Real-Time Comments
2015-02 EOP Periodic Review | EOP-008-1
Description:
Start Date: 03/27/2015
End Date: 05/11/2015
Associated Ballots:
Ballot Name | Project | Standard | Pool Open | Pool Close | Voting Start | Voting End |
---|
Hot Answers
Joshua Andersen, On Behalf of: Salt River Project, WECC, Segments 1, 3, 5, 6
- 0 - 0
Daniela Hammons, On Behalf of: CenterPoint Energy Houston Electric, LLC, Texas RE, Segments 1
- 0 - 0
Other Answers
Dennis Minton, On Behalf of: Dennis Minton, , Segments 1, 3
- 0 - 0
John Fontenot, On Behalf of: John Fontenot, , Segments 1, 5
- 0 - 0
Jeff Wells, On Behalf of: Grand River Dam Authority, , Segments 1, 3
- 0 - 0
Leonard Kula, On Behalf of: Independent Electricity System Operator, , Segments 2
- 0 - 0
Si Truc Phan, On Behalf of: Hydro-Qu?bec TransEnergie, NPCC, Segments 1
- 0 - 0
MRO-NERC Standards Review Forum (NSRF), Segment(s) 3, 4, 5, 6, 1, 2, 4/8/2015
- 0 - 0
Colorado Springs Utilities, Segment(s) 6, 3, 5, 5/6/2015
- 0 - 0
Dominion Collective Group, Segment(s) 1, 3, 5, 6, 5/7/2015
- 0 - 0
Thomas Foltz, On Behalf of: AEP, , Segments 3, 5
- 0 - 0
Brian Bartos, On Behalf of: Brian Bartos, , Segments 1, 3, 5
- 0 - 0
Joel Wise, On Behalf of: Tennessee Valley Authority - SERC - Segments 1, 3, 5, 6
- 0 - 0
Nick Vtyurin, On Behalf of: Manitoba Hydro - MRO - Segments 1, 3, 5, 6
- 0 - 0
christina bigelow, On Behalf of: christina bigelow, , Segments 2
- 0 - 0
Molly Devine, On Behalf of: Molly Devine, , Segments 1
- 0 - 0
NPCC Proj 2015-02 EOP-008-1, Segment(s) 10, 3, 2, 1, 9, 6, 5, 8, 5/11/2015
- 0 - 0
Mark Kenny, On Behalf of: Mark Kenny, , Segments 1, 3, 5
- 0 - 0
Matthew Beilfuss, On Behalf of: Wisconsin Energy Corporation, RF, Segments 3, 4, 5
- 0 - 0
ACES Standards Collaborators - EOP Project, Segment(s) 1, 4, 5, 3, 5/11/2015
- 0 - 0
Kathleen Black, On Behalf of: DTE Energy, RF, Segments 3, 4, 5
- 0 - 0
SPP Standards Review Group, Segment(s) 1, 3, 5, 5/11/2015
- 0 - 0
Jared Shakespeare, On Behalf of: Jared Shakespeare, , Segments 1
- 0 - 0
Rachel Coyne, On Behalf of: Texas Reliability Entity, Inc., , Segments 10
- 0 - 0
ISO/RTO Council Standards Review Committee, Segment(s) 2, 5/11/2015
- 0 - 0
RoLynda Shumpert, On Behalf of: SCANA - South Carolina Electric and Gas Co., SERC, Segments 1, 3, 5, 6
- 0 - 0
Sergio Banuelos, On Behalf of: Tri-State G and T Association, Inc., MRO, WECC, Segments 1, 3, 5
- 0 - 0
Leo Staples, On Behalf of: Leo Staples, , Segments 1, 3, 5, 6
- 0 - 0
Andrea Jessup, On Behalf of: Bonneville Power Administration, WECC, Segments 1, 3, 5, 6
- 0 - 0
Rick Applegate, On Behalf of: Rick Applegate, , Segments 1, 3, 4, 5, 6
- 0 - 0
minh pham, On Behalf of: Los Angeles Department of Water and Power, WECC, Segments NA - Not Applicable
- 0 - 0
Terri Pyle, On Behalf of: OGE Energy - Oklahoma Gas and Electric Co., , Segments 1, 3, 5, 6
- 0 - 0
Hot Answers
Joshua Andersen, On Behalf of: Salt River Project, WECC, Segments 1, 3, 5, 6
- 0 - 0
Daniela Hammons, On Behalf of: CenterPoint Energy Houston Electric, LLC, Texas RE, Segments 1
- 0 - 0
Other Answers
Dennis Minton, On Behalf of: Dennis Minton, , Segments 1, 3
- 0 - 0
John Fontenot, On Behalf of: John Fontenot, , Segments 1, 5
- 0 - 0
Jeff Wells, On Behalf of: Grand River Dam Authority, , Segments 1, 3
- 0 - 0
Leonard Kula, On Behalf of: Independent Electricity System Operator, , Segments 2
- 0 - 0
Si Truc Phan, On Behalf of: Hydro-Qu?bec TransEnergie, NPCC, Segments 1
- 0 - 0
MRO-NERC Standards Review Forum (NSRF), Segment(s) 3, 4, 5, 6, 1, 2, 4/8/2015
- 0 - 0
Colorado Springs Utilities, Segment(s) 6, 3, 5, 5/6/2015
- 0 - 0
Dominion Collective Group, Segment(s) 1, 3, 5, 6, 5/7/2015
- 0 - 0
Thomas Foltz, On Behalf of: AEP, , Segments 3, 5
- 0 - 0
Brian Bartos, On Behalf of: Brian Bartos, , Segments 1, 3, 5
- 0 - 0
Joel Wise, On Behalf of: Tennessee Valley Authority - SERC - Segments 1, 3, 5, 6
- 0 - 0
Nick Vtyurin, On Behalf of: Manitoba Hydro - MRO - Segments 1, 3, 5, 6
- 0 - 0
christina bigelow, On Behalf of: christina bigelow, , Segments 2
Final_Comment_Report_EOP0081_March_2015_ercot.docx
- 0 - 0
Molly Devine, On Behalf of: Molly Devine, , Segments 1
- 0 - 0
NPCC Proj 2015-02 EOP-008-1, Segment(s) 10, 3, 2, 1, 9, 6, 5, 8, 5/11/2015
- 0 - 0
Mark Kenny, On Behalf of: Mark Kenny, , Segments 1, 3, 5
- 0 - 0
Matthew Beilfuss, On Behalf of: Wisconsin Energy Corporation, RF, Segments 3, 4, 5
- 0 - 0
ACES Standards Collaborators - EOP Project, Segment(s) 1, 4, 5, 3, 5/11/2015
- 0 - 0
Kathleen Black, On Behalf of: DTE Energy, RF, Segments 3, 4, 5
- 0 - 0
SPP Standards Review Group, Segment(s) 1, 3, 5, 5/11/2015
- 0 - 0
Jared Shakespeare, On Behalf of: Jared Shakespeare, , Segments 1
- 0 - 0
Rachel Coyne, On Behalf of: Texas Reliability Entity, Inc., , Segments 10
- 0 - 0
ISO/RTO Council Standards Review Committee, Segment(s) 2, 5/11/2015
- 0 - 0
RoLynda Shumpert, On Behalf of: SCANA - South Carolina Electric and Gas Co., SERC, Segments 1, 3, 5, 6
- 0 - 0
Sergio Banuelos, On Behalf of: Tri-State G and T Association, Inc., MRO, WECC, Segments 1, 3, 5
- 0 - 0
Leo Staples, On Behalf of: Leo Staples, , Segments 1, 3, 5, 6
- 0 - 0
Andrea Jessup, On Behalf of: Bonneville Power Administration, WECC, Segments 1, 3, 5, 6
- 0 - 0
Rick Applegate, On Behalf of: Rick Applegate, , Segments 1, 3, 4, 5, 6
- 0 - 0
minh pham, On Behalf of: Los Angeles Department of Water and Power, WECC, Segments NA - Not Applicable
- 0 - 0
Terri Pyle, On Behalf of: OGE Energy - Oklahoma Gas and Electric Co., , Segments 1, 3, 5, 6
- 0 - 0
Hot Answers
SRP cannot support a revision of the standard without knowing the specifics of what is to be revised and what it is to be revised to. Attachment 1 serves as a guideline to determine if the Reliability Standard should be converted to the results-based standards format. It does not indicate what will be converted or what it would be converted to.
Joshua Andersen, On Behalf of: Salt River Project, WECC, Segments 1, 3, 5, 6
- 0 - 0
Daniela Hammons, On Behalf of: CenterPoint Energy Houston Electric, LLC, Texas RE, Segments 1
- 0 - 0
Other Answers
Dennis Minton, On Behalf of: Dennis Minton, , Segments 1, 3
- 0 - 0
John Fontenot, On Behalf of: John Fontenot, , Segments 1, 5
- 0 - 0
Jeff Wells, On Behalf of: Grand River Dam Authority, , Segments 1, 3
- 0 - 0
Leonard Kula, On Behalf of: Independent Electricity System Operator, , Segments 2
- 0 - 0
Si Truc Phan, On Behalf of: Hydro-Qu?bec TransEnergie, NPCC, Segments 1
- 0 - 0
MRO-NERC Standards Review Forum (NSRF), Segment(s) 3, 4, 5, 6, 1, 2, 4/8/2015
- 0 - 0
R1.1 – CSU does not understand the need to revise this sub-requirement. CSU believes it is clear as written.
Colorado Springs Utilities, Segment(s) 6, 3, 5, 5/6/2015
- 0 - 0
Dominion believes that the EOP PRT is asking that the SDT to introduce a specific time requirement to be contained in R1.1. We do not agree, believing that the current standard leaves that determination to the entity based upon its specific circumstance; based to a large extent, on its relationships with other entities (especially those that can provide some level of oversight or monitoring of the affected entity area).
Dominion Collective Group, Segment(s) 1, 3, 5, 6, 5/7/2015
- 0 - 0
Thomas Foltz, On Behalf of: AEP, , Segments 3, 5
- 0 - 0
Brian Bartos, On Behalf of: Brian Bartos, , Segments 1, 3, 5
- 0 - 0
Joel Wise, On Behalf of: Tennessee Valley Authority - SERC - Segments 1, 3, 5, 6
- 0 - 0
Nick Vtyurin, On Behalf of: Manitoba Hydro - MRO - Segments 1, 3, 5, 6
- 0 - 0
christina bigelow, On Behalf of: christina bigelow, , Segments 2
Final_Comment_Report_EOP0081_March_2015_ercot.docx
- 0 - 0
Molly Devine, On Behalf of: Molly Devine, , Segments 1
- 0 - 0
Agree.
Item b.--Agree.
Item c.--Agree.
The current language is clear: backup functionality to operate the power system is required for the amount of time that it takes to restore the primary control center functionality.
NPCC Proj 2015-02 EOP-008-1, Segment(s) 10, 3, 2, 1, 9, 6, 5, 8, 5/11/2015
- 0 - 0
Mark Kenny, On Behalf of: Mark Kenny, , Segments 1, 3, 5
- 0 - 0
Matthew Beilfuss, On Behalf of: Wisconsin Energy Corporation, RF, Segments 3, 4, 5
- 0 - 0
ACES Standards Collaborators - EOP Project, Segment(s) 1, 4, 5, 3, 5/11/2015
- 0 - 0
Kathleen Black, On Behalf of: DTE Energy, RF, Segments 3, 4, 5
- 0 - 0
We support the clarifying change to R1.1. It seems to streamline the intent of the requirement. Though perhaps the PRT could elaborate further on their thinking behind making this change as the intent of the change may be misunderstood.
SPP Standards Review Group, Segment(s) 1, 3, 5, 5/11/2015
- 1 - 0
R1.1 Agree with the PRT recommendation of striking “…for the time it takes to restore the primary control center functionality.”
Jared Shakespeare, On Behalf of: Jared Shakespeare, , Segments 1
- 0 - 0
Texas RE agrees that R1.1 should be clarified but striking the language does not provide enough clarity.
Rachel Coyne, On Behalf of: Texas Reliability Entity, Inc., , Segments 10
- 0 - 0
We believe that the current language is clear: backup functionality to operate the power system is required for the amount of time that it takes to restore the primary control center functionality.
ISO/RTO Council Standards Review Committee, Segment(s) 2, 5/11/2015
- 0 - 0
RoLynda Shumpert, On Behalf of: SCANA - South Carolina Electric and Gas Co., SERC, Segments 1, 3, 5, 6
- 0 - 0
Sergio Banuelos, On Behalf of: Tri-State G and T Association, Inc., MRO, WECC, Segments 1, 3, 5
- 0 - 0
Leo Staples, On Behalf of: Leo Staples, , Segments 1, 3, 5, 6
- 0 - 0
Andrea Jessup, On Behalf of: Bonneville Power Administration, WECC, Segments 1, 3, 5, 6
- 0 - 0
Rick Applegate, On Behalf of: Rick Applegate, , Segments 1, 3, 4, 5, 6
- 0 - 0
minh pham, On Behalf of: Los Angeles Department of Water and Power, WECC, Segments NA - Not Applicable
- 0 - 0
Terri Pyle, On Behalf of: OGE Energy - Oklahoma Gas and Electric Co., , Segments 1, 3, 5, 6
- 0 - 0
Hot Answers
The revision for R1, Part 1.1 appears to be gramatical in nature. It is unclear what the reasonings are for revisions to EOP-008-1. SRP does not see any other specifics in the recomendation for a revision.
Joshua Andersen, On Behalf of: Salt River Project, WECC, Segments 1, 3, 5, 6
- 0 - 0
Daniela Hammons, On Behalf of: CenterPoint Energy Houston Electric, LLC, Texas RE, Segments 1
- 0 - 0
Other Answers
Dennis Minton, On Behalf of: Dennis Minton, , Segments 1, 3
- 0 - 0
John Fontenot, On Behalf of: John Fontenot, , Segments 1, 5
- 0 - 0
Jeff Wells, On Behalf of: Grand River Dam Authority, , Segments 1, 3
- 0 - 0
Leonard Kula, On Behalf of: Independent Electricity System Operator, , Segments 2
- 0 - 0
Si Truc Phan, On Behalf of: Hydro-Qu?bec TransEnergie, NPCC, Segments 1
- 0 - 0
MRO-NERC Standards Review Forum (NSRF), Segment(s) 3, 4, 5, 6, 1, 2, 4/8/2015
- 0 - 0
R1.1 – CSU does not understand the need to revise this sub-requirement. CSU believes it is clear as written.
Colorado Springs Utilities, Segment(s) 6, 3, 5, 5/6/2015
- 0 - 0
Dominion Collective Group, Segment(s) 1, 3, 5, 6, 5/7/2015
- 0 - 0
Thomas Foltz, On Behalf of: AEP, , Segments 3, 5
- 0 - 0
Brian Bartos, On Behalf of: Brian Bartos, , Segments 1, 3, 5
- 0 - 0
Joel Wise, On Behalf of: Tennessee Valley Authority - SERC - Segments 1, 3, 5, 6
- 0 - 0
Nick Vtyurin, On Behalf of: Manitoba Hydro - MRO - Segments 1, 3, 5, 6
- 0 - 0
christina bigelow, On Behalf of: christina bigelow, , Segments 2
Final_Comment_Report_EOP0081_March_2015_ercot.docx
- 0 - 0
Molly Devine, On Behalf of: Molly Devine, , Segments 1
- 0 - 0
See the response to Question 1 above.
NPCC Proj 2015-02 EOP-008-1, Segment(s) 10, 3, 2, 1, 9, 6, 5, 8, 5/11/2015
- 0 - 0
Mark Kenny, On Behalf of: Mark Kenny, , Segments 1, 3, 5
- 0 - 0
Matthew Beilfuss, On Behalf of: Wisconsin Energy Corporation, RF, Segments 3, 4, 5
- 0 - 0
We agree that EOP-008-1 should be revised.
ACES Standards Collaborators - EOP Project, Segment(s) 1, 4, 5, 3, 5/11/2015
- 0 - 0
Kathleen Black, On Behalf of: DTE Energy, RF, Segments 3, 4, 5
- 0 - 0
SPP Standards Review Group, Segment(s) 1, 3, 5, 5/11/2015
- 0 - 0
Jared Shakespeare, On Behalf of: Jared Shakespeare, , Segments 1
- 0 - 0
Rachel Coyne, On Behalf of: Texas Reliability Entity, Inc., , Segments 10
- 0 - 0
See answer to question 1 above.
ISO/RTO Council Standards Review Committee, Segment(s) 2, 5/11/2015
- 0 - 0
RoLynda Shumpert, On Behalf of: SCANA - South Carolina Electric and Gas Co., SERC, Segments 1, 3, 5, 6
- 0 - 0
Sergio Banuelos, On Behalf of: Tri-State G and T Association, Inc., MRO, WECC, Segments 1, 3, 5
- 0 - 0
Leo Staples, On Behalf of: Leo Staples, , Segments 1, 3, 5, 6
- 0 - 0
Please change to wording of the question to clearly indicate the framework of the question is the initial recommendation decision regarding reaffirm/revise/retire of a Standard.
Andrea Jessup, On Behalf of: Bonneville Power Administration, WECC, Segments 1, 3, 5, 6
- 0 - 0
Rick Applegate, On Behalf of: Rick Applegate, , Segments 1, 3, 4, 5, 6
- 0 - 0
minh pham, On Behalf of: Los Angeles Department of Water and Power, WECC, Segments NA - Not Applicable
- 0 - 0
Terri Pyle, On Behalf of: OGE Energy - Oklahoma Gas and Electric Co., , Segments 1, 3, 5, 6
- 0 - 0
Hot Answers
Joshua Andersen, On Behalf of: Salt River Project, WECC, Segments 1, 3, 5, 6
- 0 - 0
Daniela Hammons, On Behalf of: CenterPoint Energy Houston Electric, LLC, Texas RE, Segments 1
- 0 - 0
Other Answers
Dennis Minton, On Behalf of: Dennis Minton, , Segments 1, 3
- 0 - 0
John Fontenot, On Behalf of: John Fontenot, , Segments 1, 5
- 0 - 0
Jeff Wells, On Behalf of: Grand River Dam Authority, , Segments 1, 3
- 0 - 0
Leonard Kula, On Behalf of: Independent Electricity System Operator, , Segments 2
- 0 - 0
Si Truc Phan, On Behalf of: Hydro-Qu?bec TransEnergie, NPCC, Segments 1
- 0 - 0
MRO-NERC Standards Review Forum (NSRF), Segment(s) 3, 4, 5, 6, 1, 2, 4/8/2015
- 0 - 0
No Comments
Colorado Springs Utilities, Segment(s) 6, 3, 5, 5/6/2015
- 0 - 0
The IERP (from this link (http://www.nerc.com/pa/Stand/Pages/Standards-Under-Development.aspx), select P81 and IERP Recommendations for Retirement), this includes R5 (P81), yet question 1 for the SME is marked “No”. Please explain.
Dominion Collective Group, Segment(s) 1, 3, 5, 6, 5/7/2015
- 0 - 0
While AEP does not object to the review of the standard for grammar, punctuation, syntax, etc., we would caution the team to not intentionally or unintentionally change the meaning of the standard or requirements to this recently vetted standard.
Thomas Foltz, On Behalf of: AEP, , Segments 3, 5
- 0 - 0
Brian Bartos, On Behalf of: Brian Bartos, , Segments 1, 3, 5
- 0 - 0
Joel Wise, On Behalf of: Tennessee Valley Authority - SERC - Segments 1, 3, 5, 6
- 0 - 0
Nick Vtyurin, On Behalf of: Manitoba Hydro - MRO - Segments 1, 3, 5, 6
- 0 - 0
christina bigelow, On Behalf of: christina bigelow, , Segments 2
- 0 - 0
Molly Devine, On Behalf of: Molly Devine, , Segments 1
- 0 - 0
NPCC Proj 2015-02 EOP-008-1, Segment(s) 10, 3, 2, 1, 9, 6, 5, 8, 5/11/2015
- 0 - 0
Mark Kenny, On Behalf of: Mark Kenny, , Segments 1, 3, 5
- 0 - 0
Matthew Beilfuss, On Behalf of: Wisconsin Energy Corporation, RF, Segments 3, 4, 5
- 0 - 0
(1) The standard lacks a guideline and technical basis section. The section should elaborate on the meaning of “annual” and “annually,” as well as provide guidance on instances when backup functionality takes longer than two hours to implement.
(2) Thank you for the opportunity to comment.
ACES Standards Collaborators - EOP Project, Segment(s) 1, 4, 5, 3, 5/11/2015
- 0 - 0
Kathleen Black, On Behalf of: DTE Energy, RF, Segments 3, 4, 5
- 0 - 0
We would suggest capitalizing the term ‘control center’ in sub-parts of 1.5, 1.6 of Requirement R1, Requirement R2, Requirement R3, Requirement R4, Requirement R6, and sub-part 7.1 of Requirement R7. Also, we would suggest the PRT review the use of the term ‘facility’ in Requirement R3 when describing control centers and backup control centers or “sites where backup functionality is located”. In some cases it may be appropriate to just remove the word “facility”. For example remove it after the phrase “control center” in the first sentence of R1. The use of the phrase “control center facility” could lead to different interpretations.
The reference to Power source(s) in R1.2.4 seems to indicate an inferred requirement for a backup facility to have redundant power sources. Whatever the intent, it is unclear. All of the other sub-requirements of R1 are explicitly required to be capabilities or tools that are required. Redundant power sources is not mentioned in any other requirement. We suggest the PRT review R1.2.4 for clarity.
In R2 we would like to see a change to clarify that the availability of the Operating Plan for the backup functionality can be available in hard copy or electronic copy at the primary and backup sites. This would be similar to proposed changes in EOP-005-2 and EOP-006-2.
SPP Standards Review Group, Segment(s) 1, 3, 5, 5/11/2015
- 1 - 0
Jared Shakespeare, On Behalf of: Jared Shakespeare, , Segments 1
- 0 - 0
Texas RE is concerned that the standard does not require a notification to affected entities when a Reliability Coordinator, Balancing Authority, and Transmission Operator has experienced a loss of its primary or backup functionality and that anticipates that the loss of primary or backup functionality will last for more than six calendar months. In addition, Texas RE believes that allowing an entity up to six calendar months to provide a plan to its Regional Entity when the functionality is lost, is excessive. Texas RE recommends the “Compliance Monitoring Process” section be consistent with other Standards being reviewed.
Rachel Coyne, On Behalf of: Texas Reliability Entity, Inc., , Segments 10
- 0 - 0
ISO/RTO Council Standards Review Committee, Segment(s) 2, 5/11/2015
- 0 - 0
RoLynda Shumpert, On Behalf of: SCANA - South Carolina Electric and Gas Co., SERC, Segments 1, 3, 5, 6
- 0 - 0
Sergio Banuelos, On Behalf of: Tri-State G and T Association, Inc., MRO, WECC, Segments 1, 3, 5
- 0 - 0
Leo Staples, On Behalf of: Leo Staples, , Segments 1, 3, 5, 6
- 0 - 0
None.
Andrea Jessup, On Behalf of: Bonneville Power Administration, WECC, Segments 1, 3, 5, 6
- 0 - 0
Rick Applegate, On Behalf of: Rick Applegate, , Segments 1, 3, 4, 5, 6
- 0 - 0
LADWP requests clarification on what a “unique task” will be defined as in the RSAW, maybe even add it to a future version of the NERC Glossary of Terms.
minh pham, On Behalf of: Los Angeles Department of Water and Power, WECC, Segments NA - Not Applicable
- 0 - 0
Terri Pyle, On Behalf of: OGE Energy - Oklahoma Gas and Electric Co., , Segments 1, 3, 5, 6
- 0 - 0