with the language in CIP-005, which addresses "vendor remote access," not "electronic vendor remote access." Consistent use of terms enables Responsible Entities with assets other than low impact to develop and apply controls across assets of differing impact levels.

Roger Fradenburgh, On Behalf of: Nicholas Lauriat, Network and Security Technologies, 1

- 0 - 0

 PGE supports the survey response provided by EEI.

Daniel Mason, Portland General Electric Co., 6, 4/15/2022

- 0 - 0

Hot Answers

“Vendor communications” is a new term. It doesn’t scope this new term to communications “as established in Section 3” as the others do. “Vendor communications” is too broad of a term and wide open to many interpretations of the definition meaning.

Southern Company, Segment(s) 1, 3, 6, 5, 1/14/2021

- 0 - 0

Cowlitz PUD supports the comments submitted by Utility Services Inc.

Deanna Carlson, Cowlitz County PUD, 5, 4/15/2022

- 0 - 0

Other Answers

Comments: Remote access, as widely understood today with regards to the CIP standards, involves interactive electronic access across an Electronic Security Perimeter.  Low impact sites do not have an associated requirement for an Electronic Security Perimeter, so there is no reference point for what is considered a “remote location”. 

Patricia Lynch, NRG - NRG Energy, Inc., 5, 3/23/2022

- 0 - 0

Jay Sethi, On Behalf of: Manitoba Hydro - MRO - Segments 1, 3, 5, 6

- 0 - 0

Access from remote locations is not the same as remote access. A vendor could be physically on site and connect to the system through a remote connection.

Richard Jackson, On Behalf of: U.S. Bureau of Reclamation, , Segments 1, 5

- 0 - 0

Jennifer Malon, On Behalf of: Black Hills Corporation - MRO, WECC - Segments 1, 3, 5, 6

- 0 - 0

Tennessee Valley Authority, Segment(s) 1, 3, 5, 6, 10/18/2018

- 0 - 0

Joseph Amato, Berkshire Hathaway Energy - MidAmerican Energy Co., 3, 4/6/2022

- 0 - 0

Santee Cooper, Segment(s) 1, 3, 5, 6, 4/6/2022

- 0 - 0

Mike Marshall, 4/6/2022

- 0 - 0

Andrea Jessup, On Behalf of: Bonneville Power Administration, WECC, Segments 1, 3, 5, 6

- 0 - 0

Yes, the SDT has clarified the scope.

Ellese Murphy, On Behalf of: Duke Energy - MRO, WECC, Texas RE, SERC, RF - Segments 1, 3, 5, 6

- 0 - 0

Lan Nguyen, On Behalf of: CenterPoint Energy Houston Electric, LLC, Texas RE, Segments 1

- 0 - 0

No comment

Wes DeKemper, On Behalf of: Southern Indiana Gas and Electric Co., RF, Segments 3, 5, 6

- 0 - 0

Donald Lock, On Behalf of: Talen Generation, LLC, , Segments 5

- 0 - 0

JT Kuehne, AEP, 6, 4/8/2022

- 0 - 0

Scott Miller, 4/8/2022

- 0 - 0

Jeanne Kurzynowski, On Behalf of: CMS Energy - Consumers Energy Company, RF, Segments 1, 3, 5

- 0 - 0

Lindsey Mannion, ReliabilityFirst , 10, 4/11/2022

- 0 - 0

Dominion, Segment(s) 3, 5, 1, 9/19/2019

- 0 - 0

Steve Toosevich, NiSource - Northern Indiana Public Service Co., 1, 4/11/2022

- 0 - 0

WECC Entity Monitoring, Segment(s) 10, 1/30/2022

- 0 - 0

Michelle Amarantos, APS - Arizona Public Service Co., 5, 4/11/2022

- 0 - 0

Glen Farmer, Avista - Avista Corporation, 5, 4/11/2022

- 0 - 0

Jesus Sammy Alcaraz, Imperial Irrigation District, 1, 4/11/2022

- 0 - 0

Tim Kelley, On Behalf of: Nicole Looney, Sacramento Municipal Utility District, 1,3,4,5,6; Foung Mua, Sacramento Municipal Utility District, 1,3,4,5,6; Nicole Goi, Sacramento Municipal Utility District, 1,3,4,5,6; Kevin Smith, Balancing Authority of Northern California, 1; Charles Norton, Sacramento Municipal Utility District, 1,3,4,5,6

- 0 - 0

Lindsay Wickizer, Berkshire Hathaway - PacifiCorp, 6, 4/11/2022

- 0 - 0

Israel Perez, On Behalf of: Salt River Project - WECC - Segments 1, 3, 5, 6

- 0 - 0

Rachel Coyne, Texas Reliability Entity, Inc., 10, 4/12/2022

- 0 - 0

Susan Sosbe, Wabash Valley Power Association, 3, 4/12/2022

- 0 - 0

See EEI comment.

Clay Walker, On Behalf of: John Lindsey, Cleco Corporation, 1,3,5,6; Robert Hirchak, Cleco Corporation, 1,3,5,6; Maurice Paulk, Cleco Corporation, 1,3,5,6

- 0 - 0

Scott Kinney, Avista - Avista Corporation, 3, 4/12/2022

- 0 - 0

Jennifer Bray, Arizona Electric Power Cooperative, Inc., 1, 4/12/2022

- 0 - 0

Lynn Goldstein, PNM Resources - Public Service Company of New Mexico, 1, 4/12/2022

- 0 - 0

patricia ireland, DTE Energy, 4, 4/13/2022

- 0 - 0

Xcel Energy belives the scope is clear.

Joe Gatten, On Behalf of: Xcel Energy, Inc. - MRO, WECC - Segments 1, 3, 5, 6

- 0 - 0

Donna Wood, Tri-State G and T Association, Inc., 1, 4/13/2022

- 0 - 0

Larry Heckert, Alliant Energy Corporation Services, Inc., 4, 4/13/2022

- 0 - 0

LaTroy Brumfield, American Transmission Company, LLC, 1, 4/13/2022

- 0 - 0

Vendor remote access needs to be clear to convey remote access only

FE Voter, Segment(s) 1, 3, 5, 6, 4, 12/20/2021

- 0 - 0

Request clarification on mixed sites. This update does not address locations with a mixture of Low and Medium Impact because Medium controls are at the system level while Low controls are at the asset level.

Recommend including Low Impact BES Cyber Systems in the Requirement language to bound the sub-requirements. As written, the auditor may expand the scope to include assets that do not impact the BES.

Carl Pineault, On Behalf of: Hydro-Qu?bec Production, , Segments 1, 5

- 0 - 0

Evergy supports and incorporates the comments from the Edison Electric Institute (EEI) for questions #3.

- 0 - 0

BC Hydro suggests that the use of word "Remote" will need clarification and perhaps a definition in the Glossary of Terms. For example, in the scenarios below, how will the "Remote" term be used?

  1. On site, but electronically remote (i.e. has to go through EAP despite being at the station).
  2. A "vendor" at the work location of Responsible Entity, also electronically remote (i.e. going through EAP).
  3. "Traditionally" remote, off site, and electronically remote (also going through EAP).

BC Hydro, Segment(s) 3, 5, 1, 12/18/2018

- 0 - 0

David Jendras, Ameren - Ameren Services, 3, 4/14/2022

- 0 - 0

Gerry Adamski, On Behalf of: Cogentrix Energy Power Management, LLC, , Segments 5

- 0 - 0

 

The MRO NSRF believes that the language is properly scoped. 

MRO NSRF, Segment(s) 2, 3, 5, 1, 4, 6, 4/11/2022

- 0 - 0

Acciona Energy supports Midwest Reliability Organization’s (MRO) NERC Standards Review Forum’s (NSRF) comments on this question.

George Brown, Acciona Energy North America, 5, 4/14/2022

- 0 - 0

Mike Magruder, Avista - Avista Corporation, 1, 4/14/2022

- 0 - 0

No Comment

Brian Lindsey, Entergy, 1, 4/14/2022

- 0 - 0

Please see NEE’s response to question 1 respectfully submitting updated language  CIP-003 Attachment 1, Section 6 and Attachment 2, Section 6. 

Mike ONeil, 4/14/2022

- 0 - 0

Gail Elliott, On Behalf of: International Transmission Company Holdings Corporation - MRO, RF - Segments NA - Not Applicable

- 0 - 0

LCRA Compliance, Segment(s) 6, 5, 1, 5/11/2015

- 0 - 0

The NAGF membership is concerned with the “remote locations” language in this question. Remote location is not used to describe the vendor’s access in any version of the standard language. Is the SDT referencing geographic location or network topology? The standard language references inbound and outbound communications between the BES Cyber System and “Cyber Asset(s) outside the asset” (Section 3.1.i).

Wayne Sipperly, On Behalf of: North American Generator Forum, MRO, WECC, Texas RE, NPCC, SERC, RF, Segments 5

- 0 - 0

James Baldwin, Lower Colorado River Authority, 1, 4/15/2022

- 0 - 0

ACES Standard Collaborations, Segment(s) 1, 3, 5, 4, 4/15/2022

- 0 - 0

EEI agrees in part that the language in Attachment 1, Section 6 is clear but offers some suggested edits for SDT consideration.  (See our response to Question 1)

Mark Gray, On Behalf of: Edison Electric Institute, NA - Not Applicable, Segments NA - Not Applicable

- 0 - 0

Request clarification on mixed sites. This update does not address locations with a mixture of Low and Medium Impact because Medium controls are at the system level while Low controls are at the asset level.

Recommend including Low Impact BES Cyber Systems in the Requirement language to bound the sub-requirements. As written, the auditor may expand the scope to include assets that do not impact the BES.

NPCC Regional Standards Committee, Segment(s) 10, 2, 4, 7, 3, 1, 5, 6, 4/6/2022

- 0 - 0

Dwanique Spiller, Berkshire Hathaway - NV Energy, 5, 4/15/2022

- 0 - 0

No comment.

John Galloway, On Behalf of: Michael Puscas, ISO New England, Inc., 2

- 0 - 0

Benjamin Winslett, Georgia System Operations Corporation, 4, 4/15/2022

- 0 - 0

We disagree that the intent of the NERC Board resolution is to address vendor access to low impact assets. Our understanding of the NERC Board resolution is that the controls are to apply to low impact BES Cyber Systems at assets that have low impact BES Cyber Systems. The SDT’s interpretation could require the 3 controls to be applied to vendor remote access and communication to more than not just low impact BCS.

Brian Evans-Mongeon, Utility Services, Inc., 4, 4/15/2022

- 0 - 0

Request clarification on mixed sites. This update does not address locations with a mixture of Low and Medium Impact.

Devon Tremont, Taunton Municipal Lighting Plant, 1, 4/15/2022

- 0 - 0

Remote access, as widely understood today with regards to the CIP standards, involves interactive electronic access across an Electronic Security Perimeter.  Low impact sites do not have an associated requirement for an Electronic Security Perimeter, so there is no reference point for what is considered a “remote location”.  

Martin Sidor, NRG - NRG Energy, Inc., 6, 4/15/2022

- 0 - 0

Exelon ultimately believes this would require us to have an inventory list of the lows impact assets.

Daniel Gacek, Exelon, 1, 4/15/2022

- 0 - 0

Exelon believe that ultimately, this would require us to have an inventory list of the lows impact assets.

Kinte Whitehead, Exelon, 3, 4/15/2022

- 0 - 0

The new undefined term “vendor communications” needs additional explanation. Recommend adding text in bold for clarity. In sections 6.1-6.3 the SDT should consider using “active” electronic vendor remote access and in 6.3 add “…where such access has been established under section 3”

Kimberly Turco, Constellation, 6, 4/15/2022

- 0 - 0

The new undefined term “vendor communications” needs additional explanation. Recommend adding text in bold for clarity. In sections 6.1-6.3 the SDT should consider using “active” electronic vendor remote access and in 6.3 add “…where such access has been established under section 3”

Alison Mackellar, Constellation, 5, 4/15/2022

- 0 - 0

Minnesota Power is in agreement with Edison Electric Institute’s (EEI) comments.

Jamie Monette, Allete - Minnesota Power, Inc., 1, 4/15/2022

- 0 - 0

Florida Municipal Power Agency (FMPA), Segment(s) 5, 4, 3, 6, 4/15/2022

- 0 - 0

Selene Willis, Edison International - Southern California Edison Company, 5, 4/15/2022

- 0 - 0

 PGE supports the survey response provided by EEI.

PGE Group 2, Segment(s) 1, 3, 6, 5, 4/15/2022

- 0 - 0

Romel Aquino, Edison International - Southern California Edison Company, 3, 4/15/2022

- 0 - 0

Cowlitz PUD supports the comments submitted by Utility Services Inc.

Russell Noble, Cowlitz County PUD, 3, 4/15/2022

- 0 - 0

Although NST agrees Section 6 applies only to vendor remote access, it is our opinion that a malicious code detection requirement should not be limited to only vendor remote connections.

Roger Fradenburgh, On Behalf of: Nicholas Lauriat, Network and Security Technologies, 1

- 0 - 0

 PGE supports the survey response provided by EEI.

Daniel Mason, Portland General Electric Co., 6, 4/15/2022

- 0 - 0

Hot Answers

6.3 language needs to be clearer and have a tighter bounded scoping to avoid the widest possible interpretation at audit. You can’t go to Section 3 Electronic Access Controls evidence and show you are detecting things on all identified LERC and fully prove 6.3 as it is currently written. The intent of 6.3 should be added as a requirement to Section 3.

Southern Company, Segment(s) 1, 3, 6, 5, 1/14/2021

- 0 - 0

Cowlitz PUD supports the comments submitted by Utility Services Inc.

Deanna Carlson, Cowlitz County PUD, 5, 4/15/2022

- 0 - 0

Other Answers

Comments: The lack of specificity in the “access to low impact BES Cyber Systems” verbiage could imply that an Entity will be required to document all vendor remote access or system-to-system access to the asset.  This would include BES Cyber Systems, balance of plant for non-BCSs, and corporate business networks.  The language in Section 6 states, “assets containing low impact BES Cyber System(s)” which does not limit the scope to only the “low impact BES Cyber Systems”.  If the intent is to limit the scope to “low impact BES Cyber Systems” and not the “assets containing low impact BES Cyber Systems”, then significant changes would be warranted for CIP-002/CIP-003 to ensure low impact BES Cyber Systems are identified and that an Electronic Security Perimeter is established.  

Patricia Lynch, NRG - NRG Energy, Inc., 5, 3/23/2022

- 0 - 0

Jay Sethi, On Behalf of: Manitoba Hydro - MRO - Segments 1, 3, 5, 6

- 0 - 0

Richard Jackson, On Behalf of: U.S. Bureau of Reclamation, , Segments 1, 5

- 0 - 0

Jennifer Malon, On Behalf of: Black Hills Corporation - MRO, WECC - Segments 1, 3, 5, 6

- 0 - 0

Tennessee Valley Authority, Segment(s) 1, 3, 5, 6, 10/18/2018

- 0 - 0

Joseph Amato, Berkshire Hathaway Energy - MidAmerican Energy Co., 3, 4/6/2022

- 0 - 0

Santee Cooper, Segment(s) 1, 3, 5, 6, 4/6/2022

- 0 - 0

Mike Marshall, 4/6/2022

- 0 - 0

Andrea Jessup, On Behalf of: Bonneville Power Administration, WECC, Segments 1, 3, 5, 6

- 0 - 0

Yes, the SDT has made the scope clear.

Ellese Murphy, On Behalf of: Duke Energy - MRO, WECC, Texas RE, SERC, RF - Segments 1, 3, 5, 6

- 0 - 0

Lan Nguyen, On Behalf of: CenterPoint Energy Houston Electric, LLC, Texas RE, Segments 1

- 0 - 0

No comment

Wes DeKemper, On Behalf of: Southern Indiana Gas and Electric Co., RF, Segments 3, 5, 6

- 0 - 0

Donald Lock, On Behalf of: Talen Generation, LLC, , Segments 5

- 0 - 0

While AEP believes the proposed changes to the CIP-003 Standard are trending in the right direction overall, there was language struck through that we think adds clarity to the scope of the section. The aforementioned struck through language in Attachment 1 Section 6 is in bold below:

Section 6: Electronic Vendor Remote Access Security Controls: For assets containing low impact BES Cyber System(s) identified pursuant to CIP-002, the Responsible Entity shall implement a process to mitigate risks associated with electronic vendor remote access (including interactive and system-to-system access) to low impact BES Cyber Systems that includes:

To provide a more clear understanding that the language in this section limits scope to low impact BES Cyber Systems, AEP recommends reinstating the language above that was struck from this revision.

JT Kuehne, AEP, 6, 4/8/2022

- 0 - 0

Scott Miller, 4/8/2022

- 0 - 0

Jeanne Kurzynowski, On Behalf of: CMS Energy - Consumers Energy Company, RF, Segments 1, 3, 5

- 0 - 0

Lindsey Mannion, ReliabilityFirst , 10, 4/11/2022

- 0 - 0

There is confusion with the language used in Section 6 as to whether it pertains to the assets containing the low impact BES Cyber Systems (which may contain out of scope cyber systems) or the low impact BES Cyber Systems themselves.

Dominion, Segment(s) 3, 5, 1, 9/19/2019

- 0 - 0

Steve Toosevich, NiSource - Northern Indiana Public Service Co., 1, 4/11/2022

- 0 - 0

The inclusion of ‘where such access has been established under Section 3’ appears to bring into scope electronic vendor remote access to Cyber Assets that are not low impact BES Cyber Systems, but on the same network as a low impact BES Cyber System based on the language of Section 3.1 ii ‘using a routable protocol when entering or leaving the asset containing the low impact BES Cyber System(s).’ This is due to the fact that CIP-003 uses ‘asset containing’ as a boundary.

Please consider the following two options –

Option 1: Scope Section 6 specifically to Section 3.1 i, which would more accurately scope to only low impact BES Cyber Systems.

Section 3.1 i. between a low impact BES Cyber System(s) and a Cyber Asset(s) outside the asset containing low impact BES Cyber System(s);

Option 2: Do not reference Section 3 or any part thereof, but include the following language in Attachment 1 Section 6 –

‘between a low impact BES Cyber System(s) and a Cyber Asset(s) outside the asset containing low impact BES Cyber System(s).

6.1  One or more method(s) for determining electronic vendor remote access between a low impact BES Cyber System(s) and a Cyber Asset(s) outside

the asset containing low impact BES Cyber System(s);

6.2  One or more method(s) for disabling electronic vendor remote access between a low impact BES Cyber System(s) and a Cyber Asset(s) outside asset containing low impact BES Cyber System(s); and

6.3  One or more method(s) for detecting known or suspected malicious communications for both inbound and outbound vendor communications between a low impact BES Cyber System(s) and a Cyber Asset(s) outside the asset containing low impact BES Cyber System(s).

WECC Entity Monitoring, Segment(s) 10, 1/30/2022

- 0 - 0

Michelle Amarantos, APS - Arizona Public Service Co., 5, 4/11/2022

- 0 - 0

Glen Farmer, Avista - Avista Corporation, 5, 4/11/2022

- 0 - 0

Jesus Sammy Alcaraz, Imperial Irrigation District, 1, 4/11/2022

- 0 - 0

Tim Kelley, On Behalf of: Nicole Looney, Sacramento Municipal Utility District, 1,3,4,5,6; Foung Mua, Sacramento Municipal Utility District, 1,3,4,5,6; Nicole Goi, Sacramento Municipal Utility District, 1,3,4,5,6; Kevin Smith, Balancing Authority of Northern California, 1; Charles Norton, Sacramento Municipal Utility District, 1,3,4,5,6

- 0 - 0

Lindsay Wickizer, Berkshire Hathaway - PacifiCorp, 6, 4/11/2022

- 0 - 0

Israel Perez, On Behalf of: Salt River Project - WECC - Segments 1, 3, 5, 6

- 0 - 0

Rachel Coyne, Texas Reliability Entity, Inc., 10, 4/12/2022

- 0 - 0

Susan Sosbe, Wabash Valley Power Association, 3, 4/12/2022

- 0 - 0

See EEI comment.

Clay Walker, On Behalf of: John Lindsey, Cleco Corporation, 1,3,5,6; Robert Hirchak, Cleco Corporation, 1,3,5,6; Maurice Paulk, Cleco Corporation, 1,3,5,6

- 0 - 0

Scott Kinney, Avista - Avista Corporation, 3, 4/12/2022

- 0 - 0

Jennifer Bray, Arizona Electric Power Cooperative, Inc., 1, 4/12/2022

- 0 - 0

Lynn Goldstein, PNM Resources - Public Service Company of New Mexico, 1, 4/12/2022

- 0 - 0

patricia ireland, DTE Energy, 4, 4/13/2022

- 0 - 0

Xcel Energy believes additional clarity could be established by adding verbiage to 6.3 that includes "as established in section 3" 

Joe Gatten, On Behalf of: Xcel Energy, Inc. - MRO, WECC - Segments 1, 3, 5, 6

- 0 - 0

Section 6.3 should either reference Section 3.1 or somehow limit to only low impact BES cyber systems. 

Donna Wood, Tri-State G and T Association, Inc., 1, 4/13/2022

- 0 - 0

Larry Heckert, Alliant Energy Corporation Services, Inc., 4, 4/13/2022

- 0 - 0

LaTroy Brumfield, American Transmission Company, LLC, 1, 4/13/2022

- 0 - 0

FE Voter, Segment(s) 1, 3, 5, 6, 4, 12/20/2021

- 0 - 0

Request clarification on mixed sites. This update does not address locations with a mixture of Low and Medium Impact because Medium controls are at the system level while Low controls are at the asset level.

Recommend including Low Impact BES Cyber Systems in the Requirement language to bound the sub-requirements. As written, the auditor may expand the scope to include assets that do not impact the BES.

Carl Pineault, On Behalf of: Hydro-Qu?bec Production, , Segments 1, 5

- 0 - 0

Evergy supports and incorporates the comments from the Edison Electric Institute (EEI) for questions #4.

- 0 - 0

CIP-005-5 R1.5 does not apply to Medium impact BCS if they are not at Control Centers. Why and how the Requirement in Section 6.3 applies to 'Low Impact BCS' is not very clear from the language used. The Section 6.3 does offer possible mitigation of the risks i.e., 'malicious communication and vendor remote acces's however this is even more stringent on Low Impact BCS in comparison to CIP-005-5 R1.5. BC Hydro recommends rewording or removing Section 6.3 completely.

BC Hydro, Segment(s) 3, 5, 1, 12/18/2018

- 0 - 0

David Jendras, Ameren - Ameren Services, 3, 4/14/2022

- 0 - 0

Gerry Adamski, On Behalf of: Cogentrix Energy Power Management, LLC, , Segments 5

- 0 - 0

The MRO NSRF believes that the language is properly scoped.

MRO NSRF, Segment(s) 2, 3, 5, 1, 4, 6, 4/11/2022

- 0 - 0

Acciona Energy supports Midwest Reliability Organization’s (MRO) NERC Standards Review Forum’s (NSRF) comments on this question.

George Brown, Acciona Energy North America, 5, 4/14/2022

- 0 - 0

Mike Magruder, Avista - Avista Corporation, 1, 4/14/2022

- 0 - 0

Clarity is needed for when low impacts systems exist in conjunction with medium impact systems located at Medium BES Assets/Facilities. I.E. situations where there is a medium impact BES Asset/Facility that also contains low impact systems. 

Brian Lindsey, Entergy, 1, 4/14/2022

- 0 - 0

Please see NEE’s response to question 1 respectfully submitting updated language  CIP-003 Attachment 1, Section 6 and Attachment 2, Section 6. 

Mike ONeil, 4/14/2022

- 0 - 0

much more work is needed to sufficiently scope the low impact assets which will be considered in scope.

Gail Elliott, On Behalf of: International Transmission Company Holdings Corporation - MRO, RF - Segments NA - Not Applicable

- 0 - 0

LCRA believes that the current wording makes it clear that only low impact BCS is applicable. Additionally, it is unclear if controls have to be implemented at the asset level.

LCRA Compliance, Segment(s) 6, 5, 1, 5/11/2015

- 0 - 0

The NAGF has no comments.

Wayne Sipperly, On Behalf of: North American Generator Forum, MRO, WECC, Texas RE, NPCC, SERC, RF, Segments 5

- 0 - 0

LCRA believes that the current wording makes it unclear that only low impact BCS is applicable. Additionally, it is unclear if controls have to be implemented at the asset level.

James Baldwin, Lower Colorado River Authority, 1, 4/15/2022

- 0 - 0

ACES Standard Collaborations, Segment(s) 1, 3, 5, 4, 4/15/2022

- 0 - 0

EEI disagrees that the language in Attachment 1, Section 6 clearly limits the scope to low impact BES cyber systems.  While we agree with the changes made to Section 6, subparts 6.1 and 6.2; the proposed language in subpart 6.3 is not sufficiently narrow.  (See our response to question 1 above.)

Mark Gray, On Behalf of: Edison Electric Institute, NA - Not Applicable, Segments NA - Not Applicable

- 0 - 0

Request clarification on mixed sites. This update does not address locations with a mixture of Low and Medium Impact because Medium controls are at the system level while Low controls are at the asset level.

Recommend including Low Impact BES Cyber Systems in the Requirement language to bound the sub-requirements. As written, the auditor may expand the scope to include assets that do not impact the BES.

NPCC Regional Standards Committee, Segment(s) 10, 2, 4, 7, 3, 1, 5, 6, 4/6/2022

- 0 - 0

Dwanique Spiller, Berkshire Hathaway - NV Energy, 5, 4/15/2022

- 0 - 0

No comment.

John Galloway, On Behalf of: Michael Puscas, ISO New England, Inc., 2

- 0 - 0

Benjamin Winslett, Georgia System Operations Corporation, 4, 4/15/2022

- 0 - 0

The proposed language in Section 6.3 could be interpreted to include communication to people and all Cyber Assets at an asset that contains low impact BCS. The controls for active vendor remote access could also be required to be applied to all Cyber Assets at the asset and not just those that are part of a low impact BCS.

 

We would suggest appending a statement consistent with the other two subsections of Section 6, “where such access has been established under Section 3.”

Brian Evans-Mongeon, Utility Services, Inc., 4, 4/15/2022

- 0 - 0

Request clarification on mixed sites. This update does not address locations with a mixture of Low and Medium Impact.

Devon Tremont, Taunton Municipal Lighting Plant, 1, 4/15/2022

- 0 - 0

The lack of specificity in the “access to low impact BES Cyber Systems” verbiage could imply that an Entity will be required to document all vendor remote access or system-to-system access to the asset.  This would include BES Cyber Systems, balance of plant for non-BCSs, and corporate business networks.  The language in Section 6 states, “assets containing low impact BES Cyber System(s)” which does not limit the scope to only the “low impact BES Cyber Systems”.  If the intent is to limit the scope to “low impact BES Cyber Systems” and not the “assets containing low impact BES Cyber Systems”, then significant changes would be warranted for CIP-002/CIP-003 to ensure low impact BES Cyber Systems are identified and that an Electronic Security Perimeter is established.  

Martin Sidor, NRG - NRG Energy, Inc., 6, 4/15/2022

- 0 - 0

Exelons interpretation of the proposed standard views that this opens up access to ‘any’ areas that has a low

Daniel Gacek, Exelon, 1, 4/15/2022

- 0 - 0

Exelons interpretation of the proposed standard views that this opens up access to ‘any’ areas that contain lows.

Kinte Whitehead, Exelon, 3, 4/15/2022

- 0 - 0

Constellation has elected to align with Exelon in response to this question. 

Exelons interpretation of the proposed standard views that this opens up access to ‘any’ areas that has a low.

Kimberly Turco, Constellation, 6, 4/15/2022

- 0 - 0

Constellation has elected to align with Exelon in response to this question. 

Exelons interpretation of the proposed standard views that this opens up access to ‘any’ areas that has a low.

Alison Mackellar, Constellation, 5, 4/15/2022

- 0 - 0

No additional comments

Jamie Monette, Allete - Minnesota Power, Inc., 1, 4/15/2022

- 0 - 0

Florida Municipal Power Agency (FMPA), Segment(s) 5, 4, 3, 6, 4/15/2022

- 0 - 0

Selene Willis, Edison International - Southern California Edison Company, 5, 4/15/2022

- 0 - 0

 PGE supports the survey response provided by EEI.

PGE Group 2, Segment(s) 1, 3, 6, 5, 4/15/2022

- 0 - 0

Romel Aquino, Edison International - Southern California Edison Company, 3, 4/15/2022

- 0 - 0

Cowlitz PUD supports the comments submitted by Utility Services Inc.

Russell Noble, Cowlitz County PUD, 3, 4/15/2022

- 0 - 0

While NST agrees the Section 6 language limits the scope to low impact BCS, it is our opinion that it does not adequately define the types of in-scope vendor remote access. Do Sections 6.1 through 6.3 apply to vendor remote access via dial-up? Rather than simply use a blanket referral to Section 3 in Sections 6.1 and 6.2, Section 6 should refer to specific sub-parts of Section 3 (e.g., Section 3.1, Part i).

Roger Fradenburgh, On Behalf of: Nicholas Lauriat, Network and Security Technologies, 1

- 0 - 0

 PGE supports the survey response provided by EEI.

Daniel Mason, Portland General Electric Co., 6, 4/15/2022

- 0 - 0

Hot Answers

Southern Company, Segment(s) 1, 3, 6, 5, 1/14/2021

- 0 - 0

Cowlitz PUD supports the comments submitted by Utility Services Inc.

Deanna Carlson, Cowlitz County PUD, 5, 4/15/2022

- 0 - 0

Other Answers

Comments: Most of the suggested methods of achieving compliance go beyond the current requirements for low impact sites.  Also, most of these methods require uniquely identified systems or assets, which is currently not required for low impact sites.  If the intent of these proposed methods is to create a set of requirements similar to those for Medium Impact BES Cyber Systems, then the recommendation would be to eliminate CIP-003, R2 and incorporate low impact sites throughout the rest of the CIP standards, as appropriate, under the applicable systems column(s). 

Patricia Lynch, NRG - NRG Energy, Inc., 5, 3/23/2022

- 0 - 0

The examples provided support what is required in Attachment 1 Section 6. Clarification in the language used is suggested, along with an additional example for vendor machine to machine remote access:

 

Electronic Vendor Remote Access Security Controls: Examples of evidence showing the implementation of the process for Section 6 may include, but are not limited to:

1. For Section 6.1, documentation AND EVIDENCE OF IMPLEMENTATION showing:

ï‚· DOCUMENTED steps to preauthorize access ALONG WITH AUTHORIZATION RECORDS

ï‚· CONFIGURATION OF alerts generated by vendor log on;

ï‚· PROCEDURES FOR THE USE OF VENDOR session monitoring AND SESSION MONITORING LOGS;

ï‚· Security Information Management logging alerts; - REDUNDANT TO #1, CAN BE REMOVED

ï‚· DOCUMENTED STEPS AND LOGS FOR time-of-need session initiation;

ï‚· DOCUMENTED STEPS AND LOGS FOR VENDOR REMOTE ACCESS session recording;

ï‚· DOCUMENTATION AND CONFIGURATION OF system logs SHOWING VENDOR REMOTE ACCESS CONNECTIONS 

ï‚· DOCUMENTATION OF ELECTRONIC ACCESS CONTROL RULES PERMITTING INBOUND VENDOR MACHINE TO MACHINE COMMUNICATION; or

ï‚· other operational, procedural, or technical controls.

For Section 6.2, documentation showing THE PROCESS FOR:

ï‚· disabling vendor remote access user or system accounts;

ï‚· disabling inbound and/or outbound hardware or software ports, services, or access permissions on applications, firewall, IDS/IPS, router, switch, VPN, Remote Desktop, remote control, or other hardware or software used for providing active vendor remote access;

ï‚· disabling communications protocols (such as IP) used for systems which establish and/or maintain active vendor remote access;

ï‚· Removing physical layer connectivity (e.g., disconnect an Ethernet cable, power down equipment);

ï‚· administrative control documentation listing the methods, steps, or systems used to disable active vendor remote access; or

ï‚· other operational, procedural, or technical controls.

For Section 6.3, documentation showing implementation of:

ï‚· Firewall policies IMPLEMENTING MALICIOUS TRAFFIC INSPECTION;

ï‚· Intrusion Detection System (IDS)/Intrusion Prevention System (IPS);

ï‚· Virtual Private Network (VPN) hosts IMPLEMENTING CONNECTION INSPECTION;

ï‚· manual log reviews; or

ï‚· other operational, procedural, or technical controls.

Jay Sethi, On Behalf of: Manitoba Hydro - MRO - Segments 1, 3, 5, 6

- 0 - 0

Richard Jackson, On Behalf of: U.S. Bureau of Reclamation, , Segments 1, 5

- 0 - 0

Jennifer Malon, On Behalf of: Black Hills Corporation - MRO, WECC - Segments 1, 3, 5, 6

- 0 - 0

Tennessee Valley Authority, Segment(s) 1, 3, 5, 6, 10/18/2018

- 0 - 0

Joseph Amato, Berkshire Hathaway Energy - MidAmerican Energy Co., 3, 4/6/2022

- 0 - 0

Santee Cooper, Segment(s) 1, 3, 5, 6, 4/6/2022

- 0 - 0

Mike Marshall, 4/6/2022

- 0 - 0

Andrea Jessup, On Behalf of: Bonneville Power Administration, WECC, Segments 1, 3, 5, 6

- 0 - 0

Yes, the examples support our understanding of what is required.

Ellese Murphy, On Behalf of: Duke Energy - MRO, WECC, Texas RE, SERC, RF - Segments 1, 3, 5, 6

- 0 - 0

Lan Nguyen, On Behalf of: CenterPoint Energy Houston Electric, LLC, Texas RE, Segments 1

- 0 - 0

No comment

Wes DeKemper, On Behalf of: Southern Indiana Gas and Electric Co., RF, Segments 3, 5, 6

- 0 - 0

Donald Lock, On Behalf of: Talen Generation, LLC, , Segments 5

- 0 - 0

JT Kuehne, AEP, 6, 4/8/2022

- 0 - 0

Scott Miller, 4/8/2022

- 0 - 0

Jeanne Kurzynowski, On Behalf of: CMS Energy - Consumers Energy Company, RF, Segments 1, 3, 5

- 0 - 0

Lindsey Mannion, ReliabilityFirst , 10, 4/11/2022

- 0 - 0

Dominion, Segment(s) 3, 5, 1, 9/19/2019

- 0 - 0

Steve Toosevich, NiSource - Northern Indiana Public Service Co., 1, 4/11/2022

- 0 - 0

Attachment 2 Section 6 includes multiple uses of ‘vendor remote access’ and ‘active vendor remote access.’ To ensure a consistant scope to Section 6 consider changing all to ‘electronic vendor remote access.’

disabling vendor remote access user or system accounts

disabling inbound and/or outbound hardware or software ports, services, or access permissions on applications, firewall, IDS/IPS, router, switch, VPN,Remote Desktop, remote control, or other hardware or software used for providing active vendor remote access

disabling communications protocols (such as IP) used for systems which establish and/or maintain active vendor remote access;

administrative control documentation listing the methods, steps, or systems used to disable active vendor remote access;

 

 

WECC Entity Monitoring, Segment(s) 10, 1/30/2022

- 0 - 0

Michelle Amarantos, APS - Arizona Public Service Co., 5, 4/11/2022

- 0 - 0

Glen Farmer, Avista - Avista Corporation, 5, 4/11/2022

- 0 - 0

Not clear if VPN connections established with support vendors fully adheres to requirement or additional steps are required such as an IDS/IPS.

Jesus Sammy Alcaraz, Imperial Irrigation District, 1, 4/11/2022

- 0 - 0

Tim Kelley, On Behalf of: Nicole Looney, Sacramento Municipal Utility District, 1,3,4,5,6; Foung Mua, Sacramento Municipal Utility District, 1,3,4,5,6; Nicole Goi, Sacramento Municipal Utility District, 1,3,4,5,6; Kevin Smith, Balancing Authority of Northern California, 1; Charles Norton, Sacramento Municipal Utility District, 1,3,4,5,6

- 0 - 0

Lindsay Wickizer, Berkshire Hathaway - PacifiCorp, 6, 4/11/2022

- 0 - 0

Israel Perez, On Behalf of: Salt River Project - WECC - Segments 1, 3, 5, 6

- 0 - 0

Rachel Coyne, Texas Reliability Entity, Inc., 10, 4/12/2022

- 0 - 0

Susan Sosbe, Wabash Valley Power Association, 3, 4/12/2022

- 0 - 0

See EEI comment.

Clay Walker, On Behalf of: John Lindsey, Cleco Corporation, 1,3,5,6; Robert Hirchak, Cleco Corporation, 1,3,5,6; Maurice Paulk, Cleco Corporation, 1,3,5,6

- 0 - 0

Scott Kinney, Avista - Avista Corporation, 3, 4/12/2022

- 0 - 0

Jennifer Bray, Arizona Electric Power Cooperative, Inc., 1, 4/12/2022

- 0 - 0

Lynn Goldstein, PNM Resources - Public Service Company of New Mexico, 1, 4/12/2022

- 0 - 0

patricia ireland, DTE Energy, 4, 4/13/2022

- 0 - 0

Xcel Energy believes that examples in Attachment 2 provide clarity to what is required in demonstrating compliance with Section 6.  

Joe Gatten, On Behalf of: Xcel Energy, Inc. - MRO, WECC - Segments 1, 3, 5, 6

- 0 - 0

Tri-State mostly agrees however, the example of Steps to Preauthorize is confusing and too open-ended. 

Donna Wood, Tri-State G and T Association, Inc., 1, 4/13/2022

- 0 - 0

Larry Heckert, Alliant Energy Corporation Services, Inc., 4, 4/13/2022

- 0 - 0

LaTroy Brumfield, American Transmission Company, LLC, 1, 4/13/2022

- 0 - 0

FE Voter, Segment(s) 1, 3, 5, 6, 4, 12/20/2021

- 0 - 0

Agree in principle with these examples

Request the Measures (Attachment 2) use language consistent with the Requirements (Attachment 1). Attachment 2, 6.2 includes a bullet – “administrative control documentation listing the methods, steps, or systems used to disable active vendor remote access.” Attachment 1, Section 6 does not say “active vendor remote access.” Next that bullet is inconsistent with the first Attachment, 6.2 bullet – “disabling vendor remote access user or system accounts.”

 

Request consistency or clarification between CIP-003 and CIP-005. CIP-003 Attachment 1, Section 6 and Attachment 2, Section 6 use different language than the proposed CIP-005, Part 2.5 Requirement – “Have one or more method(s) to disable active vendor remote access (including IRA and system-to-system remote access).”

Carl Pineault, On Behalf of: Hydro-Qu?bec Production, , Segments 1, 5

- 0 - 0

Evergy supports and incorporates the comments from the Edison Electric Institute (EEI) for questions #5.

- 0 - 0

BC Hydro, Segment(s) 3, 5, 1, 12/18/2018

- 0 - 0

David Jendras, Ameren - Ameren Services, 3, 4/14/2022

- 0 - 0

Agree in principle with these examples

Request the Measures (Attachment 2) use language consistent with the Requirements (Attachment 1). Attachment 2, 6.2 includes a bullet – “administrative control documentation listing the methods, steps, or systems used to disable active vendor remote access.” Attachment 1, Section 6 does not say “active vendor remote access.” Next that bullet is inconsistent with the first Attachment, 6.2 bullet – “disabling vendor remote access user or system accounts.”

Gerry Adamski, On Behalf of: Cogentrix Energy Power Management, LLC, , Segments 5

- 0 - 0

The MRO NSRF believes that the example are clear. 

MRO NSRF, Segment(s) 2, 3, 5, 1, 4, 6, 4/11/2022

- 0 - 0

Acciona Energy supports Midwest Reliability Organization’s (MRO) NERC Standards Review Forum’s (NSRF) comments on this question.

George Brown, Acciona Energy North America, 5, 4/14/2022

- 0 - 0

Mike Magruder, Avista - Avista Corporation, 1, 4/14/2022

- 0 - 0

Additional ephasis should be put on Programmatic non technical methods of allowance to clarify that processes can be leverage rather than purely technical methods. 

Brian Lindsey, Entergy, 1, 4/14/2022

- 0 - 0

Mike ONeil, 4/14/2022

- 0 - 0

Gail Elliott, On Behalf of: International Transmission Company Holdings Corporation - MRO, RF - Segments NA - Not Applicable

- 0 - 0

LCRA Compliance, Segment(s) 6, 5, 1, 5/11/2015

- 0 - 0

The NAGF has no comments.

Wayne Sipperly, On Behalf of: North American Generator Forum, MRO, WECC, Texas RE, NPCC, SERC, RF, Segments 5

- 0 - 0

James Baldwin, Lower Colorado River Authority, 1, 4/15/2022

- 0 - 0

ACES Standard Collaborations, Segment(s) 1, 3, 5, 4, 4/15/2022

- 0 - 0

EEI agrees that Attachment 2, Section 6 examples support what is required under Attachment 1, Section 6.

Mark Gray, On Behalf of: Edison Electric Institute, NA - Not Applicable, Segments NA - Not Applicable

- 0 - 0

Agree in principle with these examples

Request the Measures (Attachment 2) use language consistent with the Requirements (Attachment 1). Attachment 2, 6.2 includes a bullet – “administrative control documentation listing the methods, steps, or systems used to disable active vendor remote access.” Attachment 1, Section 6 does not say “active vendor remote access.” Next, that bullet is inconsistent with the first Attachment, 6.2 bullet – “disabling vendor remote access user or system accounts.”

 

Request consistency or clarification between CIP-003 and CIP-005. CIP-003 Attachment 1, Section 6 and Attachment 2, Section 6 use different language than the proposed CIP-005, Part 2.5 Requirement – “Have one or more method(s) to disable active vendor remote access (including IRA and system-to-system remote access).”

NPCC Regional Standards Committee, Segment(s) 10, 2, 4, 7, 3, 1, 5, 6, 4/6/2022

- 0 - 0

Dwanique Spiller, Berkshire Hathaway - NV Energy, 5, 4/15/2022

- 0 - 0

No comment.

John Galloway, On Behalf of: Michael Puscas, ISO New England, Inc., 2

- 0 - 0

GSOC recommends that the language in Section 6.1 be revised to more closely mirror the language of CIP-005-7, R2.4, which would more clearly indicate the time frame and intent/activities to which the requirement and documentation should be focused.

Benjamin Winslett, Georgia System Operations Corporation, 4, 4/15/2022

- 0 - 0

The examples listed for Section 6.2 include controls for disabling and controls for terminating remote access. In addition, these examples use the terms “vendor remote access” and “active vendor remote access” but do not use the “electronic vendor remote access” term used in Attachment 1. While we do not think the term “electronic vendor remote access” should be used at all, there should be consistency throughout the document and preferably, consistency throughout the CIP Standards.

Brian Evans-Mongeon, Utility Services, Inc., 4, 4/15/2022

- 0 - 0

Request the Measures (Attachment 2) use language consistent with the Requirements (Attachment 1). Attachment 2, 6.2 includes a bullet – “administrative control documentation listing the methods, steps, or systems used to disable active vendor remote access.” Attachment 1, Section 6 does not say “active vendor remote access.” Next that bullet is inconsistent with the first Attachment, 6.2 bullet – “disabling vendor remote access user or system accounts.”

Devon Tremont, Taunton Municipal Lighting Plant, 1, 4/15/2022

- 0 - 0

Most of the suggested methods of achieving compliance go beyond the current requirements for low impact sites.  Also, most of these methods require uniquely identified systems or assets, which is currently not required for low impact sites.  If the intent of these proposed methods is to create a set of requirements similar to those for Medium Impact BES Cyber Systems, then the recommendation would be to eliminate CIP-003, R2 and incorporate low impact sites throughout the rest of the CIP standards, as appropriate, under the applicable systems column(s).  

Martin Sidor, NRG - NRG Energy, Inc., 6, 4/15/2022

- 0 - 0

Firewall Policy and Virtual Private Networks aren’t the greatest examples of capturing whats in Attachment 1.

Daniel Gacek, Exelon, 1, 4/15/2022

- 0 - 0

Firewall Policy and Virtual Private Networks aren’t the greatest examples of capturing whats in Attachment 1.

Kinte Whitehead, Exelon, 3, 4/15/2022

- 0 - 0

Constellation has elected to align with Exelon in response to this question.

Firewall Policy and Virtual Private Networks aren’t the greatest examples of capturing whats in Attachment 1.

Kimberly Turco, Constellation, 6, 4/15/2022

- 0 - 0

Constellation has elected to align with Exelon in response to this question.

Firewall Policy and Virtual Private Networks aren’t the greatest examples of capturing whats in Attachment 1.

Alison Mackellar, Constellation, 5, 4/15/2022

- 0 - 0

No additional comments

Jamie Monette, Allete - Minnesota Power, Inc., 1, 4/15/2022

- 0 - 0

Florida Municipal Power Agency (FMPA), Segment(s) 5, 4, 3, 6, 4/15/2022

- 0 - 0

Selene Willis, Edison International - Southern California Edison Company, 5, 4/15/2022

- 0 - 0

 PGE supports the survey response provided by EEI.

PGE Group 2, Segment(s) 1, 3, 6, 5, 4/15/2022

- 0 - 0

Romel Aquino, Edison International - Southern California Edison Company, 3, 4/15/2022

- 0 - 0

Russell Noble, Cowlitz County PUD, 3, 4/15/2022

- 0 - 0

NST has no comment.

Roger Fradenburgh, On Behalf of: Nicholas Lauriat, Network and Security Technologies, 1

- 0 - 0

 PGE supports the survey response provided by EEI.

Daniel Mason, Portland General Electric Co., 6, 4/15/2022

- 0 - 0

Hot Answers

Southern Company, Segment(s) 1, 3, 6, 5, 1/14/2021

- 0 - 0

Deanna Carlson, Cowlitz County PUD, 5, 4/15/2022

- 0 - 0

Other Answers

Comments: These modifications, as they are currently written, could be misinterpreted, which would result in a significant expansion of scope of the CIP-003 Attachment 1 requirements and prove detrimental to a cost-efffective approach.  Please reference previously provided comments for additional detail.

Patricia Lynch, NRG - NRG Energy, Inc., 5, 3/23/2022

- 0 - 0

Jay Sethi, On Behalf of: Manitoba Hydro - MRO - Segments 1, 3, 5, 6

- 0 - 0

Reclamation identifies that it is not cost effective to have separate standards for low impact and medium impact BES Cyber Systems, especially when the language of the requirements for each impact level is identical. Reclamation observes that Project 2016-02 will bring many changes to a majority of the CIP standards; therefore, Reclamation recommends this project may be a good avenue to incorporate low impact requirements into these standards to avoid the continuous churn of CIP-003 Attachment 1 when ultimately the requirements for low impact BES Cyber Systems will end up being identical to those for medium impact BCS.

Richard Jackson, On Behalf of: U.S. Bureau of Reclamation, , Segments 1, 5

- 0 - 0

Jennifer Malon, On Behalf of: Black Hills Corporation - MRO, WECC - Segments 1, 3, 5, 6

- 0 - 0

Tennessee Valley Authority, Segment(s) 1, 3, 5, 6, 10/18/2018

- 0 - 0

Due to supply chain issues and other geopolitical factors, it is difficult to determine the cost effectiveness of implementing this standard. 

Joseph Amato, Berkshire Hathaway Energy - MidAmerican Energy Co., 3, 4/6/2022

- 0 - 0

Santee Cooper, Segment(s) 1, 3, 5, 6, 4/6/2022

- 0 - 0

Mike Marshall, 4/6/2022

- 0 - 0

Andrea Jessup, On Behalf of: Bonneville Power Administration, WECC, Segments 1, 3, 5, 6

- 0 - 0

A longer implementation timeline would offer more cost effectiveness. This would allow industry to spread their investments and capital purchases.

Ellese Murphy, On Behalf of: Duke Energy - MRO, WECC, Texas RE, SERC, RF - Segments 1, 3, 5, 6

- 0 - 0

Lan Nguyen, On Behalf of: CenterPoint Energy Houston Electric, LLC, Texas RE, Segments 1

- 0 - 0

SIGE will not provide a response to the cost effectiveness of the proposed changes to CIP-003-x.

Wes DeKemper, On Behalf of: Southern Indiana Gas and Electric Co., RF, Segments 3, 5, 6

- 0 - 0

Donald Lock, On Behalf of: Talen Generation, LLC, , Segments 5

- 0 - 0

JT Kuehne, AEP, 6, 4/8/2022

- 0 - 0

Scott Miller, 4/8/2022

- 0 - 0

Jeanne Kurzynowski, On Behalf of: CMS Energy - Consumers Energy Company, RF, Segments 1, 3, 5

- 0 - 0

Lindsey Mannion, ReliabilityFirst , 10, 4/11/2022

- 0 - 0

The scope should be narrowed to just where the risk exists as opposed to a broad swath of assets. The way it is written it implies that all communications need to be monitored to determine malicious communications through vendor remote access.

Dominion, Segment(s) 3, 5, 1, 9/19/2019

- 0 - 0

Depending on the solution(s) determined by NIPSCO, cost would most likely be a factor to purchase the equipment and resources necessary to achieve the goal of securing vendor remote access. 

Steve Toosevich, NiSource - Northern Indiana Public Service Co., 1, 4/11/2022

- 0 - 0

WECC Entity Monitoring, Segment(s) 10, 1/30/2022

- 0 - 0

Michelle Amarantos, APS - Arizona Public Service Co., 5, 4/11/2022

- 0 - 0

The changes limit the scope of what traffic must be monitored, but the technology and resources needed to conduct the monitoring remains the same.

Glen Farmer, Avista - Avista Corporation, 5, 4/11/2022

- 0 - 0

Jesus Sammy Alcaraz, Imperial Irrigation District, 1, 4/11/2022

- 0 - 0

Tim Kelley, On Behalf of: Nicole Looney, Sacramento Municipal Utility District, 1,3,4,5,6; Foung Mua, Sacramento Municipal Utility District, 1,3,4,5,6; Nicole Goi, Sacramento Municipal Utility District, 1,3,4,5,6; Kevin Smith, Balancing Authority of Northern California, 1; Charles Norton, Sacramento Municipal Utility District, 1,3,4,5,6

- 0 - 0

Due to supply chain issues and other geopolitical factors, it is difficult to determine the cost effectiveness of implementing this standard. 

Lindsay Wickizer, Berkshire Hathaway - PacifiCorp, 6, 4/11/2022

- 0 - 0

Israel Perez, On Behalf of: Salt River Project - WECC - Segments 1, 3, 5, 6

- 0 - 0

Texas RE does not have comments on the question.

Rachel Coyne, Texas Reliability Entity, Inc., 10, 4/12/2022

- 0 - 0

This is very dependent on how an entity chose to implement it’s low impact electronic access controls, the size of the organization, and if the organization has medium or high impact Control Centers. 

Susan Sosbe, Wabash Valley Power Association, 3, 4/12/2022

- 0 - 0

Clay Walker, On Behalf of: John Lindsey, Cleco Corporation, 1,3,5,6; Robert Hirchak, Cleco Corporation, 1,3,5,6; Maurice Paulk, Cleco Corporation, 1,3,5,6

- 0 - 0

The changes limit the scope of what traffic must be monitored, but the technology and resources needed to conduct the monitoring remains the same.

Scott Kinney, Avista - Avista Corporation, 3, 4/12/2022

- 0 - 0

AEPCO is signing on to ACES comments below.

ACES comments:  This is very dependent on how an entity chose to implement it’s low impact electronic access controls, the size of the organization, and if the organization has medium or high impact Control Centers. 

Jennifer Bray, Arizona Electric Power Cooperative, Inc., 1, 4/12/2022

- 0 - 0

Lynn Goldstein, PNM Resources - Public Service Company of New Mexico, 1, 4/12/2022

- 0 - 0

We will need more information to adequately assess the cost-effectiveness of the proposed approach

patricia ireland, DTE Energy, 4, 4/13/2022

- 0 - 0

Xcel Energy is concerned with meeting the demands of section 6 in a cost effective manner at this time. World events have created issues with supply chain and receiving the needed products to perform activities required in the standard in a timely and cost effective manner. The vast number of low impact sites as compared to high and medium sites will cause a sudden surge in demand and cause prices to rise dramatically. The standard drafting team should take these issues into consideration in their implementation plan to spread costs and demand for products across and longer span of time. 

Joe Gatten, On Behalf of: Xcel Energy, Inc. - MRO, WECC - Segments 1, 3, 5, 6

- 0 - 0

There are many entities that have a large amount of low impact sites that are in remote locations and struggle with limited bandwith that will be impacted.   With the recent supply chain and staffing issues you will have higher than normal costs to implement these requirements.  

Donna Wood, Tri-State G and T Association, Inc., 1, 4/13/2022

- 0 - 0

Alliant Energy supports the comments submitted by the MRO NSRF.

Larry Heckert, Alliant Energy Corporation Services, Inc., 4, 4/13/2022

- 0 - 0

LaTroy Brumfield, American Transmission Company, LLC, 1, 4/13/2022

- 0 - 0

To be “cost effective”, this implies the proposed modification to the CIP-003 standard can be absorbed with existing company staff and minor procedure adjustment.  Based on the high volume of Low Impact Cyber System locations and varied configurations that we have in our service territory (approximately 10 times the level of CIP Medium Impact locations), this is not a cost-effective change.  Additional staff and procedures will be required to monitor this level of detail to meet the requirements of CIP-003.

FE Voter, Segment(s) 1, 3, 5, 6, 4, 12/20/2021

2020-03_Supply_Chain_Lows_Unofficial_Comment_Form_02252022 Presentation FINAL COMMENTS v2.docx

- 0 - 0

No comment

Carl Pineault, On Behalf of: Hydro-Qu?bec Production, , Segments 1, 5

- 0 - 0

Making this a requirement on all low impact BES Cyber Systems would be extremely expensive because new equipment must be installed at each low location to monitor for remote vendor access, allow for the ability to terminate sessions and detect malicious code.  It would be more cost effective to create a risk-based approach that would target those low impact BES Cyber Systems that could have the most potential impact on the BES.  

- 0 - 0

Although the cost may differ between entities, BC Hydro's assessment is that the impact may change based on understanding & clarity of terms and scope of application. As outlined in BC Hydro's comments to Question 1 above, CIP-005-5 R1.5 does not apply to Medium impact BCS if they are not at Control Centers. However, the requirement in CIP-003-X Section 6.3 applies to 'Low Impact BCS' which is even more stringent on Low Impact BCS in comparison to CIP-005-5 R1.5, where only High and Medium Impact BCS at Control Centers are in scope leaving all the other Medium impact BCS out of scope.

Implementing this requirement and adding detection methods for known or suspected malicious communications for both inbound and outbound communications concerning Low impact BCS will likely have significant cost impact.

BC Hydro, Segment(s) 3, 5, 1, 12/18/2018

- 0 - 0

David Jendras, Ameren - Ameren Services, 3, 4/14/2022

- 0 - 0

Gerry Adamski, On Behalf of: Cogentrix Energy Power Management, LLC, , Segments 5

- 0 - 0

The MRO NSRF has concerns about the potential of ineffective costs. Due to recent supply chain issues, industry-wide staffing shortages, and other geopolitical factors the cost of implementation of the Requirements is at a much higher risk than what would normally be expected. Higher than expected costs may result in the need for a longer or adaptive implementation timeline. 

MRO NSRF, Segment(s) 2, 3, 5, 1, 4, 6, 4/11/2022

- 0 - 0

Acciona Energy supports Midwest Reliability Organization’s (MRO) NERC Standards Review Forum’s (NSRF) comments on this question.

George Brown, Acciona Energy North America, 5, 4/14/2022

- 0 - 0

The changes limit the scope of what traffic must be monitored, but the technology and resources needed to conduct the monitoring remains the same.

Mike Magruder, Avista - Avista Corporation, 1, 4/14/2022

- 0 - 0

Brian Lindsey, Entergy, 1, 4/14/2022

- 0 - 0

Mike ONeil, 4/14/2022

- 0 - 0

Any low impact related changes are likely to lead to significant scope creep and potentially many underlying, unknown costs that will be incurred.

Gail Elliott, On Behalf of: International Transmission Company Holdings Corporation - MRO, RF - Segments NA - Not Applicable

- 0 - 0

There is a high likelihood that new technology controls will be required to effectively meet the intent of these new requirements. This could pose fiscal challenges to entities.

LCRA Compliance, Segment(s) 6, 5, 1, 5/11/2015

- 0 - 0

GO/GOPs will need more information to adequately assess the cost-effectiveness of the proposed approach.

Wayne Sipperly, On Behalf of: North American Generator Forum, MRO, WECC, Texas RE, NPCC, SERC, RF, Segments 5

- 0 - 0

There is a high likelihood that new technology controls will be required to effectively meet the intent of these new requirements. This could pose fiscal challenges to entities.

James Baldwin, Lower Colorado River Authority, 1, 4/15/2022

- 0 - 0

This is very dependent on how an entity chose to implement it’s low impact electronic access controls, the size of the organization, and if the organization has medium or high impact Control Centers.  

ACES Standard Collaborations, Segment(s) 1, 3, 5, 4, 4/15/2022

- 0 - 0

Mark Gray, On Behalf of: Edison Electric Institute, NA - Not Applicable, Segments NA - Not Applicable

- 0 - 0

NPCC Regional Standards Committee, Segment(s) 10, 2, 4, 7, 3, 1, 5, 6, 4/6/2022

- 0 - 0

Due to supply chain issues and other geopolitical factors, it is difficult to determine the cost effectiveness of implementing this standard. 

Dwanique Spiller, Berkshire Hathaway - NV Energy, 5, 4/15/2022

- 0 - 0

No comment.

John Galloway, On Behalf of: Michael Puscas, ISO New England, Inc., 2

- 0 - 0

GSOC is concerned that compliance with Section 6, as proposed, may require a significant investment of resources, specifically that such investment is beyond what is applied to protect high or medium impact BES cyber assets despite the fact that such investment may not yield commensurate reliability and security benefits.

Benjamin Winslett, Georgia System Operations Corporation, 4, 4/15/2022

- 0 - 0

The expansion of the requirement to detect suspicious malicious communication to systems that may not have routable communication and to systems that are not at a Control Center, as is required for high and medium impact, imposes costs that are not consistent with the risks as determined by previous Standard Drafting Teams.

Furthermore we believe the SDT is only accounting for the cost of the equipment that would be responsible for performing the tasks of Section 6.  While this is one cost to consider, there may be additional resources required to allow for implementation of such technology including but not limited to additional staffing, training, or other equipment that would allow a SIM/SEM/SIEM or IDS/IPS to have visibility.

Brian Evans-Mongeon, Utility Services, Inc., 4, 4/15/2022

- 0 - 0

Devon Tremont, Taunton Municipal Lighting Plant, 1, 4/15/2022

- 0 - 0

These modifications, as they are currently written, could be misinterpreted, which would result in a significant expansion of scope of the CIP-003 Attachment 1 requirements and prove detrimental to a cost-efffective approach.  Please reference previously provided comments for additional detail.

Martin Sidor, NRG - NRG Energy, Inc., 6, 4/15/2022

- 0 - 0

Registered Entities would incur significant costs implementing, considering the Low asset inventory included in the scope.

Daniel Gacek, Exelon, 1, 4/15/2022

- 0 - 0

Registered Entities would incur significant costs implementing, considering the Low asset inventory included in the scope.

Kinte Whitehead, Exelon, 3, 4/15/2022

- 0 - 0

Constellation has elected to align with Exelon in response to this question.

Registered Entities could incur significant costs implementing considering the Low Cyber Asset inventory included.

Kimberly Turco, Constellation, 6, 4/15/2022

- 0 - 0

Constellation has elected to align with Exelon in response to this question.

Registered Entities could incur significant costs implementing considering the Low Cyber Asset inventory included.

Alison Mackellar, Constellation, 5, 4/15/2022

- 0 - 0

Until additional clarity is provided on the scope and intent of the proposed modifications, the overall cost is difficult to ascertain.  

Jamie Monette, Allete - Minnesota Power, Inc., 1, 4/15/2022

- 0 - 0

Florida Municipal Power Agency (FMPA), Segment(s) 5, 4, 3, 6, 4/15/2022

- 0 - 0

Selene Willis, Edison International - Southern California Edison Company, 5, 4/15/2022

- 0 - 0

PGE Group 2, Segment(s) 1, 3, 6, 5, 4/15/2022

- 0 - 0

Romel Aquino, Edison International - Southern California Edison Company, 3, 4/15/2022

- 0 - 0

Cowlitz PUD supports the comments submitted by Utility Services Inc.

Russell Noble, Cowlitz County PUD, 3, 4/15/2022

- 0 - 0

NST believes that a considerable amount of research would be needed before many respondents would be able to provide a well-informed answer to this question. We note the December 2019 “Supply Chain Risk Assessment” report states, “More than 99% of the responders (to a survey question about costs and benefits) agreed with the draft response that it was premature for CIP-013 registered entities to determine or estimate costs or benefits associated with the implementation of the standard…” That said, NST believes the cost to implement the proposed requirements could be significant, depending on how a given Responsible Entity has addressed Electronic Access Controls requirements in CIP-003-8, Attachment 1, Section 3 and on the number of facilities where controls may need to be applied.

Roger Fradenburgh, On Behalf of: Nicholas Lauriat, Network and Security Technologies, 1

- 0 - 0

N/A

Daniel Mason, Portland General Electric Co., 6, 4/15/2022

- 0 - 0

Hot Answers

We would rather have one date of 24 months for the whole thing.  Simpler to track and entities are going to need the time for various reasons.  Some that don’t have IDS capabilities at all their sites will have to order and receive and then implement a lot of equipment at a lot of sites.  The 6.1 and 6.2 can be shorter for TO/TOPs that just have substations, or for those with only control centers. With the wide diversity of vendor situations out there on everything from a small solar to a string of wind turbines to a large Generation facility and all matters of variety of vendor arrangements and support, the timeframe and implementation plan is not simple. We do not want to make the assumption that 6.3 is ‘hard’ and needs more time and 6.1 and 6.2 are ‘easier’ and can be done quicker.  In some cases, it might be the opposite.  Whatever the maximum implementation time is, give that to everyone. 

Southern Company, Segment(s) 1, 3, 6, 5, 1/14/2021

- 0 - 0

Deanna Carlson, Cowlitz County PUD, 5, 4/15/2022

- 0 - 0

Other Answers

Comments: These timeframes are sufficient assuming that a significant expansion in scope isn’t being proposed.  Please reference previously provided comments for additional detail.

Patricia Lynch, NRG - NRG Energy, Inc., 5, 3/23/2022

- 0 - 0

Jay Sethi, On Behalf of: Manitoba Hydro - MRO - Segments 1, 3, 5, 6

- 0 - 0

Reclamation recommends a 24-month Implementation Plan. This will allow entities time to determine the effects of the revised requirements and definitions, develop adequate written processes, and train personnel/vendors appropriately.

Richard Jackson, On Behalf of: U.S. Bureau of Reclamation, , Segments 1, 5

- 0 - 0

Jennifer Malon, On Behalf of: Black Hills Corporation - MRO, WECC - Segments 1, 3, 5, 6

- 0 - 0

Tennessee Valley Authority, Segment(s) 1, 3, 5, 6, 10/18/2018

- 0 - 0

BHE expects implementation of Section 6.3 to require the purchase of a significant amount of new equipment. Hundreds of Registered Entities will all be purchasing intrusion detection systems at the same time, and within a short deliverable window to allow time for installation, resulting in even greater supply chain issues. Please consider adding something like the following to the implementation plan to address this potential issue: “If the Responsible Entity encounters significant supply chain issues, the Responsible Entity may request an extension from the Regional Entity.” While this would need additional details developed, it would provide the industry with assurance that supply chain issues outside of their control would not result in non-compliance. An example of an extension might be equal to the time between placing orders for needed equipment and receiving said orders. BHE also requests NERC consider ways to work with equipment manufacturers to try to address the increased demand for this equipment. 

Joseph Amato, Berkshire Hathaway Energy - MidAmerican Energy Co., 3, 4/6/2022

- 0 - 0

Santee Cooper, Segment(s) 1, 3, 5, 6, 4/6/2022

- 0 - 0

Mike Marshall, 4/6/2022

- 0 - 0

Sections 6.1 and 6.2 will not have equivalent language for Mediums without ERC until CIP-005-8 R2.4 and R2.5 are adopted. Therefore, BPA recommends that implementation of these sections should be aligned with the passage of CIP-005-8 to avoid entities having to monitor their Low assets but not their Mediums without ERC and/or Dialup.

Section 6.3 has no current equivalent language in CIP-005-8 (nor any other standards) for Medium impact BES Cyber Systems except at Control Centers.  Until then, entities will be expected to detect malicious communications at certain Low assets but none of their Medium assets outside of a control center.  This is a significant gap; BPA recommends that the drafting team delay Section 6.3 until CIP-005 is expanded to include Mediums outside of Control Centers.

Andrea Jessup, On Behalf of: Bonneville Power Administration, WECC, Segments 1, 3, 5, 6

- 0 - 0

After further consideration, we believe that a 36 month implementation timeline would be most appropriate for incorporating all the revisions in Project 2020-03. This will allow for proper installation, testing and documentation of new controls across a large inventory of sites and assets. This timeline would also be more feasible given the current supply chain challenges across industry.

Ellese Murphy, On Behalf of: Duke Energy - MRO, WECC, Texas RE, SERC, RF - Segments 1, 3, 5, 6

- 0 - 0

Lan Nguyen, On Behalf of: CenterPoint Energy Houston Electric, LLC, Texas RE, Segments 1

- 0 - 0

No comment

Wes DeKemper, On Behalf of: Southern Indiana Gas and Electric Co., RF, Segments 3, 5, 6

- 0 - 0

Donald Lock, On Behalf of: Talen Generation, LLC, , Segments 5

- 0 - 0

JT Kuehne, AEP, 6, 4/8/2022

- 0 - 0

Scott Miller, 4/8/2022

- 0 - 0

Jeanne Kurzynowski, On Behalf of: CMS Energy - Consumers Energy Company, RF, Segments 1, 3, 5

- 0 - 0

Lindsey Mannion, ReliabilityFirst , 10, 4/11/2022

- 0 - 0

The expansion of scope for vendor remote access monitoring and malicious communication monitoring may require new technology to be implemented within the program.  The implementation for said technology for a large utility will require a longer implementation than 24 months.

Dominion, Segment(s) 3, 5, 1, 9/19/2019

- 0 - 0

36 months minimum as additional staff or staff augmentation would have to be employed as there would be a significant amount of design, planning, testing, and finally, deployiment of solutions to the affected assets in the field.

Steve Toosevich, NiSource - Northern Indiana Public Service Co., 1, 4/11/2022

- 0 - 0

WECC Entity Monitoring, Segment(s) 10, 1/30/2022

- 0 - 0

AZPS feels that a 24-month implementation plan would be a reasonable timeframe to implement process, procedures or technology to meet the proposed language in Sections 6.1 and 6.2, in addition to Section 6.3. It may be necessary to design and implement multiple solutions to meet the proposed language in Section 6 across the various environments in which low impact assets are in use. Alternatively, a single solution which could be applied across a broader group of low assets may require significant design changes to process, procedures and/or technology.

Michelle Amarantos, APS - Arizona Public Service Co., 5, 4/11/2022

- 0 - 0

Glen Farmer, Avista - Avista Corporation, 5, 4/11/2022

- 0 - 0

Due to supply chain constraints on security equipment we believe an additional 12 months should be included or an exception were procurements happens within that time frame to adhere compliance.

Jesus Sammy Alcaraz, Imperial Irrigation District, 1, 4/11/2022

- 0 - 0

Tim Kelley, On Behalf of: Nicole Looney, Sacramento Municipal Utility District, 1,3,4,5,6; Foung Mua, Sacramento Municipal Utility District, 1,3,4,5,6; Nicole Goi, Sacramento Municipal Utility District, 1,3,4,5,6; Kevin Smith, Balancing Authority of Northern California, 1; Charles Norton, Sacramento Municipal Utility District, 1,3,4,5,6

- 0 - 0

BHE expects implementation of Section 6.3 to require the purchase of a significant amount of new equipment. Hundreds of Registered Entities will all be purchasing intrusion detection systems at the same time, and within a short deliverable window to allow time for installation, resulting in even greater supply chain issues. Please consider adding something like the following to the implementation plan to address this potential issue: “If the Responsible Entity encounters significant supply chain issues, the Responsible Entity may request an extension from the Regional Entity.” While this would need additional details developed, it would provide the industry with assurance that supply chain issues outside of their control would not result in non-compliance. An example of an extension might be equal to the time between placing orders for needed equipment and receiving said orders. BHE also requests NERC consider ways to work with equipment manufacturers to try to address the increased demand for this equipment.

Lindsay Wickizer, Berkshire Hathaway - PacifiCorp, 6, 4/11/2022

- 0 - 0

A 24 month implementation is desirable due to budget, supply chain, and resources to implement solutions for SRP’s Generation fleet.

Israel Perez, On Behalf of: Salt River Project - WECC - Segments 1, 3, 5, 6

- 0 - 0

Texas RE does not have comments on the question.

Rachel Coyne, Texas Reliability Entity, Inc., 10, 4/12/2022

- 0 - 0

Again this is very dependent on the size of the entity, if the entity has medium or high impact BES Cyber Systems, if the entity has medium or high impact BES Cyber Systems at Control Centers, how many low impact BES Cyber Systems the entity has, and if supply chain will play a role in delaying the implementation of the controls for entities.  Because of potential supply chain issues and new technology implementation, there needs to be allowances at least for Attachment 1, Section 6.3, to allow entities more time to implement, the required control, if necessary.

Susan Sosbe, Wabash Valley Power Association, 3, 4/12/2022

- 0 - 0

See EEI comment.

Clay Walker, On Behalf of: John Lindsey, Cleco Corporation, 1,3,5,6; Robert Hirchak, Cleco Corporation, 1,3,5,6; Maurice Paulk, Cleco Corporation, 1,3,5,6

- 0 - 0

Scott Kinney, Avista - Avista Corporation, 3, 4/12/2022

- 0 - 0

AEPCO is signing on to ACES comments below.

ACES comments:  Again this is very dependent on the size of the entity, if the entity has medium or high impact BES Cyber Systems, if the entity has medium or high impact BES Cyber Systems at Control Centers, how many low impact BES Cyber Systems the entity has, and if supply chain will play a role in delaying the implementation of the controls for entities.  Because of potential supply chain issues and new technology implementation, there needs to be allowances at least for Attachment 1, Setion 6.3, to allow entities more time to implement, the required control, if necessary.

Jennifer Bray, Arizona Electric Power Cooperative, Inc., 1, 4/12/2022

- 0 - 0

PNM supports EEI comments regarding the implementation timeframe for 6.3 to be extended to 36-months if the scope of 6.3 is not sufficiently narrowed as mentioned in the comments for question 1. 

Lynn Goldstein, PNM Resources - Public Service Company of New Mexico, 1, 4/12/2022

- 0 - 0

patricia ireland, DTE Energy, 4, 4/13/2022

- 0 - 0

Xcel Energy is concerned with meeting the implementation demands of section 6 within the proposed timeline identified in the implementation plan. World events have created issues with supply chain and obtaining the needed products and staff to perform activities required in the standard in a timely manner. The vast number of low impact sites as compared to high and medium sites will cause a sudden surge in demand and cause prices to rise dramatically. Additionally, an industry-wide staffing shortage will slow efforts to implement and maintain newly procured products. The standard drafting team should take these issues into consideration in their implementation plan to spread costs and demand for products and staff across and longer span of time.  

Joe Gatten, On Behalf of: Xcel Energy, Inc. - MRO, WECC - Segments 1, 3, 5, 6

- 0 - 0

As mentioned in Question 6, many entities have large amount of low impact sites that are in remote locations and struggle with limited bandwith which makes procruement, and implementation of new hardware and software difficult.  There is the other challenge of the recent supply chain and staffing issues that will also impact implementation timelines.  The supply chain being taxed all at once by utilites to meet the short timeline should must be taken into consideration.  

 

 

Donna Wood, Tri-State G and T Association, Inc., 1, 4/13/2022

- 0 - 0

Alliant Energy supports the comments submitted by the MRO NSRF.

Larry Heckert, Alliant Energy Corporation Services, Inc., 4, 4/13/2022

- 0 - 0

LaTroy Brumfield, American Transmission Company, LLC, 1, 4/13/2022

- 0 - 0

If scope of this standard is tightened to what FE believes is the spirit of the standard, we feel we could follow the proposed implementation plan. As it is written, we feel the vagueness of the draft leaves ambiguity and would require a longer implementation plan to fulfill our obligation.

FE Voter, Segment(s) 1, 3, 5, 6, 4, 12/20/2021

- 0 - 0

Consider large-scale supply chain and implementation issues. If all entities request supplies at the same time, what will be the supply chain impact?

Carl Pineault, On Behalf of: Hydro-Qu?bec Production, , Segments 1, 5

- 0 - 0

Evergy supports and incorporates the comments from the Edison Electric Institute (EEI) for questions #7.

- 0 - 0

BC Hydro recommends a longer implementation plan, e.g. more than ~ 36 months considering the cost and scope impact as identified in comments to Questions 1 and 4 above. Once the clarity of terms and definitions is obtained as identified in comments to Questions 1 and 4, BC Hydro will be in a better position to provide an alternate detailed implmentation plan to meet the target completion deadline.

BC Hydro, Segment(s) 3, 5, 1, 12/18/2018

- 0 - 0

If all examples in Attachment 2 are ever required then we believe that additional time above the 18 months may be required.

David Jendras, Ameren - Ameren Services, 3, 4/14/2022

- 0 - 0

Gerry Adamski, On Behalf of: Cogentrix Energy Power Management, LLC, , Segments 5

- 0 - 0

The MRO NSRF anticipates the procurement and implementation of new software, hardware, and associated services needed to detect vendor’s malicious communications to be particularly challenging given recent supply chain issues, industry-wide staffing shortages, and other geopolitical factors. Registered Entities across North America will all be attempting to procure needed solutions in a relatively small window of time. This will create a deficit of supply with increased demand and will drive up costs. That, along with current staffing shortages and geopolitical events, may produce scenarios that will prevent a responsible entity from meeting the effective date set in the approved implementation plan. The MRO NSRF suggests the SDT align with NERC legal staff to allow for a provision in the implementation plan that would provide an opportunity for entities to request extensions based on the aforementioned factors.

MRO NSRF, Segment(s) 2, 3, 5, 1, 4, 6, 4/11/2022

- 0 - 0

Acciona Energy supports Midwest Reliability Organization’s (MRO) NERC Standards Review Forum’s (NSRF) comments on this question.

George Brown, Acciona Energy North America, 5, 4/14/2022

- 0 - 0

Mike Magruder, Avista - Avista Corporation, 1, 4/14/2022

- 0 - 0

There could be additional needs for technology purposes which would create funding needs based on funding cycles and implementation. Strongly recommended to inceas all sections to a 24 mth implementation.

Brian Lindsey, Entergy, 1, 4/14/2022

- 0 - 0

  • NextEra Energy requests consideration of a 36-month implementation period due to a large number of sites (in the hundreds) requiring assessment and potentially new equipment and/or process implementation.  The work must be planned and typically will be scheduled with planned maintenance and scheduled generation outages.   

  • The last few years the supply chain has adversely impacted maintenance including staffing and is expected to impact the implementation.    

  • Entities may need to evaluate and update vendor, supplier, customer and other agreements and contracts.   

Mike ONeil, 4/14/2022

- 0 - 0

Given the uncertainty regarding the exact scope of implementation across low impact and all vendor communications it is hard to believe the 18 months will be sufficient timing.

Gail Elliott, On Behalf of: International Transmission Company Holdings Corporation - MRO, RF - Segments NA - Not Applicable

- 0 - 0

There is a high likelihood that new technology controls will be required to effectively meet the intent of these new requirements. Implementation of new technology takes time and careful consideration. Additionally, current supply chain challenges may pose an additional risk to effectively implementing.

LCRA Compliance, Segment(s) 6, 5, 1, 5/11/2015

- 0 - 0

The NAGF has no comments.

Wayne Sipperly, On Behalf of: North American Generator Forum, MRO, WECC, Texas RE, NPCC, SERC, RF, Segments 5

- 0 - 0

There is a high likelihood that new technology controls will be required to effectively meet the intent of these new requirements. Implementation of new technology takes time and careful consideration. Additionally, current supply chain challenges may pose an additional risk to effectively implementing.

James Baldwin, Lower Colorado River Authority, 1, 4/15/2022

- 0 - 0

Again this is very dependent on the size of the entity, if the entity has medium or high impact BES Cyber Systems, if the entity has medium or high impact BES Cyber Systems at Control Centers, how many low impact BES Cyber Systems the entity has, and if supply chain will play a role in delaying the implementation of the controls for entities.  Because of potential supply chain issues and new technology implementation, there needs to be allowances at least for Attachment 1, Setion 6.3, to allow entities more time to implement, the required control, if necessary.

ACES Standard Collaborations, Segment(s) 1, 3, 5, 4, 4/15/2022

- 0 - 0

EEI appreciates the two-phase implementation plan for Attachment 1, Section 6 and supports the proposed 18-month implementation plan for subparts 6.1 and 6.2.  However, we do not agree that an additional 6 months to complete subpart 6.3 is adequate, particularly given the current proposed language could be interpreted to mean all low impact BES Cyber System communication.  Moreover, if the current language is not narrowed consistent with a risk-based approach it may be a significant challenge for some entities to complete this work in 36 months.  EEI previously noted that there will be substantial work to complete 6.3 and companies are also facing significant supply chain issues/delays to secure materials necessary to implement these changes.  For these reasons, the implementation plan should be at a minimum of 36 months.

Mark Gray, On Behalf of: Edison Electric Institute, NA - Not Applicable, Segments NA - Not Applicable

- 0 - 0

Consider large-scale supply chain and implementation issues. If all entities request supplies at the same time, what will be the supply chain impact?

NPCC Regional Standards Committee, Segment(s) 10, 2, 4, 7, 3, 1, 5, 6, 4/6/2022

- 0 - 0

NVE expects implementation of Section 6.3 to require the purchase of a significant amount of new equipment. Hundreds of Registered Entities will all be purchasing intrusion detection systems at the same time, and within a short deliverable window to allow time for installation, resulting in even greater supply chain issues. Please consider adding something like the following to the implementation plan to address this potential issue: “If the Responsible Entity encounters significant supply chain issues, the Responsible Entity may request an extension from the Regional Entity.” While this would need additional details developed, it would provide the industry with assurance that supply chain issues outside of their control would not result in non-compliance. An example of an extension might be equal to the time between placing orders for needed equipment and receiving said orders. NVE also requests NERC consider ways to work with equipment manufacturers to try to address the increased demand for this equipment.

Dwanique Spiller, Berkshire Hathaway - NV Energy, 5, 4/15/2022

- 0 - 0

No comment.

John Galloway, On Behalf of: Michael Puscas, ISO New England, Inc., 2

- 0 - 0

Given the potential impact of expanded scope of Section 6.3, GSOC would respectfully request a 24 month implementation period given the current state of global supply chain lead times.

Benjamin Winslett, Georgia System Operations Corporation, 4, 4/15/2022

- 0 - 0

The ability for entities to apply these control may be limited by the availability of equipment and the vendors qualified to install them. The SDT should request that NERC provide information on the expected number of substations that may be required to implement these controls. It may be necessary to include an automatic extension of the time allowed for implementation, if necessary, equipment and personnel to perform the installation are not available.

Brian Evans-Mongeon, Utility Services, Inc., 4, 4/15/2022

- 0 - 0

Devon Tremont, Taunton Municipal Lighting Plant, 1, 4/15/2022

- 0 - 0

These timeframes are sufficient assuming that a significant expansion in scope isn’t being proposed.  Please reference previously provided comments for additional detail.

Martin Sidor, NRG - NRG Energy, Inc., 6, 4/15/2022

- 0 - 0

One collective implementation time frame. Because of the significant changes proposed by the SDT, can we set the entire standard to a 36 months implementation plan. 

Daniel Gacek, Exelon, 1, 4/15/2022

- 0 - 0

One collective implementation time frame. Because of the significant changes proposed by the SDT, can we set the entire standard to a 36 months implementation plan.

Kinte Whitehead, Exelon, 3, 4/15/2022

- 0 - 0

Constellation has elected to align with Exelon in response to this question.

One collective implementation time frame. Because of the significant changes proposed by the SDT, can we set the entire standard to a 36 months implementation plan.

Kimberly Turco, Constellation, 6, 4/15/2022

- 0 - 0

Constellation has elected to align with Exelon in response to this question.

One collective implementation time frame. Because of the significant changes proposed by the SDT, can we set the entire standard to a 36 months implementation plan.

Alison Mackellar, Constellation, 5, 4/15/2022

- 0 - 0

Until additional clarification is provided on the scope and intent of the proposed changes, it’s unclear if the drafted implementation timelines are sufficient to implement the requirements.

Jamie Monette, Allete - Minnesota Power, Inc., 1, 4/15/2022

- 0 - 0

Florida Municipal Power Agency (FMPA), Segment(s) 5, 4, 3, 6, 4/15/2022

- 0 - 0

Selene Willis, Edison International - Southern California Edison Company, 5, 4/15/2022

- 0 - 0

 PGE supports the survey response provided by EEI.

PGE Group 2, Segment(s) 1, 3, 6, 5, 4/15/2022

- 0 - 0

Romel Aquino, Edison International - Southern California Edison Company, 3, 4/15/2022

- 0 - 0

Cowlitz PUD supports the comments submitted by the Bonneville Power Administration (BPA).

Russell Noble, Cowlitz County PUD, 3, 4/15/2022

- 0 - 0

NST believes the time required to implement the proposed requirements could be significant, depending on how a given Responsible Entity has addressed Electronic Access Controls requirements in CIP-003-8, Attachment 1, Section 3 and on the number of facilities where controls may need to be applied. NST recommends a 24-month implementation time frame for all of Attachment 1, Section 6 requirements.

Roger Fradenburgh, On Behalf of: Nicholas Lauriat, Network and Security Technologies, 1

- 0 - 0

 PGE supports the survey response provided by EEI.

Daniel Mason, Portland General Electric Co., 6, 4/15/2022

- 0 - 0

Hot Answers

These ‘low’ requirements as written seem to be more stringent than what highs and mediums have to comply with today. Highs and Mediums have to determine ‘active’ sessions and have a method to disable remote access. That is far easier than determining what constitutes malicious inbound and outbound communications.

Southern Company, Segment(s) 1, 3, 6, 5, 1/14/2021

- 0 - 0

Deanna Carlson, Cowlitz County PUD, 5, 4/15/2022

- 0 - 0

Other Answers

Patricia Lynch, NRG - NRG Energy, Inc., 5, 3/23/2022

- 0 - 0

Jay Sethi, On Behalf of: Manitoba Hydro - MRO - Segments 1, 3, 5, 6

- 0 - 0

Reclamation appreciates the SDT’s efforts to incorporate the NIST Framework into the NERC Standards. Reclamation encourages the SDT to continue this practice to ensure that NERC standards do not duplicate requirements contained within the NIST Framework.

Richard Jackson, On Behalf of: U.S. Bureau of Reclamation, , Segments 1, 5

- 0 - 0

Jennifer Malon, On Behalf of: Black Hills Corporation - MRO, WECC - Segments 1, 3, 5, 6

- 0 - 0

Tennessee Valley Authority, Segment(s) 1, 3, 5, 6, 10/18/2018

- 0 - 0

The Technical Rationale document had a footnote reference to the term vendor as used in CIP-013 that was removed. BHE found it useful and requests that the footnote be reinstated. 

Joseph Amato, Berkshire Hathaway Energy - MidAmerican Energy Co., 3, 4/6/2022

- 0 - 0

Santee Cooper, Segment(s) 1, 3, 5, 6, 4/6/2022

- 0 - 0

Mike Marshall, 4/6/2022

- 0 - 0

Andrea Jessup, On Behalf of: Bonneville Power Administration, WECC, Segments 1, 3, 5, 6

- 0 - 0

Ellese Murphy, On Behalf of: Duke Energy - MRO, WECC, Texas RE, SERC, RF - Segments 1, 3, 5, 6

- 0 - 0

Lan Nguyen, On Behalf of: CenterPoint Energy Houston Electric, LLC, Texas RE, Segments 1

- 0 - 0

No comment

Wes DeKemper, On Behalf of: Southern Indiana Gas and Electric Co., RF, Segments 3, 5, 6

- 0 - 0

Donald Lock, On Behalf of: Talen Generation, LLC, , Segments 5

- 0 - 0

JT Kuehne, AEP, 6, 4/8/2022

- 0 - 0

 

 

Scott Miller, 4/8/2022

- 0 - 0

Jeanne Kurzynowski, On Behalf of: CMS Energy - Consumers Energy Company, RF, Segments 1, 3, 5

- 0 - 0

Lindsey Mannion, ReliabilityFirst , 10, 4/11/2022

- 0 - 0

Dominion, Segment(s) 3, 5, 1, 9/19/2019

- 0 - 0

Steve Toosevich, NiSource - Northern Indiana Public Service Co., 1, 4/11/2022

- 0 - 0

In the Technical Rational, first sentence in the foreward, consider using language consistent with Section 6. Change ‘electronic remote vendor access’ to ‘electronic vendor remote access.

WECC Entity Monitoring, Segment(s) 10, 1/30/2022

- 0 - 0

Michelle Amarantos, APS - Arizona Public Service Co., 5, 4/11/2022

- 0 - 0

Glen Farmer, Avista - Avista Corporation, 5, 4/11/2022

- 0 - 0

With the consideration of the FERC NOPR.  Additional architecture diagrams should be illustrated for a possible IDS/IPS implementation similar to when EAC under section 3 there were guidance architecture diagrams.

Jesus Sammy Alcaraz, Imperial Irrigation District, 1, 4/11/2022

- 0 - 0

Tim Kelley, On Behalf of: Nicole Looney, Sacramento Municipal Utility District, 1,3,4,5,6; Foung Mua, Sacramento Municipal Utility District, 1,3,4,5,6; Nicole Goi, Sacramento Municipal Utility District, 1,3,4,5,6; Kevin Smith, Balancing Authority of Northern California, 1; Charles Norton, Sacramento Municipal Utility District, 1,3,4,5,6

- 0 - 0

The Technical Rationale document had a footnote reference to the term vendor as used in CIP-013 that was removed. BHE found it useful and requests that the footnote be reinstated. 

Lindsay Wickizer, Berkshire Hathaway - PacifiCorp, 6, 4/11/2022

- 0 - 0

Will inventory lists now be required for Low Impact sites? Based on the current requirements, is it safe to assume that cloud electronic access controls are acceptable for vendor remote access into low impact sites?

Israel Perez, On Behalf of: Salt River Project - WECC - Segments 1, 3, 5, 6

- 0 - 0

Texas RE continues to have the following additional recommendations for the SDT:

  • Include language for (1) software integrity and authenticity, (2) information system planning and (3) vendor risk and procurement controls, which addresses various aspects of supply chain risk management as is consistent with Reliability Standards CIP-013 and CIP-010.
  • Include vendor multi-factor authentication (MFA). Passwords can be subjected to numerous cyber-attacks, including brute force. MFA provides an additional layer of security and protects systems should passwords become known by unauthorized users.
  • Include controls for encrypted vendor remote access sessions, which is consistent with CIP-005 Requirement R2.

Rachel Coyne, Texas Reliability Entity, Inc., 10, 4/12/2022

- 0 - 0

We would like to thank the SDT for their efforts and allowing the industry to participate in the drafting process. 

 

Susan Sosbe, Wabash Valley Power Association, 3, 4/12/2022

- 0 - 0

See EEI comment.

Clay Walker, On Behalf of: John Lindsey, Cleco Corporation, 1,3,5,6; Robert Hirchak, Cleco Corporation, 1,3,5,6; Maurice Paulk, Cleco Corporation, 1,3,5,6

- 0 - 0

My intended vote for this ballot was negative based on the comments provided in this survey. However due to technical issues with the voting platform while casting my vote it is shown as affirmative.  If possible please replace my affirmative vote with a negative vote. 

Scott Kinney, Avista - Avista Corporation, 3, 4/12/2022

- 0 - 0

Thank you to the SDT for their efforts and allowing AEPCO to participate in the drafting process.

Jennifer Bray, Arizona Electric Power Cooperative, Inc., 1, 4/12/2022

- 0 - 0

Lynn Goldstein, PNM Resources - Public Service Company of New Mexico, 1, 4/12/2022

- 0 - 0

We remain concerned that the CIP-003 Attachment 1, Section 6.3 requirement for malicious communication places a heavier compliance burden on low impact assets than High and Medium, as deliniteated in CIP-005 (2.4 and 2.5).  Simply extending the the implementation timeframe for this requirement does not address that basic inconsistency.

patricia ireland, DTE Energy, 4, 4/13/2022

- 0 - 0

Xcel Energy would like to thank the drafting team for their diligent work and bringing forward language to address the concerns identified by the NERC BOT. 

Joe Gatten, On Behalf of: Xcel Energy, Inc. - MRO, WECC - Segments 1, 3, 5, 6

- 0 - 0

Donna Wood, Tri-State G and T Association, Inc., 1, 4/13/2022

- 0 - 0

Alliant Energy appreciates the Standard Drafting Team's work on this project.

Larry Heckert, Alliant Energy Corporation Services, Inc., 4, 4/13/2022

- 0 - 0

LaTroy Brumfield, American Transmission Company, LLC, 1, 4/13/2022

- 0 - 0

FE Voter, Segment(s) 1, 3, 5, 6, 4, 12/20/2021

- 0 - 0

For future reference, request redline to last approved since that shows the true SDT proposed updates.

 

Recommend updating R1.2.6 by removing “Electronic” from “Electronic vendor remote access security controls.” The security concern is vendor remote access.

 

Recommend updating Attachment 1 by removing “Electronic” from “Electronic

vendor” for consistency with Requirement R1.2.6

 

Request clarification on Attachment 1 Section 6.3. Why a Low Requirement has a larger scope than the corresponding Medium Requirement (CIP-005 R1.6) The proposed Requirement for CIP-005 R1.6 says “detecting known or suspected malicious Internet Protocol (IP) communications entering or leaving an ESP.” 6.3 says “detecting known or suspected malicious communications for both inbound and outbound vendor communications.” 6.3 applies to all vendor communications, not just IP. Next CIP-005 R1.6’s Applicable Systems says “Medium impact BCS at Control Centers” 6.3 applies to all vendor communications, not just Control Centers.

 

Recommend updating Attachment 2 by removing “Electronic” from “Electronic vendor” for consistency with Requirement R1.2.6

Carl Pineault, On Behalf of: Hydro-Qu?bec Production, , Segments 1, 5

- 0 - 0

Evergy supports and incorporates the comments from the Edison Electric Institute (EEI) for questions #8.

- 0 - 0

BC Hydro ackowledges the effort and hard work SDT put into putting these complex changes to CIP-003-X. As identified in comments to Questions 1 to 4 above. The definitions of terms and clarity of application with some specific industry use case examples will help providing a more clear understanding and likely result in a faster and appropriate approvals of these proposed changes.

BC Hydro, Segment(s) 3, 5, 1, 12/18/2018

- 0 - 0

David Jendras, Ameren - Ameren Services, 3, 4/14/2022

- 0 - 0

For future reference, request redline to last approved since that shows the true SDT proposed updates.

Recommend updating R1.2.6 by removing “Electronic” from “Electronic vendor remote access security controls.” The security concern is vendor remote access.

Recommend updating Attachment 1 by removing “Electronic” from “Electronic vendor” for consistency with Requirement R1.2.6

Request clarification on Attachment 1 Section 6.3. Why a Low Requirement has a larger scope than the corresponding Medium Requirement (CIP-005 R1.6) The proposed Requirement for CIP-005 R1.6 says “detecting known or suspected malicious Internet Protocol (IP) communications entering or leaving an ESP.” 6.3 says “detecting known or suspected malicious communications for both inbound and outbound vendor communications.” 6.3 applies to all vendor communications, not just IP. Next CIP-005 R1.6’s Applicable Systems says “Medium impact BCS at Control Centers” 6.3 applies to all vendor communications, not just Control Centers.  The low requirement may encompass email, phone, and or mail communications from vendors, because of the vague language used.

Recommend updating Attachment 2 by removing “Electronic” from “Electronic vendor” for consistency with Requirement R1.2.6

Gerry Adamski, On Behalf of: Cogentrix Energy Power Management, LLC, , Segments 5

- 0 - 0

The MRO NSRF would like to thank the Standard Drafting Team, NERC Staff and all other contributors for their work on this project.

MRO NSRF, Segment(s) 2, 3, 5, 1, 4, 6, 4/11/2022

- 0 - 0

Acciona Energy supports Midwest Reliability Organization’s (MRO) NERC Standards Review Forum’s (NSRF) comments on this question.

George Brown, Acciona Energy North America, 5, 4/14/2022

- 0 - 0

Mike Magruder, Avista - Avista Corporation, 1, 4/14/2022

- 0 - 0

NA

Brian Lindsey, Entergy, 1, 4/14/2022

- 0 - 0

  • Please provide redline to last approved since that shows the true SDT proposed updates. 

  • Please apply  NEE’s response to question 1 respectfully submitting updated language  CIP-003 Attachment 1, Section 6 and Attachment 2, Section 6 to the standard and technical rationale document.  

  • Page 4 “ The SDT agreed to retain Section 3 and establish Section 6 to address vendors and low impact electronic remote access,” change to “The SDT agreed to retain Section 3 and establish Section 6 to address low impact vendor electronic remote access,” 

  • Page 5: 

  • “establish and disable electronic vendor remote access.”  to be “establish and disable vendor electronic remote access.” 

  • “low impact BES Cyber Systems to: (1) detect known or suspected malicious communications for both inbound and outbound communications; (2) determine when active vendor remote access sessions are initiated; and (3) disable active vendor remote access when necessary.”  to be  “low impact BES Cyber Systems to: (1) detect known or suspected malicious communications for both inbound and outbound communications; (2) determine when active vendor electronic remote access sessions are initiated; and (3) disable active vendor electronic remote access when necessary.” 

  • Attachment 1 Section 6 Part 6.1 – Determining Vendor Electronic Remote Access 

  • “associated with malicious communications and electronic vendor remote access.”   to be “associated with malicious communications and vendor electronic remote access.” 

  • Attachment 1 Section 6 Part 6.2 – Disabling vendor electronic remote access 

  • Enhanced visibility into electronic vendor remote access and the ability to terminate electronic vendor remote access could mitigate such a vulnerability. The obligation in Section 6.2 requires that entities have a method to disable electronic vendor remote access.”      to  be  “Enhanced visibility into vendor electronic remote access and the ability to terminate   vendor electronic remote access could mitigate such a vulnerability. The obligation in Section 6.2 requires that entities have a method to disable vendor electronic remote access

  • Page 6 

  • Attachment 1 Section 6 Part 6.3 – Detecting known or suspected malicious communications for both inbound and outbound communications for vendor electronic remote access 

Mike ONeil, 4/14/2022

- 0 - 0

Gail Elliott, On Behalf of: International Transmission Company Holdings Corporation - MRO, RF - Segments NA - Not Applicable

- 0 - 0

No additional comments at this time.

LCRA Compliance, Segment(s) 6, 5, 1, 5/11/2015

- 0 - 0

The NAGF membership recommends that the SDT consider providing reference architecture diagram(s) similar to previous reference model provided in CIP-003.

Wayne Sipperly, On Behalf of: North American Generator Forum, MRO, WECC, Texas RE, NPCC, SERC, RF, Segments 5

- 0 - 0

James Baldwin, Lower Colorado River Authority, 1, 4/15/2022

- 0 - 0

We would like to thank the SDT for their efforts and allowing the industry to participate in the drafting process.

ACES Standard Collaborations, Segment(s) 1, 3, 5, 4, 4/15/2022

- 0 - 0

In the proposed Draft 2 of CIP-003-x, the undefined term “Electronic Vendor” has been used eleven times (including within Section 6 of Attachment 1).  It is unclear what is meant by the use of this term and if this term is to remain within this Reliability Standard, the SDT should provide needed clarification through the Technical Rationale. 

 

Mark Gray, On Behalf of: Edison Electric Institute, NA - Not Applicable, Segments NA - Not Applicable

- 0 - 0

For future reference, request redline to last approved since that shows the true SDT proposed updates.

 

Recommend updating R1.2.6 by removing “Electronic” from “Electronic vendor remote access security controls.” The security concern is vendor remote access.

 

Recommend updating Attachment 1 by removing “Electronic” from “Electronic

vendor” for consistency with Requirement R1.2.6

 

Request clarification on Attachment 1 Section 6.3. Why a Low Requirement has a larger scope than the corresponding Medium Requirement (CIP-005 R1.6) The proposed Requirement for CIP-005 R1.6 says “detecting known or suspected malicious Internet Protocol (IP) communications entering or leaving an ESP.” 6.3 says “detecting known or suspected malicious communications for both inbound and outbound vendor communications.” 6.3 applies to all vendor communications, not just IP. Next CIP-005 R1.6’s Applicable Systems says “Medium impact BCS at Control Centers” 6.3 applies to all vendor communications, not just Control Centers.

 

Recommend updating Attachment 2 by removing “Electronic” from “Electronic vendor” for consistency with Requirement R1.2.6

NPCC Regional Standards Committee, Segment(s) 10, 2, 4, 7, 3, 1, 5, 6, 4/6/2022

- 0 - 0

The Technical Rationale document had a footnote reference to the term vendor as used in CIP-013 that was removed. NVE found it useful and requests that the footnote be reinstated.

Dwanique Spiller, Berkshire Hathaway - NV Energy, 5, 4/15/2022

- 0 - 0

No comment.

John Galloway, On Behalf of: Michael Puscas, ISO New England, Inc., 2

- 0 - 0

Benjamin Winslett, Georgia System Operations Corporation, 4, 4/15/2022

- 0 - 0

All proposed controls should be limited to only low impact BES Cyber Systems as opposed to assets containing low impact BES Cyber Systems.

 

The proposed control for detecting malicious communication should be limited to:

1.      Only low impact BES Cyber Systems using a routable protocol to communicate across the asset boundary and,

2.      Only Control Centers (to align with CIP-005-7 R1.5)

Brian Evans-Mongeon, Utility Services, Inc., 4, 4/15/2022

- 0 - 0

The most concerning to us is Attachment 1, Section 6.3 in which the term "detecting" known or suspected malicious communications for vendors is used. The term "detecting" is unclear to us. We are unsure if this would require continuous monitoring of the vendor's session, or if it is simply intended to at least manually review the vendor's session after the fact. Is the intent to provide constant real-time monitoring, which would be costly and time consuming? 

Devon Tremont, Taunton Municipal Lighting Plant, 1, 4/15/2022

- 0 - 0

Martin Sidor, NRG - NRG Energy, Inc., 6, 4/15/2022

- 0 - 0

What is meant by ‘Electronic Vendor’? Currently it’s not a defined term, SDT should consider making this a NERC defined glossary term. 

Daniel Gacek, Exelon, 1, 4/15/2022

- 0 - 0

What is meant by ‘Electronic Vendor’? Currently it’s not a defined term, SDT should consider making this a NERC defined glossary term.

Kinte Whitehead, Exelon, 3, 4/15/2022

- 0 - 0

SDT should consider defining the term “Electronic Vendor” in the NERC defined Glossary of Terms.

Kimberly Turco, Constellation, 6, 4/15/2022

- 0 - 0

SDT should consider defining the term “Electronic Vendor” in the NERC defined Glossary of Terms.

Alison Mackellar, Constellation, 5, 4/15/2022

- 0 - 0

Jamie Monette, Allete - Minnesota Power, Inc., 1, 4/15/2022

- 0 - 0

Florida Municipal Power Agency (FMPA), Segment(s) 5, 4, 3, 6, 4/15/2022

- 0 - 0

See Comments submitted by the Edison Electric Institute.” with your ballot.

 

Selene Willis, Edison International - Southern California Edison Company, 5, 4/15/2022

- 0 - 0

PGE Group 2, Segment(s) 1, 3, 6, 5, 4/15/2022

- 0 - 0

See Comments submitted by the Edison Electric Institute.

Romel Aquino, Edison International - Southern California Edison Company, 3, 4/15/2022

- 0 - 0

Cowlitz PUD supports the comments submitted by Utility Services Inc.

Russell Noble, Cowlitz County PUD, 3, 4/15/2022

- 0 - 0

NST believes it is short-sighted to add a new requirement to CIP-003 for malicious communications detection that is limited to vendor remote access only. Advocates for this limitation seem to be ignoring the possibility a Responsible Entity's own remote computer systems could be compromised by attackers and used to deliver malware to BES Cyber Systems (BCS) at BES assets containing low impact BCS. In addition, NST believes that limiting the scope of monitoring and detecting to only vendor remote access either may not be practical or may result in sub-optimal designs that would need to be updated should monitoring and detecting requirements be expanded in the future. Given the likely time, effort, and expense associated with implementing a solution for malicious code detection (using IDS or similar technology), we think it only makes sense to require it for all remote access. NST also notes that in its recent NOPR proposing "Internal Network Security Monitoring" requirements for high and medium BES Cyber Systems, FERC indicated it is interested in the possibility of applying "INSM" requirements to low impact, as well. This suggests to us that while FERC might approve the current set of proposed supply chain revisions to CIP-003, were they to be approved by industry ballot and the NERC board, they might also direct NERC to further modify CIP-003 to apply malicious communications detection requirements to any remote access that uses routable protocols outside BES assets containing low impact BCS.

Roger Fradenburgh, On Behalf of: Nicholas Lauriat, Network and Security Technologies, 1

- 0 - 0

N/A

Daniel Mason, Portland General Electric Co., 6, 4/15/2022

- 0 - 0