Real-Time Comments
2016-02 Modifications to CIP Standards | Technical Rationale and Justification and Implementation Guidance for CIP-012-1
Description:
Start Date: 11/20/2017
End Date: 12/11/2017
Associated Ballots:
Ballot Name | Project | Standard | Pool Open | Pool Close | Voting Start | Voting End |
---|
Hot Answers
Tacoma Power endorses the draft comments shared with it by Salt River Project (SRP), which follow:
While the Technical Rationale and Justification for CIP-012 goes into great detail for R1 to give an understanding and overview of the rationale behind the scope, demarcation points, and the need for roles and responsibilities, SRP asserts it did not properly address Requirement 2.
While physical protections may satisfy the objective of protecting confidentiality between Control Centers owned by the same Registered Entity, it does not address non-repudiation in any situation, and therefore integrity as it was defined by NIST 800-53, Revision 4, page B-6. SRP requests the SDT provide more rationale and justification as to how these protections are being required “…in a manner that reflects the risks posed to bulk electric system reliability,” as stated on page 12 of FERC Order No. 822.
Rick Applegate, On Behalf of: Rick Applegate, , Segments 1, 3, 4, 5, 6
- 0 - 0
Brandon Cain, On Behalf of: Southern Company - Southern Company Services, Inc., FRCC, MRO, WECC, Texas RE, SERC, SPP RE, Segments 1, 3, 5, 6
- 0 - 0
Other Answers
The technical guidance sections do a suitable job of describing the problem that the SDT is being asked to solve. The rationale for the alignment, however, introduces concern given that the term “Real-time monitoring”, while aligned with IRO and TOP terminology, is not itself a NERC-defined term and is also being further modified to create another new “Real-time monitoring and control” undefined term. Given that the term is already being changed, CHPD requests that the STD instead consider creating a new “BES data” (a term used by the SDT in the Draft 2 Unofficial Comment Form) NERC Glossary term to be used to clearly scope the data in question. Here is a potential, admittedly simple, initial definition to consider:
BES Data – Electronic data used by BES Cyber Systems to perform Supervisory Control and Data Acquisition (SCADA).
The intent of the concept of “demarcation points” is well-reasoned and CHPD supports this identification capability. CHPD requests that the Technical Rationale and Justification (TR&J) for this section be more clearly aligned with the Requirement R1.2, which does not currently limit the scope to the Responsible Entity’s Control Center. Consider the following revision:
“1.2 Identification of the Responsible Entity’s demarcation point(s)…”
A change to a demarcation point in one system should not create a paperwork or compliance issue for a neighbor or vice versa. Alternatively, consider defining the term “demarcation point” in the NERC glossary to identify the scope within the definition of the term, rather than in the language of the standard.
Chelan PUD, Segment(s) 5, 3, 1, 6, 11/13/2017
- 0 - 0
This is reasonable given that some of the communications may flow on third-party networks. That said, there seems to be no discussion of protecting the communications devices themselves. Recommend taking a “high watermark” approach to categorizing the importance and risk of communication systems. Many utilities use internal communications between their PCC and BCC. If those links are not trusted and require the protections of CIP-012, why trust the substation SCADA links feeding data to the control centers? Being more prescriptive would be helpful. Is the SDT mandating encryption? What physical protections would be sufficient? Is OPGW fiber “protected” or just “difficult?”
John Tolo, On Behalf of: John Tolo, , Segments 1
- 0 - 0
Page 5 (Control Center Ownership) - Recommend changing ‘ensure adequate protection is applied’ to ‘ensure the security objective is met’ in the sentence, ‘It is strongly recommended, however, that these partnering entities develop agreements, or use existing ones, to define responsibilities to ensure adequate protection is applied.’
Steven Rueckert, On Behalf of: Western Electricity Coordinating Council, , Segments 10
- 0 - 0
DTE Energy - DTE Electric, Segment(s) 5, 4, 3, 2/27/2017
- 0 - 0
Reclamation also recommends the Drafting Team state clearly that examples provided in Technical Rationale and Justification documents are neither mandatory, nor enforceable, nor the only method of achieving compliance.
Richard Jackson, On Behalf of: U.S. Bureau of Reclamation, , Segments 1, 5
- 0 - 0
The California ISO supports the comments of the IRC Security Working Group (SWG)
Richard Vine, On Behalf of: Richard Vine, , Segments 2
- 0 - 0
Glen Farmer, On Behalf of: Avista - Avista Corporation, , Segments 1, 3, 5
- 0 - 0
Austin Energy (AE) generally agrees with the Draft 2 revision. However, the SDT should define the new terms “monitoring data” and “control data” in the NERC Glossary. Additionally, the concept of “demarcation point(s)” is unclear. The Standard should indicate a Registered Entity should identify the Cyber Asset at which the Entity begins protected data and ceases to protect data. The current wording implies each entity should document its demarcation point and any demarcation point(s) at a neighboring system. A change to a demarcation point for one entity should not create a paperwork or compliance issue for a neighbor. Alternatively, the SDT could define “demarcation point.”
Also, while the Technical Rationale and Justification for CIP-012 addresses R1 (scope, demarcation points, roles and responsibilities), it does not properly address R2. While physical protections may protect confidentiality between Control Centers owned by the same entity, it does not address non-repudiation and, therefore, integrity as defined by NIST 800-53, Revision 4, page B-6. AE asks the SDT to provide additional rationale and justification regarding how the protections are required “…in a manner that reflects the risks posed to bulk electric system reliability,” as stated on page 12 of FERC Order No. 822.
Andrew Gallo, On Behalf of: Andrew Gallo, , Segments 1, 3, 4, 5, 6
- 0 - 0
Vivian Moser, On Behalf of: Vivian Moser, , Segments 1, 3, 5, 6
- 0 - 0
Eleanor Ewry, On Behalf of: Eleanor Ewry, , Segments 1, 3, 5
- 0 - 0
N&ST believes the draft Technical Rationale and Justification fails to address the applicability of CIP-012 to the exchange of Real-time Assessment data between a BES Control Center and a third party provider of such data. At the same time, the draft Implementation Guidance document clearly indicates that the SDT believes this scenario would be in scope. If this is in fact true, then both the Technical Rationale and Justification and CIP-012 standard document should include explicit statements to that effect.
Nicholas Lauriat, On Behalf of: Network and Security Technologies, , Segments 1
- 0 - 0
The SPP Standards Review Group proposes to include the defined terms “Confidentiality” and “Integrity” in the NERC Glossary of Terms or, at a minimum, define the terms in the body of the standard. The current definitions are stated in the National Institute of Standards and Technology’s (NIST) Special Publication 800-53A, Revision 4 (as footnoted in the Technical Rationale Documentation); however, the NIST document is non-governing and could be revised outside the purview of NERC, which could have a negative impact on an entity’s compliance with standards such as CIP-012. The SPP Standards Review Group would recommend utilizing the definitions for “Confidentiality” and “Integrity” as stated in the current Technical Rational and Justification for CIP-012.
Additionally, the SPP Standards Review Group would recommend the same course of action be applicable to the term “Demarcation Point.”
SPP Standards Review Group, Segment(s) 0, 12/10/2017
- 0 - 0
See comments from the MRO NSRF for the ballot conducted for CIP-012-1 which closed on December 11, 2017.
Don Schmit, On Behalf of: Don Schmit, , Segments 1, 3, 5
- 0 - 0
We do not agree with two separate requirements, one for a plan and one to implement. We recommend following precedent in the other CIP standards, for example, CIP-004-011. The obligation can be accomplished with one requirement, as follows. “The Responsible Entity shall implement one or more documented process(es) to mitigate the risk of the unauthorized disclosure or modification of Real-time Assessments and Real-time monitoring and control data while being transmitted between any Control Centers, except under CIP Exceptional Circumstances. This excludes oral communications. The process(es) shall identify: 1.1 security protection used to mitigate risk of unauthorized disclosure or modification of Real-time Assessment and Real-time monitoring and control data while being transmitted between Control Centers. 1.2 demarcation point(s) where security protection is applied for transmitting Real-time Assessment and Real-time monitoring and control data between Control Centers. Demarcation points identified by the Responsible Entity do not add additional Cyber Assets to the scope of the CIP Reliability Standards; and 1.3 roles and responsibilities of each Responsible Entity for applying security protection to the transmission of Real-time Assessment and Real-time monitoring and control data between Control Centers, when the Control Centers are owned or operated by different Responsible Entities.” This also includes important scoping from the implementation guidance that belongs in the requirement, that demarcation points don’t add additional Cyber Assets to the scope of the CIP standards.
Terry Harbour, On Behalf of: Berkshire Hathaway Energy - MidAmerican Energy Co., , Segments 1, 3
- 0 - 0
While the Technical Rationale and Justification for CIP-012 goes into great detail for R1 to give an understanding and overview of the rationale behind the scope, demarcation points, and the need for roles and responsibilities, SRP asserts it did not properly address Requirement 2.
While physical protections may satisfy the objective of protecting confidentiality between Control Centers owned by the same Registered Entity, it does not address non-repudiation in any situation, and therefore integrity as it was defined by NIST 800-53, Revision 4, page B-6. SRP requests the SDT provide more rationale and justification as to how these protections are being required “…in a manner that reflects the risks posed to bulk electric system reliability,” as stated on page 12 of FERC Order No. 822.
Lona Calderon, On Behalf of: Salt River Project, WECC, Segments 1, 3, 5, 6
- 0 - 0
Support Terry Harbour comments (Berhshire Hathaway Company - MidAmerican Energy Company)
Annette Johnston, On Behalf of: Annette Johnston, , Segments 1, 3
- 0 - 0
Daniel Gacek, On Behalf of: Exelon, , Segments 1, 3, 5, 6
- 0 - 0
CenterPoint Energy Houston Electric, LLC (“CenterPoint Energy”) does not agree with certain comments in the draft Technical Rationale and Justification. As detailed in its Comment Form for proposed CIP-012-1, CenterPoint Energy recommends that the phrase “and control” be removed from proposed Requirement R1 on page 4 of the draft Technical Rationale and Justification. Inclusion of this phrase may create confusion and does not align with TOP-003 and IRO-010 data specification Requirements. Additionally, the phrase was not mentioned in FERC Order 822. Thus, CenterPoint Energy recommends corresponding revisions to the Technical Rational and Justification.
The SDT’s justification on page 5 of the draft Technical Rationale and Justification for adding “and control” to “Real-time monitoring and control data” is unclear and confusing. The SDT recognizes that “in practice Real-time control data is not transmitted separately from Real-time monitoring data.” Given this practice, the introduction of the concept of separately transmitted “Real-time control data” may create confusion on whether there are additional data specification responsibilities besides those detailed in TOP-003 and IRO-010.
To align with the revisions recommended above and in its Comment Form for proposed CIP-012-1, CenterPoint Energy also recommends that the following sentences be removed from the first paragraph of page 5 of the draft Technical Rationale and Justification:
“The SDT notes that it expanded the phrase ‘Real-time monitoring’ from TOP-003 and IRO-010 to ‘Real-time monitoring and control’ data.”
“However, the SDT wanted to ensure that Real-time control data was included regardless of whether or not it is transmitted along with Real-time monitoring data.”
CenterPoint Energy believes the rest of the first paragraph on page 5 is appropriate to be included because it states the SDT’s thought process and concern.
Lan Nguyen, On Behalf of: CenterPoint Energy Houston Electric, LLC, Texas RE, Segments 1
- 0 - 0
Texas RE is concerned about the use of the term “or” as used in Requirement R1. Please see Texas RE’s comments for Question #1 on the unofficial comment form for the comment period ending on December 11, 2017.
Texas RE also has a concern about the difference between monitoring and control data. On page 5 of the Technical Rationale, the SDT notes that it expanded the phrase “Real-time monitoring” data from TOP-003 and IRO-010 to “Real-time monitoring and control” data. The SDT was concerned that data transmitted between Control Centers that results in the physical operation of BES Elements was not explicitly included in Real-time monitoring data. The SDT understands that in practice Real-time control data is not transmitted separately from Real-time monitoring data. However, the SDT wanted to ensure that Real-time control data was included regardless of whether or not it is transmitted along with Real-time monitoring data. If entities only transmit Real-time control data along with Real-time monitoring data, then the SDT does not intend for such entities to identify additional data beyond that Real-time monitoring data already included in the data specifications for TOP-003 and IRO-010. Texas RE is concerned that if there is a need to expand the phrase to include control data in CIP-012-1, there might also be a need in IRO-010 and TOP-003.
Rachel Coyne, On Behalf of: Texas Reliability Entity, Inc., , Segments 10
- 0 - 0
Under the General Considerations section of the Technical Rationale, Xcel Energy has concerns with implementation of this Standard as related to the term and definition of Control Center. Specifically, we are concerned with the definition of an "associated data center" as part of the Control Center. The Standard does not appear to apply to communication between the control center and a field device (per reference model on page 5 of Technical Rationale). However, if we have a Control Center communicating with a device that aggregates multiple field devices, is that aggregating device location considered an associated data center?
Under the Alignment with IRO and TOP Standards, we believe that the types of data to be within scope, as identified by data specification lists originating from TOP-003 and IRO-010 are not specific enough to determine or limit the types of data or communication methods that would need to be protected as Real Time Assessments, Real Time Monitoring, or Control Data. These lists contain data and methods of communicating data that Xcel Energy would not classify as Real Time Assessment, Real Time Monitoring, or Control Data. Xcel Energy's concern is that NERC and Regional Entities may. The inclusion of all data types and methods on these lists could bring systems like corporate email into scope, which we would adamantly oppose. We suggest adding further clarification as to what types of data are included as Real Time Assessment, Real Time Monitoring, and Control Data.
Amy Casuscelli, On Behalf of: Xcel Energy, Inc. - MRO, WECC, SPP RE - Segments 1, 3, 5, 6
- 0 - 0
We support SRP and Chelan PUD comments.
Seattle City Light Ballot Body, Segment(s) 1, 4, 6, 5, 3, 12/2/2016
- 0 - 0
Laurie Williams, On Behalf of: Laurie Williams, , Segments 1, 3
- 0 - 0
Douglas Webb, On Behalf of: Great Plains Energy - Kansas City Power and Light Co., SPP RE, Segments 1, 3, 5, 6
- 0 - 0
David Ramkalawan, On Behalf of: David Ramkalawan, , Segments 5
- 0 - 0
Leonard Kula, On Behalf of: Independent Electricity System Operator, , Segments 2
- 0 - 0
ERCOT signs onto the comments of the SRC/ITC/SWG of the IRC, pasted below.
The SRC & ITC SWG offers the following comments and recommendations. To solidify the intent of the SDT, as noted in the response to comments, the SRC & ITC SWG recommend that it be clarified in the Technical Rationale and Justification that CIP-012-1 is a standalone Standard similar to CIP-014 and is not intended to increase the scope of applicable systems to be protected under CIP-003 thru CIP-011.
Elizabeth Axson, On Behalf of: Elizabeth Axson, , Segments 2
- 0 - 0
RSC no Dominion and ISO-NE, Segment(s) 10, 2, 4, 5, 6, 7, 1, 3, 12/11/2017
- 0 - 0
Comments: The SRC & ITC SWG offers the following comments and recommendations. To solidify the intent of the SDT, as noted in the response to comments, the SRC & ITC SWG recommend that it be clarified in the Technical Rationale and Justification that CIP-012-1 is a standalone Standard similar to CIP-014 and is not intended to increase the scope of applicable systems to be protected under CIP-003 thru CIP-011.
SRC + SWG , Segment(s) 2, 3, 1, 0, 10/30/2017
- 0 - 0
Hot Answers
Tacoma Power endorses the draft comments shared with it by Salt River Project (SRP), which follow:
The Implementation Guidance states “The protection must also meet the security objective of mitigating the risk of unauthorized disclosure or modification of applicable data while in transit between Control Centers for the entire distance between CIP-012-1 demarcation points.” The document also describes a situation where Entity Alpha exchanges data with Entity Beta through a “3rd party network.” The guidance asserts “a number of security controls may be leveraged such as network segmentation and system access control to protect the data as it transits the 3rd party network.” However, the document does not describe the implications if the third part circumvents these controls. Additionally, these controls within the 3rd party network do not address non-repudiation, and therefore integrity as it was defined by NIST 800-53, Revision 4, page B-6. SRP asserts more explanation is required within the Implementation Guidance to explain how the example approaches satisfy the security objective. If the approaches indeed satisfy the security objective, then the requirement must be updated to fit the scenario.
Although the SDT states it does not specify controls, the only examples provided in the implementation guidance includes encryption. If there are other methods available other than encryption to achieve the security objective, please provide them.
Rick Applegate, On Behalf of: Rick Applegate, , Segments 1, 3, 4, 5, 6
- 0 - 0
Brandon Cain, On Behalf of: Southern Company - Southern Company Services, Inc., FRCC, MRO, WECC, Texas RE, SERC, SPP RE, Segments 1, 3, 5, 6
- 0 - 0
Other Answers
The Technical Rationale and Justification (TR&J) does not currently provide any technical implementation guidelines to identify where protections may be applied under the language of the CIP-012-1 standard. CHPD requests the addition of one or more sample connectivity drawings to the TR&J that depict compliant topology configurations showing the R1.1 security protection and R1.2 demarcation point placement that could be applied to an existing pair of in-scope Control Centers, including the associated BCS, ESP (EAP/EACMS), and PSP boundaries.
Chelan PUD, Segment(s) 5, 3, 1, 6, 11/13/2017
- 0 - 0
Sometimes the lack of specifics causes confusion and lost time. Being more specific about the technological controls would be more helpful. For instance, PCI-DSS specifically calls out when encryption is needed for data at-rest and in-transit. If the intent is to encrypt data, it would be better to say so up-front and specify the protection boundaries. Some entities may decide to implement different protection mechanisms that may not be sufficient from a security perspective and then through the course of presentations and guidance have to re-work.
TEP appreciates the opportunity to comment.
John Tolo, On Behalf of: John Tolo, , Segments 1
- 0 - 0
Page 1 Introduction - Recommend including in the Introduction the same paragraph found in the Technical Rationale and Justification Introduction as it provides an important perspective that appears to not be fully understood.
‘Although the Commission directed NERC to develop modifications to CIP-006, the SDT determined that modifications to CIP-006 would not be appropriate. There are differences between the plan(s) required to be developed and implemented for CIP-012-1 and the protection required in CIP-006-6 Requirement R1 Part 1.10. CIP-012-1 Requirements R1 and R2 protect the applicable data during transmission between two separate Control Centers. CIP-006 Requirement R1 Part 1.10 protects nonprogrammable communication components within an Electronic Security Perimeter (ESP) but outside of a Physical Security Perimeter (PSP). The transmission of applicable data between Control Centers takes place outside of an ESP. Therefore, the protection contained in CIP-006-6 Requirement R1 Part 1.10 does not apply.’
Steven Rueckert, On Behalf of: Western Electricity Coordinating Council, , Segments 10
- 0 - 0
DTE Energy - DTE Electric, Segment(s) 5, 4, 3, 2/27/2017
- 0 - 0
Richard Jackson, On Behalf of: U.S. Bureau of Reclamation, , Segments 1, 5
- 0 - 0
The California ISO supports the comments of the IRC Security Working Group (SWG)
Richard Vine, On Behalf of: Richard Vine, , Segments 2
- 0 - 0
Glen Farmer, On Behalf of: Avista - Avista Corporation, , Segments 1, 3, 5
- 0 - 0
AE requests a formal definition of terms describing the data in question (e.g. “BES data” to address “monitoring” and “control” data types in a single definition. BES Data could be defined as, “Electronic data in BES Cyber Systems used to perform Supervisory Control and Data Acquisition (SCADA).” If the STD believes monitoring and control data should be defined separately, AE requests new NERC Glossary terms for “monitoring data” and “control data.”
Additionally, the Implementation Guidance states “The protection must also meet the security objective of mitigating the risk of unauthorized disclosure or modification of applicable data while in transit between Control Centers for the entire distance between CIP-012-1 demarcation points.” The document describes a situation where Entity Alpha exchanges data with Entity Beta through a “3rd party network.” The guidance asserts “a number of security controls may be leveraged such as network segmentation and system access control to protect the data as it transits the 3rd party network.” The document does not, however, describe the implications of the 3rd party circumventing those controls. Additionally, the controls in the 3rd party network do not address non-repudiation and, therefore, integrity as defined in NIST 800-53, Revision 4, page B-6. AE requests additional explanation to explain how the example approaches meet the security objective.
Although the SDT states it does not specify controls, the only examples provided include encryption. If other methods exist, the SDT should provide them.
Andrew Gallo, On Behalf of: Andrew Gallo, , Segments 1, 3, 4, 5, 6
- 0 - 0
Vivian Moser, On Behalf of: Vivian Moser, , Segments 1, 3, 5, 6
- 0 - 0
Further details about the technological controls required to meet the requirements would be helpful. Providing additional, specific examples about appropriate approaches would help ensure entities implement sufficient protection mechanisms, per the requirements.
Eleanor Ewry, On Behalf of: Eleanor Ewry, , Segments 1, 3, 5
- 0 - 0
N&ST believes that Figure 4 (“Network Diagram depicting communications through a 3rd party”) and its accompanying discussion describe a scenario for which CIP-012, as presently written, would not apply. As the figure is presently drawn, Control Centers “Alpha” and “Beta” are not communicating, that is, exchanging data, with each other. Each one is communicating with the “3rd party.” The fact that the 3rd party is presumably forwarding data that it has processed in some fashion to Beta after receiving it from Alpha, or vice-versa, does not, in N&ST’s opinion, constitute communications between two BES Control Centers.
If the SDT believes that communication links carrying Real-time Assessment data between BES Control Centers and 3rd party providers of such data, then CIP-012-1 should be modified to make this an explicit requirement.
Nicholas Lauriat, On Behalf of: Network and Security Technologies, , Segments 1
- 0 - 0
SPP Standards Review Group, Segment(s) 0, 12/10/2017
- 0 - 0
Don Schmit, On Behalf of: Don Schmit, , Segments 1, 3, 5
- 0 - 0
We do not agree with two separate requirements, one for a plan and one to implement. We recommend following precedent in the other CIP standards, for example, CIP-004-011. The obligation can be accomplished with one requirement, as follows. “The Responsible Entity shall implement one or more documented process(es) to mitigate the risk of the unauthorized disclosure or modification of Real-time Assessments and Real-time monitoring and control data while being transmitted between any Control Centers, except under CIP Exceptional Circumstances. This excludes oral communications. The process(es) shall identify: 1.1 security protection used to mitigate risk of unauthorized disclosure or modification of Real-time Assessment and Real-time monitoring and control data while being transmitted between Control Centers. 1.2 demarcation point(s) where security protection is applied for transmitting Real-time Assessment and Real-time monitoring and control data between Control Centers. Demarcation points identified by the Responsible Entity do not add additional Cyber Assets to the scope of the CIP Reliability Standards; and 1.3 roles and responsibilities of each Responsible Entity for applying security protection to the transmission of Real-time Assessment and Real-time monitoring and control data between Control Centers, when the Control Centers are owned or operated by different Responsible Entities.” This also includes important scoping from the implementation guidance that belongs in the requirement, that demarcation points don’t add additional Cyber Assets to the scope of the CIP standards. Also, the Proposed Reliability Standard lacks sufficient specificity (i.e., sufficient to stand on its own), without an endorsed Technical Rationale and Implementation Guidance. Relative to the draft Implementation Guidance document, MEC agrees with EEI that Industry will likely find it difficult to make any final judgments on the proposed Reliability Standard without NERC's endorsement of the draft Implementation Guidance. We trust that once the Proposed Reliability Standard gets closer to a final ballot NERC will endorse the final draft of the Implementation Guidance. In the event that doesn't occur, we fear the approval of this standard may be at risk.
Terry Harbour, On Behalf of: Berkshire Hathaway Energy - MidAmerican Energy Co., , Segments 1, 3
- 0 - 0
The Implementation Guidance states “The protection must also meet the security objective of mitigating the risk of unauthorized disclosure or modification of applicable data while in transit between Control Centers for the entire distance between CIP-012-1 demarcation points.” The document also describes a situation where Entity Alpha exchanges data with Entity Beta through a “3rd party network.” The guidance asserts “a number of security controls may be leveraged such as network segmentation and system access control to protect the data as it transits the 3rd party network.” However, the document does not describe the implications if the third part circumvents these controls. Additionally, these controls within the 3rd party network do not address non-repudiation, and therefore integrity as it was defined by NIST 800-53, Revision 4, page B-6. SRP asserts more explanation is required within the Implementation Guidance to explain how the example approaches satisfy the security objective. If the approaches indeed satisfy the security objective, then the requirement must be updated to fit the scenario.
Although the SDT states it does not specify controls, the only examples provided in the implementation guidance includes encryption. If there are other methods available other than encryption to achieve the security objective, please provide them.
Lona Calderon, On Behalf of: Salt River Project, WECC, Segments 1, 3, 5, 6
- 0 - 0
Support Terry Harbour comments (Berhshire Hathaway Company - MidAmerican Energy Company)
Annette Johnston, On Behalf of: Annette Johnston, , Segments 1, 3
- 0 - 0
Exelon generally agrees with the approach in the draft Implementation Guidance, noting the following concerns and suggestions.
We have a concern that the CIP-012-1 Standard may be approved prior to NERC endorsement of the Technical Rationale and Justification and the Implementation Guidance for CIP-012. Our approval of the CIP-012-1 Standard language as presented is in part predicated upon the clarifications present within the Implementation Guidance. We would expect to see the endorsement by NERC of these supporting documents before we vote for final approval of the Standard.
Within the Standard, Technical Rationale and Justification, and the Implementation Guidance, there is no mention of the scenario of data transmission between a Control Center and its associated Data Center(s) located in separate physical locations. Clarification of whether this intra-Control Center data transmission is in scope seems appropriate.
Our SMEs raised questions about data not currently determined to have a 15-minute impact and therefore out of scope for CIP-002 thru CIP-011, e.g. synchrophasers data. Can we automatically assume then, that this same data is also currently out of scope for CIP-012? Looking for clarification on this question within the Standard or supporting documents.
Daniel Gacek, On Behalf of: Exelon, , Segments 1, 3, 5, 6
- 0 - 0
For the same reasons discussed in its Response to Question No. 1 and in its Comment Form for proposed CIP-012-1, CenterPoint Energy recommends that the phrase “and control” be removed from Requirement R1on page 4 of the draft Implementation Guidance..
In accordance with Requirement R1.3, Responsible Entities are required to identify roles and responsibilities for applying security protections. However, on page 5 of the Implementation Guidance, consideration of the following situations was listed: (1) configuration of security protocols, (2) responding to communication failures, and (3) responding to Cyber Security Incidents. Items (2) and (3) go beyond the scope of Requirement R1.3 and, therefore, should be removed from the Implementation Guidance.
Similarly, on page 9, the following example goes beyond the scope of Requirement 1.3 and should be removed from the Implementation Guidance:
“Entity Alpha and Entity Beta have agreed to a 30 character pre-shared key for coordinated response to any communication failures. They have also exchanged contact information for their Security Operations Centers to enable a coordinated response to any suspected Cyber Security Incidents.”
Page 8 and page 13 lists “AES-128 encryption” as an example of protection; however, 128 bit encryption is the lowest key length. CenterPoint Energy recommends removing “AES-128” and only stating the word “encryption.”
In the last paragraph of page 9, regarding communications through a third party, the Implementation Guidance should recommend stronger controls around protecting the data being transmitted through a third party communication link. For example, Entity Alpha and Entity Beta should establish agreements with the 3rd party responsible for the communication to protect the data transiting its network. The last sentence, “The 3rd party may take responsibility for protecting the data transiting its network” does not allow for adequate protection of the data.
Lan Nguyen, On Behalf of: CenterPoint Energy Houston Electric, LLC, Texas RE, Segments 1
- 0 - 0
Texas RE has the following comments regarding the implementation guidance:
In the Identification of Security Protection section on page 6: “Alternatively, a Responsible Entity may demonstrate implementation through monitoring of the security control such as a report generated from an automated tool that monitors the encryption service used to protect a communications link.”
Texas RE recommends adding monitoring and logging, monitors and logs.
In the Reference Model Discussion for Requirement R1 section on page 7:
“Additionally, Entity Alpha does not need to consider any communications to other non-Control Center facilities such as generating plants or substations. These communications are out of scope for CIP-012-1.”
Although this may be out-of-scope as a best security practice, Texas RE recommend Entity Alpha should “consider any communications to other non-Control Center facilities such as generating plants or substations.”
In the Identification of Security Protection section on page 13:
“When physical security controls are used, Entity Alpha may demonstrate the implementation of physical protection using a floorplan diagram showing the physical access controls in place.”
Texas RE suggests including other types of evidence with a floorplan as a floorplan diagram alone would not be sufficient.
Rachel Coyne, On Behalf of: Texas Reliability Entity, Inc., , Segments 10
- 0 - 0
Xcel Energy agrees that the approaches offered in the CIP-012-2 Implementation Guidance are non-prescriptive and can be sufficient models to be used in implementation. However, Xcel Energy cannot agree with the proposed timeline of 24 months. We share real-time data with Registered Entities (REs) such as the Reliability Coordinators (RCs) including MISO, SPP and PEAK. Additionally, we would share data with many utilities with Control Centers across our service territory. Finding a common technological solution to implement the proposed mitigating activities in the Requirements will take a substantial effort on the part of all REs. Once a common technology and all legal agreements between REs are in place, Xcel Energy may still have to purchase and implement those technology solutions.
Xcel Energy stakeholders suggest that NERC should advice and work with all RCs to agree upon a common technology first and then drive those solutions from the RC down to each utility in scope.
Amy Casuscelli, On Behalf of: Xcel Energy, Inc. - MRO, WECC, SPP RE - Segments 1, 3, 5, 6
- 0 - 0
We support SRP and Chelan PUD comments.
Seattle City Light Ballot Body, Segment(s) 1, 4, 6, 5, 3, 12/2/2016
- 0 - 0
While PNMR agrees with the example approaches in the draft Implementation Guidance there is one scenario that does not appear and possible should. Some entities use mailbox or virtual RTUs to communicate data between Control Centers either as redundant method to or in lieu of ICCP. Some Entities may forget that such communication could be in-scope of the standard especially if “Real-time Assessment and Real-time monitoring and control data” is passed through these mailbox or virtual RTUs. Typically these have points to point serial protocols and those serial connections would need to have protections applied. While PNMR does not know how many still use mailbox or virtual RTUs as an alternate means, it is something the drafting team should take into consideration.
Laurie Williams, On Behalf of: Laurie Williams, , Segments 1, 3
- 0 - 0
Douglas Webb, On Behalf of: Great Plains Energy - Kansas City Power and Light Co., SPP RE, Segments 1, 3, 5, 6
- 0 - 0
David Ramkalawan, On Behalf of: David Ramkalawan, , Segments 5
- 0 - 0
Leonard Kula, On Behalf of: Independent Electricity System Operator, , Segments 2
- 0 - 0
Comments: There are concerns regarding the statement, “Demarcation points identified by the Responsible Entity do not add additional assets to the scope of the CIP Reliability Standards.” Entities may already include the demarcation points as Cyber Asset relevant to CIP-002 thru CIP-011. The statement could be revised as, “Demarcation points identified by the Responsible Entity are not intended to add additional assets to the scope of the CIP Reliability Standards.”
With regards to the references models and narrative, it would be helpful to have the narrative and the reference model together. It is cumbersome to keep skipping back and forth in the document.
Elizabeth Axson, On Behalf of: Elizabeth Axson, , Segments 2
- 0 - 0
RSC no Dominion and ISO-NE, Segment(s) 10, 2, 4, 5, 6, 7, 1, 3, 12/11/2017
- 0 - 0
Comments: There are concerns regarding the statement, “Demarcation points identified by the Responsible Entity do not add additional assets to the scope of the CIP Reliability Standards.” Entities may already include the demarcation points as Cyber Asset relevant to CIP-002 thru CIP-011. The statement could be revised as, “Demarcation points identified by the Responsible Entity is not intended to add additional assets to the scope of the CIP Reliability Standards.”
With regards to the references models and narrative, it would be helpful to have the narrative and the reference model together. It is cumbersome to keep skipping back and forth in the document.
SRC + SWG , Segment(s) 2, 3, 1, 0, 10/30/2017
- 0 - 0